1-13
Section 1 PLC Specifications
1-2 PLC Internal Memory
(11) CPU running information %MW10.49 (Read only)
(12) CPU configuration/fault information %MW10.50, %MW10.51 (Read only)
* The status of this board is recognized by the combination of the configuration flag and error flag.
(13) System configuration/fault information %MW10.52 to 83 (Read only)
The status of the system is recognized by the combination of the system configuration information and system fault information.
Board configuration
information
Board fault information
Board status
OFF
OFF
Nonexistent
ON
OFF
Normal
ON
ON
Nonfatal fault
OFF
ON
Fatal fault or dropped
Address
Name
Description
%MX10.49.0
PLC running
Set to "ON" while the PLC is running.
%MX10.49.1
|
%MX10.49.15
Not used
Address
Name
Description
%MX10.50.0
Configuration flag
Set to "ON" while the PLC is running normally or in nonfatal fault condition.
%MX10.50.1
|
%MX10.50.15
Not used
%MX10.51.0
Error flag
Set to "ON" when the PLC stops due to fatal fault or is running in nonfatal fault
condition.
%MX10.51.1
|
%MX10.51.15
Not used
Configuration flag
Error flag
Board status
OFF
OFF
Nonexistent
ON
OFF
Normal (run or stop)
ON
ON
Nonfatal fault (run or stop)
OFF
ON
Fatal fault (stop or drop)
Address
Name
Description
%MX10.52.0
I/O board 0 configuration
Set to "ON" when the I/O is in normal or nonfatal fault condition.
%MX10.52.1
|
%MX10.67.13
Not used
%MX10.67.14
CPU configuration
Set to "ON" when the PLC is in normal or nonfatal fault condition.
%MX10.67.15
Not used
%MX10.68.0
Expansion I/O board 0 error
Set to "ON" when the I/O is in nonfatal or fatal fault condition.
%MX10.68.0
|
%MX10.83.13
Not used
%MX10.83.14
CPU error
Set to "ON" when the PLC is in nonfatal or fatal fault condition.
%MX10.83.15
Not used