background image

 

Chapter 3: Mechanical Installation 

_______________________________________________________________________________________________________________

 

10 

3. MECHANICAL INSTALLATION 
 
 
3.1  Operating Environment 

 

Install the inverter in an environment that satisfies the requirements listed in Table 3.1. 
 

Table 3.1 Environmental Requirements 

Item 

Specifications 

Site location 

Indoors 

Ambient 
temperature 

-10 to +50

°

C

 (Note 1)

 

Relative 
humidity 

5 to 95% (No condensation) 

Atmosphere 

The inverter must not be exposed to dust, 
direct sunlight, corrosive gases, flammable 
gas, oil mist, vapor or water drops.

 (Note 2)

 

The atmosphere must contain only a low 
level of salt. 
(0.01 mg/cm

2

 or less per year) 

The inverter must not be subjected to 
sudden changes in temperature that will 
cause condensation to form. 

Altitude 

1000 m max.

 

(Note 3)

 

Atmospheric 
pressure 

86 to 106 kPa 

Vibration 

3 mm (Max. amplitude)  2 to less than 9 Hz 
9.8 m/s

2

 

9 to less than 20 Hz 

2 m/s

2

 

20 to less than 55 Hz 

1 m/s

2

 

55 to less than 200 Hz 

 
 
 

3.2 Installing the Inverter 

 

(1)  Mounting base 

The  temperature  of  the  heat  sink  will  rise  up  to  approx.  90°C  during 
operation of the inverter, so the inverter should be mounted on a base made 
of material that can withstand temperatures of this level. 

 

Install  the  inverter  on  a  base  constructed  from  metal  or  other  non-flammable 
material. 

A fire may result with other material. 

 

(2)  Clearances 

Ensure that the minimum clearances indicated in Figure 3.1 are maintained 
at  all  times.  When  installing  the  inverter  in  the  panel  of  your  system,  take 
extra  care  with  ventilation  inside  the  panel  as  the  temperature  around  the 
inverter will tend to increase. Do not install the inverter in a small panel with 
poor ventilation.

 

 
 

 

 

 

Prevent  lint,  paper  fibers,  sawdust,  dust,  metallic  chips,  or  other  foreign  materials  from  getting  into  the  inverter  or  from 
accumulating on the heat sink. 

This may result in a fire or accident. 

 

 

 

Figure 3.1  Mounting Direction and 

Required Clearances 

Table 3.2  Output Current Derating 

Factor in Relation to Altitude 

Altitude 

Output current 
derating factor 

1000 m or lower 

1.00 

1000 to 1500 m 

0.97 

1500 to 2000 m 

0.95 

2000 to 2500 m 

0.91 

2500 to 3000 m 

0.88 

 

(Note 1)  When inverters are mounted side-
by-side without any gap between them (less 
than  5.5  kW),  the  ambient  temperature
should  be  within  the  range  from  -10  to 
+40

°

C. 

(Note  2)    Do  not  install  the  inverter  in  an 
environment  where  it  may  be  exposed  to 
cotton  waste  or  moist  dust  or  dirt  which  will 
clog  the  heat  sink  in  the  inverter.  If  the 
inverter  is  to  be  used  in  such  an 
environment,  install  it  in  the  panel  of  your 
system or other dustproof containers. 

(Note 3)  If you use the inverter in an altitude 
above  1000  m,  you  should  apply  an  output 
current derating factor as listed in Table 3.2. 

Содержание FRENIC-Multi FRN0.1E1S-2LM1

Страница 1: ...STARTING GUIDE FRENIC Multi LM 1 High performance compact inverter for lift applications 3 ph 400 V 0 4 kW 15 kW 3 ph 200 V 0 1 kW 15 kW SG_Multi LM1_EN_1 4 3 ...

