Alarm codes for standard types
• Timer codes
[Alarm type list]
The table below shows the meaning of symbols in the following operation figures.
• Alarm 1 and 3 are activated in the same way as alarm 2 except codes 12 to 15. (Codes 12 to 15 cannot be selected for
Alarm 1 or 3. If any of them is selected, the instrument recognizes it as code 0, “No alarm,” and operates as such.)
• When any code of 12 to 15 is selected for Alarm 2, Alarm 2 is activated and Alarm 1 is not raised. “Alarm hysteresis”,
“Delay time”, and “Alarm latch” can be selected in Alarm 2 settings.
• The display of the parameter in which the alarm value is set varies depending on the alarm operation types.
• Since the alarm set value may change after changing the alarm operation types, confirm the alarm set value. (Note that
this is not abnormal.)
Alarm type
0 to 15
16 to 31
Set value of Alarm 1
Lower-limit of set value of Alarm 1
Upper-limit of set value of Alarm 1
Set value of Alarm 2
Lower-limit of set value of Alarm 2
Upper-limit of set value of Alarm 2
AL1
A1-L
A1-H
Set value of Alarm 3
Lower-limit of set value of Alarm 3
Upper-limit of set value of Alarm 3
Alarm 1
Alarm 2
Alarm 3
Display
symbol
AL2
A2-L
A2-H
Display
symbol
AL3
A3-L
A3-H
Display
symbol
Screen name
Screen name
Screen name
Absolute
value
alarm
ALM1
0
1
2
3
4
5
6
7
8
9
10
PV
PV
ALn
Alarm type
No alarm
Upper-limit
absolute value
Lower-limit
absolute value
Upper-limit
absolute value
(with hold)
Lower-limit
absolute value
(with hold)
Upper-limit
deviation
Lower-limit
deviation
Upper and lower
limits deviation
Upper-limit
deviation (with hold)
Lower-limit
deviation (with hold)
Upper and lower
limits deviation
(with hold)
ALM3
0
1
2
3
4
5
6
7
8
9
10
ALM2
0
1
2
3
4
5
6
7
8
9
10
Operation figure
PV
ALn
PV
ALn
PV
ALn
PV
ALn
SV
PV
ALn
SV
PV
ALn
ALn
SV
PV
ALn
SV
PV
ALn
SV
PV
ALn
ALn
SV
Deviation
value
alarm
Range
alarm
ALM1
11
-
-
-
-
Alarm type
Range upper and
lower limits deviation
(ALM1/2 indepen-
dent operation)
Range upper
and lower limits
absolute value
Range upper and
lower limits
deviation
Range upper limit
absolute value and
lower limit deviation
Range upper limit
deviation and lower
limit absolute value
ALM3
11
-
-
-
-
ALM2
11
12
13
14
15
Operation figure
PV
ALn
SV
ALn
PV
AL2
AL1
PV
AL1
SV
AL2
PV
AL1
SV
AL2
PV
AL1
SV
AL2
Timer
ALM1
32
33
34
ALM2
32
33
34
Alarm type
ON-delay
timer
OFF-delay
timer
ON/OFF-
delay timer
ALM3
32
33
34
Operation figure
dLYn
Di
ALM
dLYn
Di
ALM
dLYn
Di
ALM
dLYn