2-5
Section 2 Specifications
Item
Specification
Type
NA3AY02-MR
No. of output channels
2 channels
External load resistance
Voltage output: 1k
W
to 1M
W
, Current output: 0 to 500
W
or less
Analog output range
0 to +10V
0 to 20mA
* Selectable by wiring of the terminal block.
Resolution
12 bits
Overall accuracy
±1%
Data type of digital output value INT type
Output period
Synchronized with the scan of the main unit.
External wire connections
5-pole European-style terminal block (M2) x 1, Tightening torque: 0.2 N·m
Applicable wire size
AWG#28-16 * Be sure to use shielded twisted pair cables.
Status indication
None
Isolation method
Not isolated
Occupied words
2 words
Internal current consumption
5V DC, 223mA
Mass
Approx. 20g
(4) Analog output board, 2 channels NA3AY02-MR
*1 Tightening torque for mounting the board on the main unit: 0.2 N·m
*2 Notes on using analog output
The analog unit does not support the hold function. If the main unit stops due to a system error, the analog output value
becomes 0 (zero). It is not possible to hold the output status after occurrence of an error or CPU stop.