6 Errors
6-6
Error Messages
* If the above error messages are displayed on the X1 series unit without establishing communication between X1 and PLC, test the solution “1”. If the error
occurs suddenly during communication, test the solution “2”.
Error Messages
Contents
Solution
Time-Out
Although a request to send is given to a controller, no
answer is returned within the specified time.
1. Check the settings in the [Hardware Setting]
[PLC
Properties] window.
Check that the cable is correctly connected.
2. Data may be disrupted because of noise.
Take measures against noise.
Parity
An error occurred in parity check.
1. Check that the cable is correctly connected.
2. Data may be disrupted because of noise.
Take measures against noise.
Framing
Although the stop bit must be “1”, it was detected as “0”.
1. Check the settings in the [Hardware Setting]
[PLC
Properties] window.
Check the cables and wiring.
2. Data may be disrupted because of noise.
Take measures against noise.
Overrun
After receiving one character, the next character was
received before internal processing was completed.
1. Check the settings in the [Hardware Setting]
[PLC
Properties] window.
2. Data may be disrupted because of noise.
Take measures against noise.
Check code error
The check code in the controller response was not correct.
1. Check the settings in the [Hardware Setting]
[PLC
Properties] window.
2. Data may be disrupted because of noise.
Take measures against noise.
Error code received
An error code was sent by a controller.
(NAK)
Examine the controller error code and solve the problem.
Breakage detected
The controller’s SD remains at the low level.
Examine the connection between the controller’s SD and the
X1’s RD.
Invalid memory
(Mitsubishi CPU, or other
equipment)
An address outside the permissible range of the connected
PLC was specified.
Check the type and range of the specified device memory.
Format
The code of the received data was different from the
specified code.
1. Confirm link unit settings.
(After making settings, turn off the power to each
controller.)
On the V-SFT version 6 editor, select [System Setting]
[Hardware Setting], and check the settings.
2. If errors only occur from time to time, data may be
disrupted because of noise.
Take measures against noise.
Compare
(Hitachi HIDIC-S10)
Transmitted data and received data were inconsistent.
NAK
The X1 series unit judged that communication is
impossible.
Transaction Error
(Allen-Bradley PLC)
Transmitted transaction data and received transaction data
were inconsistent.
Count error
(Mitsubishi CPU/Sharp CPU)
The expected data amount was different from the count
value.
Command error
(Mitsubishi CPU)
The response code was different from the expected code.
Invalid Cassette
(Mitsubishi ACPU)
There is no memory cassette that corresponds to the
cassettes currently supported.
Contact your local distributor.
CPU Type Error
(Mitsubishi CPU)
Unsupported CPU type (incorrect password)
Check whether or not the X1 series unit supports this CPU.
Unsupported CPU
(Siemens S5)
Unsupported CPU type
Invalid DB
(Siemens S5)
The corresponding DB cannot be found in the CPU.
Check if the corresponding DB exists using the ladder tool.
If the DB does not exist, create it using the ladder tool.
Содержание MONITOUCH X1 Series
Страница 1: ...Series Hardware Specifications...
Страница 3: ......
Страница 5: ......
Страница 9: ......
Страница 13: ......
Страница 14: ...1 Product Outline 1 1 Features 1 2 Models and Peripheral Equipment 1 3 System Configuration...
Страница 15: ......
Страница 19: ...1 Product Outline 1 4...
Страница 21: ......
Страница 40: ...3 Installation 3 1 Installation 3 2 Power Supply 3 3 Securing USB and HDMI Cables 3 4 Battery...
Страница 41: ......
Страница 51: ...3 Installation 3 10...
Страница 53: ......
Страница 59: ......
Страница 161: ...5 Operation Method 5 102 5 5 13 Reboot Reboot the X1 series unit RUN screen or System Configurator...
Страница 162: ...6 Errors 6 1 Errors 6 2 Troubleshooting...
Страница 163: ......
Страница 173: ...6 Errors 6 10...
Страница 174: ...7 Inspection and Maintenance 7 1 Inspection and Maintenance 7 2 Warranty Policy...
Страница 175: ......
Страница 179: ...7 Inspection and Maintenance 7 4...