Fuji Electric Model: PXR4 Скачать руководство пользователя страница 1

Micro-controller X

Model: PXR4/5/9

Operation Manual

C1      C2     AL1    AL2    AL3

PV

SV

°

C

PXR

SEL

ECNO:406e

Содержание Model: PXR4

Страница 1: ...Micro controller X Model PXR4 5 9 Operation Manual C1 C2 AL1 AL2 AL3 PV SV C PXR SEL ECNO 406e...

Страница 2: ...OFF control 27 Cooling side proportional band coefficient 28 Cooling side proportional band shift Dead band Overlap band 29 Output offset value 30 Anti reset windup 30 Control algorithm 31 PV Measured...

Страница 3: ...r control output 2 62 Output limit types 63 Output value display 64 RCJ Cold junction compensation 65 Adjusting the PV Measured value display 0 66 Adjusting the PV Measured value display 100 66 DI1 2...

Страница 4: ...Digital input 1 point 9 10 11 12 13 Digit Note 1 Note 2 Note 2 Note 2 Note 2 Note 3 Note 3 Note 3 Note 3 Note 3 Note 3 Note 3 Note 4 Note Note 1 Cannot be combined with heater break alarm 2 3 6 7 H c...

Страница 5: ...ut 2 points RS485 Modbus communication Digital input 1 point RS485 ASCII communication Digital input 1 point 9 10 11 12 13 Digit Note 1 Note 2 Note 2 Note 2 Note 2 Note 2 Note 2 Note 2 Note 3 Note Not...

Страница 6: ...hts up on detecting a heater break r PV Measured value display Displays the PV When setting a parameter its name appears t SV Setting value display Displays the SV When setting a parameter its value a...

Страница 7: ...es whether or not to allow the change of parameters Lower limit value of alarm 3 Sets the lower limit value at which alarm 3 is detected Set value of alarm 3 Sets the value at which alarm 3 is detecte...

Страница 8: ...Y Runs PID control with fuzzy logic SELF Runs PID control with self running 0 to 100 FS 2 FS oFF Starts the two position control at the values of SV HYS 2 and SV HYS 2 on Starts the two position contr...

Страница 9: ...ion Sets the 8th ramp segment time Sets the 8th soak segment time Selects the power on start repeat and standby functions for ramp soak operations 0 to 99h59m 0 00 Within the SV limit 0 FS 0 to 99h59m...

Страница 10: ...the cold junction compensation function to ON OFF Shifts the zero point of input value Shifts the span of input value Sets the DI1 operations Sets the DI2 operations Sets the station No for communica...

Страница 11: ...nt of input value Shifts the span point of input value Sets the filter constant of remote SV input value Displays remote SV input value Sets whether or not to display each parameter 0 Z ASCII 1 Modbus...

Страница 12: ...basic operations for the PXR C1 C2 AL1 AL2 AL3 PV SV C PXR SEL Just after power on PV SV displayed SEL SEL SEL approx 1 second Changes SV Not operated for 30 seconds approx 3 seconds approx 5 seconds...

Страница 13: ...n 3 seconds without any operation C1 C2 AL1 AL2 AL3 PV SV C PXR SEL Just after power on PV MV displayed C1 C2 AL1 AL2 AL3 PV SV C PXR SEL PV SV displayed SEL SEL SEL approx 1 second Changes MV Not ope...

Страница 14: ...ange set in the parameters of lower limit and upper limit of the third block cannot be set See page 54 Setting example Changing the SV from 250 C to 1195 C Press the or keys to display will be registe...

Страница 15: ...o Manual while auto or self tuning is being done the tuning is forcibly terminated The PID parameter remains the same in such cases Manual operation output is not limited by MV limit Manual operation...

Страница 16: ...L key for one second will be displayed Then press the key once Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once The standby stat...

Страница 17: ...Flickering stops and the operation is switched to remote To display the operation status press and hold the SEL key for two seconds Operating procedure Display 1 2 4 6 Set value Operation Performs lo...

Страница 18: ...ak operation Press and hold the SEL key for one second will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or ke...

Страница 19: ...and hold the SEL key for one second will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press...

Страница 20: ...ms the auto tuning based on the SV Setting code 2 Low PV type Performs the auto tuning based on the SV 10 FS Note Since ON OFF control is performed during auto tun ing overshoot against the SV may occ...

Страница 21: ...ing count down if the PV changes to the value of the temperature at which the alarm is set to OFF or if DI for the timer is set to OFF the counter is reset and the alarm relay is opened PV SV Remainin...

Страница 22: ...ion status press and hold the SEL key for two seconds Operating procedure Display 1 2 3 4 5 6 Description These parameters are used to for settings of alarm 1 2 and 3 When the alarm type or is set to...

Страница 23: ...mmunication All settings are changeable from the controller but unchangeable via communication All settings are unchangeable from the controller or via communication Only the SV is changeable from the...

Страница 24: ...ill be displayed on the PV display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be registered fo...

