Section 1 PLC Specifications
1-2
1-1 Performance Specifications
Note 1: The area sizes of the standard memory, retain memory, memory for user FB and memory for system FB can freely be
increased or decreased.
Note 2: The initial value setting areas of the standard memory and retain memory are included.
Note 3: This depends on each instruction.
Note 4: When the PLC is started up with data of the internal RAM lost, it operates as follows:
All data of the internal RAM are cleared to “0”.
The “ALM LED” lights up.
The nonfatal fault flag, memory error flag, and memory backup error flag are set to ON. You can check the error with
the diagnostic function of the loader.
To restore the system, set the memory backup error flag to OFF with the user program or loader, or power this board
off and on again. The nonfatal fault flag and memory error flag are set to OFF and the “ALM LED” goes out.
Backup
(Note 4)
Backup time
Backup time by battery: Approx. 5 years (at ambient temperature of 25
)
Program, system definition area
Built-in flash memory, built-in RAM: Backed up by battery
Data memory, RAS
Built-in RAM: Backed up by battery
ZIP file
Built-in flash memory
Calendar
Built-in RAM: Backed up by battery