Страница 2: ...o adjust experimentally P12 is removed Chapter 7 3 Torque boost gain is added Chapter 7 4 Compensation response time is added 11 11 08 J Alonso S Ureña S Ureña 1 4 1 Version updated from LM to LM1 Header changed from LM to LM1 Small text corrections Over rating table for 400 V is added Factory setting is changed updated Auto tuning mode 2 is static updated Table 7 1 Sentence is added 28 04 2011 S ...

Страница 3: ...erminal cover and the main circuit terminal block cover 11 4 2 Wiring for main circuit terminals and grounding terminals 13 4 3 Wiring for control circuit terminals 14 4 4 Control terminal description 14 4 5 Setting up the slide switches 17 5 OPERATION USING THE KEYPAD 18 6 SETTING 21 6 1 Basic setting for induction motor 21 6 2 Quick start commissioning auto tuning 21 6 3 Additional setting 22 6 ...

Страница 4: ... place until this product is discarded Listed below are the other materials related to the use of the FRENIC Multi LM1 Read them in conjunction with this manual if necessary FRENIC Multi User s Manual MEH457 FRENIC Multi Instruction Manual INR SI47 1094a E The materials are subject to change without notice Be sure to obtain the latest editions for use Inputs and outputs can be set to different fun...

Страница 5: ... observed at all times Application FRENIC Multi LM1 is designed to drive a three phase induction motor Do not use it for single phase motors or for other purposes Fire or an accident could occur FRENIC Multi LM1 may not be used for a life support system or other purposes directly related to the human safety Though FRENIC Multi LM1 is manufactured under strict quality control install safety devices...

Страница 6: ...upply wires to output terminals U V and W Do not insert a braking resistor between terminals P and N P1 and N P and P1 DB and N or P1 and DB Doing so could cause fire or an accident Generally control signal wires are not reinforced insulation If they accidentally touch any of live parts in the main circuit their insulation coat may break for any reasons In such a case ensure the signal control wir...

Страница 7: ...ntial requirements of the Electromagnetic Compatibility EMC Directive 89 336 EEC issued by the Council of the European Communities and the Low Voltage Directive 73 23 EEC Inverters with built in EMC filter that bear a CE marking are in conformity with EMC directives Inverters having no built in EMC filter can be in conformity with EMC directives if an optional EMC compliant filter is connected to ...

Страница 8: ...tegory C3 EN 61800 3 2004 Immunity 2nd Env EN 61800 3 2004 Mass kg 1 5 1 6 2 5 2 5 3 0 4 8 5 0 8 1 9 1 1 Rated current for Ta 50 ºC Cf 8 kHz ED 40 2 Available only in 4 0 kW 400 V 2 2 Three phase 200 V class series Items Specifications Type FRN E1S 2LM1 0 1 0 2 0 4 0 75 1 5 2 2 3 7 5 5 7 5 11 15 Nominal applied motor kW 0 1 0 2 0 4 0 75 1 5 2 2 3 7 5 5 7 5 11 15 Output ratings Rated capacity kVA 0...

Страница 9: ...________________ 9 2 3 Over rating table for 400 V series Inverter Size Maximum motor POWER I rated A Overload Time s Overload Time s 4 0 4 kW 10 4 130 60 173 0 5 5 5 5 5 kW 15 130 60 173 0 5 7 5 7 5 kW 20 8 130 60 173 0 5 11 11 kW 27 6 130 60 174 0 5 15 15 kW 34 5 130 60 174 0 5 Rated current for Ta 45 ºC Cf 8 kHz ED 40 ...

Страница 10: ...constructed from metal or other non flammable material A fire may result with other material 2 Clearances Ensure that the minimum clearances indicated in Figure 3 1 are maintained at all times When installing the inverter in the panel of your system take extra care with ventilation inside the panel as the temperature around the inverter will tend to increase Do not install the inverter in a small ...

Страница 11: ...he main circuit terminal block cover hold its right and left ends with your fingers and slide it toward you Refer to figure 4 1 Figure 3 1 Removing the Covers For Inverters with a Capacity of Less than 5 5 kW 2 For inverters with a capacity of 5 5 and 7 5 kW To remove the terminal cover first loosen the terminal cover fixing screw put your finger in the dimple of the terminal cover labelled PULL a...