Страница 25: ...makes the setting of ineffec tive Press and hold the SEL key for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the S...

Страница 26: ...0 this makes the setting of ineffective Press and hold the SEL key for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on...

Страница 27: ...Changing the hysteresis range from 1 C to 35 C Press and hold the SEL key for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting fla...

Страница 28: ...press and hold the SEL key for two seconds Operating procedure Display 1 2 3 4 5 6 Before setting the cooling side proportional band set the heating side proportional band to an optimum value To sele...

Страница 29: ...key once will stop flashing and will be registered for After that the controller will operate with being 2 0 If you want to display the operation status press and hold the SEL key for two seconds Ope...

Страница 30: ...d hold the SEL key for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Pres...

Страница 31: ...yed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be r...

Страница 32: ...w Set the SV e Select in the parameter of 1 r Power off the PXR t Power on the device to be controlled y Power on the PXR Tuning Control 2 To re start the self tuning If the device that is to be cont...

Страница 33: ...osition control Parameter of 0 e During auto tuning operation r During ramp soak operation t Error display or is displayed y During dual output The set value of the parameter of is larger than 4 u Whe...

Страница 34: ...ing figures show the operations at power on and changing the SV and under unstable control q Operations at power on w Operations at changing the SV e Operation under unstable control PV SV Time During...

Страница 35: ...ed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be re...

Страница 36: ...ss and hold the SEL key for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the key to display Pre...

Страница 37: ...vice and the contacts Typical 30 seconds For SSR driving output Use in short cycles if there is no problem with the device to be controlled Typical 1 to 2 seconds Output ON Cycle time Cycle time Setti...

Страница 38: ...he SEL key once The current setting flashes on the SV display Press the or key to display Press the SEL key once will stop flashing and will be registered for After that the controller will operate wi...

Страница 39: ...the voltage in put remove the resistance of 250 as well as changing the code Note After changing the codes power off the PXR and then power it on again Code 1 2 3 4 5 6 7 8 12 13 16 Input signal Resi...

Страница 40: ...cept the cases shown below Thermocouple R at 0 to 500 C Thermocouple B at 0 to 400 C Other kinds of thermocouples 0 5 FS 1 digit 1 C 150 300 500 600 100 200 600 850 400 800 400 800 1200 1600 1800 1600...

Страница 41: ...display Press the SEL key once will stop flashing and will be registered for Press the key to display on the PV display Press the SEL key once The current setting flashes on the SV display Press the...

Страница 42: ...Press the key to display Press the SEL key once The current setting flashes on the SV display Press the key to display Press the SEL key once will stop flashing and will be registered for After that...

Страница 43: ...conds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or key to display Press the SEL key once will stop fla...

Страница 44: ...for three seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or key to display Press the SEL key once w...

Страница 45: ...tting range 0 0 to 900 0 seconds Setting example Changing the filter constant from 5 0 5 seconds to 10 0 10 seconds Press and hold the SEL key for three seconds will be displayed on the PV display Pre...

Страница 46: ...anging the alarm operation types power the PXR off and then on Setting code 0 indicates No alarm Note Alarm set value and alarm operations Alarm set value AL Upper limit Lower limit Lower limit Upper...

Страница 47: ...f Alarm 3 Alarm 1 Alarm 2 Alarm 3 Display symbol AL2 A2 L A2 H Display symbol AL3 A3 L A3 H Display symbol Screen name Screen name Screen name Absolute value alarm ALM1 0 1 2 3 4 5 6 7 8 9 10 PV PV AL...

Страница 48: ...viation and lower limit absolute value with hold ALM3 16 17 18 19 20 21 22 23 ALM2 16 17 18 19 20 21 22 23 Operation figure PV An L An H PV SV An L An H PV SV An L An H PV SV An H An L PV An L An H PV...

Страница 49: ...nds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the key to display Press the SEL key once will stop flashing...

Страница 50: ...tern is changed to the new setting to to to Parameters In order to execute these functions it is necessary to set the programs in advance To set the programs set the SV Setting value and time desired...

Страница 51: ...ntrol Continuous control Standby mode Standby mode Standby mode Standby mode Output at OFF Continuous control Continuous control Standby mode Standby mode Continuous control Continuous control Standby...

Страница 52: ...ay 1 2 3 4 5 6 PV 200 100 50 TM1r TM1S TM3r TM3S SV 1 SV 2 PV TM1r TM1S TM2S TM3r SV 3 TM2r Pattern of the program Pattern that is affected by the SV limit function The segment in which both the ramp...

Страница 53: ...to display Press the SEL key once will stop flashing and will be registered for After that the controller will operate with the Direct Upper limit for burn out output selected If you want to display t...

Страница 54: ...he set values of to are not affected When the SV limiter is set during ramp soak operation or switching the SV with the DI1 function the SV SV0 that is set manually and the displayed SV are affected b...

Страница 55: ...Mn 33 the timer cannot be activated while the DI input is set to ON The relay is closed in the set time after DI input is set to OFF When the ON OFF delay timer is selected ALMn 34 the timer is activa...

