26
Example) Altering filter constant 5.0 (5 seconds) to 10.0
(10 seconds)
Key operation
Description
Press the SEL key for 3 seconds, and
P-n1 is displayed.
Press the SEL key repeatedly until
P-dF is displayed.
Press the or key to display
10.0.
Press the DATA key. Current data
is displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
ENT
SV
DATA
Input filter constant (Setting range: 0.0 to 900.0 sec.)
[Description]
• Input filter function is used to reduce
noise contained in input signal. In-
put filter constant is time constant.
For example, the following response
can be obtained by setting the input
filter constant to 10 seconds.
• The set value is the time to read 63%
(Y) on the controller for change in
PV of 100% (X).
(Note) The unit is set to 5.0 (5 sec.)
prior to delivery. Do not
change it unless necessary.
X
Y
PID
10 sec.
Control output
Input
filter
X,Y
X
Y
t
100
63
(%)