1-7
Section 1 PLC Specifications
1-2-4 System memory
(1) PLC operation/state status %MW10.0 to 10.1 (Read only)
Address
Name
Description
%MX10.0.0
Run
Set to "ON" while the PLC is running.
%MX10.0.1
Stop
Set to "ON" while the PLC is down.
%MX10.0.2
Fatal fault
Set to "ON" when a fatal PLC error has occurred.
%MX10.0.3
Nonfatal fault
Set to "ON" when a non-fatal PLC error has occurred.
%MX10.0.4
|
%MX10.0.8
Not used
%MX10.0.9
Automatic operation mode
Set to "ON" while in the automatic operation mode.
In this mode, operation is started when this board is powered up.
This board is always set in this mode.
%MX10.0.10
Not used
%MX10.0.11
Battery-less operation mode
Set to "ON" while in the battery-less mode.
In this mode, all memories are initialized (assigned initial values or cleared
to 0) when this board is powered up. No checks is performed on battery
connection or voltage.
The battery-less operation mode is set by the "CPU running definition" under
the "system definition".
%MX10.0.12
|
%MX10.0.15
Not used
%MX10.1.0
CPU number
Fixed to 0 for this board
%MX10.1.1
|
%MX10.1.5
Not used
%MX10.1.6
User ROM card connection state
ON: connected, OFF: unconnected
%MX10.1.7
User ROM card write protect
ON: write-protected, OFF: write-permitted (enabled when %MX10.1.6=ON)
%MX10.1.8
STOP position
Set ON if the set bit is OFF (STOP) when the remote RUN/STOP function is
used.
%MX10.1.9
Not used
%MX10.1.10
Remote RUN/STOP state
Set ON when the remote RUN/STOP function is not used.
In addition, set ON if the set bit is ON when the remote RUN/STOP function is
used.
%MX10.1.11
|
%MX10.1.15
Not used
1-2 PLC Internal Memory