Страница 12: ...ple of the terminal cover labelled PULL and then pull it up towards you To remove the main circuit terminal block cover hold the handles on the both sides of the main circuit terminal block cover and pull it up Refer to figure 4 4 Figure 4 4 Removing the Covers For Inverters with a Capacity of 11 and 15 kW When mounting the main circuit terminal block cover fit it according to the guide on the inv...

Страница 13: ...rminals and connect the grounding terminal of the motor Inverters provide a pair of grounding terminals that function equivalently Table 4 1 Symbols names and functions of the main circuit power terminals Please connect the screen in both motor and inverter sides Ensure that the screen is continued also through the contactors It is recommended to use a braking resistor with clixon and connect the ...

Страница 14: ...h SW1 located on the control PCB Factory setting is PNP Source Logic Connection example using PNP Logic Lift controller FRENIC Multi LM1 Up Speed 1 X1 FWD PLC 24 V Figure 4 8 Normal connection using free potential contacts of the lift controller 12 11 V2 C1 11 PLC FWD REV CM X1 X2 X3 X4 X5 CM Y1 Y2 CMY FRENIC Multi LM1 30A 30B 30C Analog Inputs Keypad connector or RS 485 Modbus RTU Up Down Lift di...

Страница 15: ...hes Contact rating 250 VAC 0 3 A 48 VDC 0 5 A d Transistor outputs Terminals Y1 to Y2 are configured from factory with the functions described in the table below Other functions can be set using functions E20 to E21 Figure 4 10 Connection using PNP Source Logic Terminal Function description of the digital inputs FWD Left rotation direction of the motor seen from the shaft side Depending on the mec...

Страница 16: ...er e Communication connections keypad and PC FRENIC Multi LM1 has one RS485 port available for communication The RS485 port through a RJ 45 connector makes possible the connection of the FRENIC Multi LM standard and multifunctional keypad or a PC Only one communication is possible at the same time i Keypad The keypad can be remotely connected up to 20m Pin Nr Signal Function Comments 1 and 8 VDC K...

Страница 17: ...ove the terminal cover refer to Section 4 1 Removing the terminal cover and main circuit terminal block cover Slide Switch Function SW1 Switches the service mode of the digital input terminals between SINK and SOURCE To make the digital input terminal X1 to X5 FWD or REV serve as a current sink turn SW1 to the SINK position To make them serve as a current source turn SW1 to the SOURCE position Fac...

Страница 18: ...s the function code and sets the data entered with and keys In Alarm mode Pressing this key displays the details of the problem indicated by the alarm code that has come up on the LED monitor RUN key Press this key to run the motor STOP key Press this key to stop the motor and UP and DOWN keys Press these keys to select the setting options and change the function code data displayed on the LED mon...

Страница 19: ...erter status and maintenance Alarm mode If an alarm condition arises the inverter automatically enters Alarm mode In this mode you can view the corresponding alarm code and its related information on the LED monitor Alarm code Indicates the cause of the alarm condition that has triggered a protective function For details refer to Chapter 9 Troubleshooting 1 The speed monitor allows you to select t...

Страница 20: ...e and calculated torque 4 I O Checking 4 I_o Displays external interface information The status of control I O signal terminals may be displayed with ON OFF of the LED segment Segments LED 4 LED 3 LED 2 LED 1 a 30A B C Y1 CMY FWD b Y2 CMY REV c X1 d X2 e X3 f XF X4 g XR X5 h RST If all terminal input signals are OFF open segment g on all of LED1 to LED4 will light 5 Maintenance Information 5 CHE S...

Страница 21: ...02 Motor rated capacity power from name plate kW Depends on the inverter capacity Depends on the motor P03 Motor rated current from name plate A Depends on the inverter capacity Depends on the motor P06 Motor no load current A The Auto tuning procedure measures the value of this function when P04 2 Depends on the inverter capacity See chapter 6 3 P07 Motor stator resistance R1 in The Auto tuning p...

