(2) Input power requirements
Select the 24 V input power supply that meets the specifications listed in Table 4.3.
Table 4.3 Input Power Requirements
Item
Specifications
Input power voltage range
21.6 to 27.0 V
Power consumption
Maximum 150 mA
4.3 Wiring for CC-Link Terminal Block
(1) To connect this option to a CC-Link network, use a CC-Link dedicated cable complying with the CC-Link
specifications. Using a cable other than a CC-Link dedicated cable does not assure the CC-Link system
performance. Also observe the wiring lengths specified in the CC-Link version 1.10 specifications.
The recommended CC-Link cable is FANC-110SBH made by Kuramo Electric Co., Ltd.
For details about wiring for CC-Link, refer to the CC-Link Master Use's Manual or CC-Link Cable Wiring
Manual published by the CC-Link Partner Association. The CC-Link Cable Wiring Manual is available as a
free download from the CC-Link Partner Association's website at:
http://www.cc-link.org/eng/t_html/siryo.html
(2) Wiring around the CC-Link terminal block
The terminal block uses a pluggable 5-pin connector as shown in Figure 4.4. Table 4.4 shows the
correspondence between the pin numbers and the ID colors.
A typical connector that matches this terminal block is Phoenix Contact MSTB 2.5/5-ST-5.08 AU.
The Phoenix Contact TMSTBP 2.5/5-ST-5.08 AU and TFKC 2.5/5-STF-5.08 AU (spring-cage
connection type) connectors for multidrop connection are also usable. Note that, however, the
former can be used only for FRENIC-Multi with a capacity of 3.7 kW or below.
Table 4.4 Layout of Terminal Pins
Terminal
Pin Name
ID Color of
Wire Sheath
Description
Remarks
DA
Blue
DB
White
DG
Yellow
For
communication
data
SLD
Metallic
For shielded
wire
This is internally
connected with
terminal FG.
FG
---
For grounding
Connect the ground
terminal of the inverter
( G) to this terminal.
㪝㪞 㪪㪣㪛 㪛㪞
㪛㪙
㪛㪘
Figure 4.4 Connectors on the
CC-Link Terminal Block