Chapter 5 CONFIGURING INVERTER'S FUNCTION CODES FOR CC-Link
COMMUNICATION
Before starting CC-Link communication between the inverter equipped with this option and the CC-Link master
device, configure the inverter's function codes listed in Table 5.1.
Table 5.2 lists other related function codes to be configured if necessary.
Table 5.1 Inverter's Function Codes for CC-Link Communication
(The underlined values are factory defaults.)
Function
code
Function
Setting range
Description
o27
*1
Response mode to apply
when a CC-Link
communications error occurs
0 to 15
Select a response mode to apply when a
communications link error or an option failure is
detected.
o28
*1
Operation timer to apply when
a CC-Link communications
error occurs
0.0 to 60.0 sec.
Specify the timer period during which the
inverter keeps running even if a communications
link error is detected.
0, 1
1 station occupied (CC-Link version 1.10)
2
1 station occupied, 2X setting
(CC-Link version 2.00)
3
1 station occupied, 4X setting
(CC-Link version 2.00)
4
1 station occupied, 8X setting
(CC-Link version 2.00)
o30
*2
CC-Link extension
5 to 255
No operation
1 to 64
Set a station address.
o31
*3
Station address
0, 65 to 255
Invalid
0
156 kbps
1
625 kbps
2
2.5 Mbps
3
5 Mbps
4
10 Mbps
o32
*3
Transmission speed
5 to 255
Invalid
*1 For details about the function codes o27 and o28, refer to Chapter 8 "INVERTER REACTION TO CC-Link
COMMUNICATIONS ERRORS."
*2 After changing the o30 data, resetting the option (by turning the terminal RST ON or by turning the option's power
OFF and then ON) validates the new setting. However, resetting the option causes an inverter trip with an alarm
GT
if Version 1.xx is specified on the master station and Version 2.xx on the option.
*3 Changing the o31 or o32 data causes the L.ERR LED to start blinking. Resetting the option validates the new setting
and turns the L.ERR LED OFF.
Table 5.2 Other Related Function Codes
Function
code
Function
Factory default
Function code data
Remarks
y98
*1
Run/frequency
command sources
0
Select from the following choices:
Frequency
command
Run
command
0
Inverter Inverter
1
CC-Link
Inverter
2
Inverter CC-Link
3
CC-Link
CC-Link
If there is no
special problem
with your system,
setting y98 = 3 is
recommended.
*1 In addition to y98, there are some function codes that specify run/frequency command sources. Using those function
codes enables more flexible settings of run/frequency command sources. For details, refer to the description for the
function codes H30 and y98 in the FRENIC-Multi Instruction Manual (INR-SI47-1094-E), Chapter 5 "FUNCTION
CODES."