2-16
Section 2 Specifications
Status indication LED
Status
Specification
PWR of analog input unit
ON (red)
While 5V DC power is normally supplied.
Digital value range
JP1 setting
-8192 to 8191
0 to 16383
Signal range
JP3 setting
JP2 setting
0 to 10V
or
0 to 20mA
0 to 5V
or
0 to 10mA
-10 to 10V
or
-20 to 20mA
-5 to 5V
or
-10 to 10mA
Voltage/current Setting of
JP4 (CH0) to JP9 (CH5)
Voltage
Current
(2) Functions
1) Status indication LED
2) Terminal block
These are terminals for 24V DC power supply to operate the analog unit and analog input signal.
3) JP1: Digital value range selection
This jumper pin is used to set the digital value range.
4) JP2 and JP3: Analog input range selection
These jumper pins are used to set the analog signal range
for six channels in a batch.
5) JP4 to 9: Voltage/current selection
This jumper pin is used to select voltage or current for
each channel.
* For the wiring method, see
“2-4 Wiring.”