Страница 56: ...display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be registered for...

Страница 57: ...aters and the current of n 1 heaters When the thyristor SCR phase control system is used to control the heater the parameters of and can not be used Connect this to the heater Pass it through the hole...

Страница 58: ...stop flashing and will be registered for After that the controller will operate with detecting current of heater break being 9 0A If you want to display the operation status press and hold the SEL ke...

Страница 59: ...it alarm Range alarm AL1 A1hy ALM1 ALM2 AL2 A2hy ALM3 AL3 A3hy Setting example Changing the hysteresis of alarm 2 from 1 C to 3 C Press and hold the SEL key for five seconds will be displayed on the P...

Страница 60: ...function set the alarm types ALM1 2 or 3 to 0 Display Causes A break in the thermocouple sensor A break in the resistance bulb sensor RTD A The PV reading value exceeds the P SU by 5 FS or more A bre...

Страница 61: ...s the SEL key once The current setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be registered for After that the controller will operat...

Страница 62: ...the SV display Press the or keys to display Press the SEL key once will stop flashing and will be registered for After that the controller will operate with the output lower limit being 10 If you want...

Страница 63: ...for After that the controller will operate with outputs 1 and 2 maintained within the upper and lower limits If you want to display the operation status press and hold the SEL key for two seconds Ope...

Страница 64: ...e some error comparing to the actual output Setting example Confirming the output value the calculated value of control output 1 Press and hold the SEL key for five seconds will be displayed on the PV...

Страница 65: ...the SEL key for five seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Press the S...

Страница 66: ...input of 0 C 1 C Display at input of 400 C 402 C Adjustment value Display at input of 0 C 0 C Display at input of 400 C 400 C 1 2 Adjustment example for input range of 0 to 400 C Setting the paramete...

Страница 67: ...ely SV 2 seconds SV No 1 second However the SV No is not displayed during the ramp soak operation DI operation Setting range 0 to 12 Option Ramp soak operation RUN RESET DI function 12 The ramp soak o...

Страница 68: ...ion to ON Timer operation DI functions 9 to 11 The DI can set the ON OFF of timer while codes 32 to 34 are set in Setting alarm types page 46 For the operation see page 46 DI function AT Standard AT L...

Страница 69: ...ll be registered for Press and hold the key for five seconds will be displayed Press the or keys to flicker and to display Repeat the procedure from 3 to 5 to check the set value Press the key once Th...

Страница 70: ...t setting flashes on the SV display Press the or keys to display Press the SEL key once will stop flashing and will be registered for After that the controller will operate with the station number bei...

Страница 71: ...and hold the SEL key for five seconds will be displayed on the PV display Press the key to display Press the SEL key once The current setting flashes on the SV display Press the or keys to display Pr...

Страница 72: ...Set value Output type 1 Modbus RTU protocol 0 Z ASCII protocol Related parameters page 70 page 71 Setting example Changing to Z ASCII protocol Press and hold the SEL key for 5 seconds will be displaye...

Страница 73: ...ill be displayed on the display area If unoperated state continues the PV will be displayed Press the key once will be displayed and 1 SV retransmission will be registred for the retransmission output...

Страница 74: ...to 400 C P SL 0 lower limit value of measurement range and P SU 400 upper limit value of measurement range So from the formula shown above A 100 C 0 or 300 C 0 B 400 0 400 1 Setting Ao L What positio...

Страница 75: ...These parameters are used to correct the deviation of remote SV input By setting 0 to the parameters the status at the time of delivery from the factory can be restored 1 To correct the deviation from...

Страница 76: ...h the filter constant of 5 0 seconds To display the operation status press and hold the SEL key for 2 seconds Operating procedure 1 2 3 4 5 6 Description This parameter is used to make the input signa...

Страница 77: ...filter and remote SV input adjustment is displayed as display value Setting example Checking the remote SV input value Press and hold the SEL key for 5 seconds will be displayed in the PV display sec...

Страница 78: ...the SEL key once will stop flashing and will be registered for After that the parameters of and will be skipped and will not be displayed If you want to display the operation status press and hold the...

Страница 79: ...or 2 has been dis played 3 A decimal point has not been displayed 4 The SV or the set val ues of some parameters have been changed without any operation 5 ON OFF control Two posi tion control has not...

Страница 80: ...layed 13 Auto tuning does not work properly 14 An excessive over shoot has occurred dur ing auto tuning opera tion 15 The self tuning does not work properly 16 The PV display disap peared Possible cau...

Страница 81: ...tion control 24 Operation methods 7 Options of alarm 1 2 and 3 60 Output direction at input burn out 53 Output limit types 63 Output offset value 30 Overlap band 29 Parameter display mask 78 Parameter...

Страница 82: ...82 Memo...

Страница 83: ...sor to disable the heating circuit in case of overheating The controller alarm signal is not designed to function as a protective measure in case of controller failure Safety Precaution Before using t...