Страница 22: ...lculate no load current you can use the formula 2 2 F05 1 47 1000 P02 P03 P06 Too low values in P03 will make that the motor does not have enough torque Too high values will make that the motor oscillates this oscillation will cause a vibration in the motor that is transmitted to the cabin Slip frequency function P12 The slip frequency function defines the value of the slip frequency of the motor ...

Страница 23: ... ON OFF OFF C08 ON ON OFF ON C09 ON ON ON OFF C10 ON ON ON ON C11 Table 6 2 Speed selection table Setting F01 0 an extra speed on the keypad is available After Change Before Change Stop Zero Speed High Speed Maintenance Speed Creep Speed UPS operation Speed Stop Dec o65 o66 E10 Acc o61 o62 F07 Acc o65 o65 E10 Acc E11 Zero Speed Dec o65 o66 E10 Acc o61 o62 F07 Acc o65 o65 E10 High Speed Maintenance...

Страница 24: ...The inverter accelerates to high speed Afterwards the inverter is driven at a constant speed Inverter in operation d The inverter decelerates to the creep speed Inverter in operation e The inverter decelerates to the stopping speed The inverter keeps driving at stopping speed from less than DC brake starting frequency to the time of F22 passes The inverter shifts from the operating state to the st...

Страница 25: ...ng on the operation speed load motor and type of instalation The BATRY function must be turned on The UPS will be connected as follow Figure 7 1 Basic Wiring Diagram This is only a schematic drawing This is for information only and without responsibility The start of rescue operation enable signal activation and contactors control is handled by the lift controller and is not in the range of the re...

Страница 26: ...y the auto resetting operation When the following requirements are met the inverter will automatically reset the tripped state RUN command goes to OFF Auto resetting reset time interval H05 is elapsed Auto resetting times H04 not equal 0 Auto resetting times interval counter H04 setting value Even if any alarm subject to auto resetting is activated the inverter issues an alarm for any fault The al...

Страница 27: ...inimum value of torque boost gain is 0 01 If 0 00 is set to torque boost gain it means o40 1 20 and o81 1 00 A high value in torque boost gain can cause over current trips OC on the inverter especially at starting and in creep speed Use a different value than recommended only if it is necessary 7 4 Compensation response time The voltage compensation response time and the slip compensation response...

Страница 28: ...R controlled voltage for 400 V class series 380 V F07 Acceleration Deceleration Time 1 0 00 to 3600 s 2 00 s Note Entering 0 00 cancels the acceleration time requiring external soft start F08 Acceleration Deceleration Time 2 0 00 to 3600 s 1 80 s Note Entering 0 00 cancels the deceleration time requiring external soft start F09 Torque Boost 1 0 0 to 20 0 percentage with respect to F05 Rated Voltag...

Страница 29: ...E20 Terminal Y1 Function Selecting function code data assigns the corresponding function to terminals Y1 Y2 and 30A B C as listed below 57 E21 Terminal Y2 Function 0 1000 Inverter running RUN 12 E27 Terminal 30A B C Function 1 1001 Frequency arrival signal FAR 99 2 1002 Frequency detected FDT 3 1003 Undervoltage detected Inverter stopped LU 4 1004 Torque polarity detected B D 5 1005 Inverter outpu...

Страница 30: ...0 Fuji standard motors 8 series 0 1 Motor characteristics 1 HP rating motors 3 Motor characteristics 3 Fuji standard motors 6 series 4 Other motors H codes High performance functions Code Name Data setting range Default setting H03 Data Initialization 0 Disable initialization 0 1 Initialize all function code data to the factory defaults 2 Initialize motor 1 parameters 3 Initialize motor 2 paramete...

Страница 31: ...e Setting 5 20 o66 S curve Setting 6 20 o75 MC Control Startup delay time 0 00 to 10 00 s 0 10 s o76 MC OFF delay time 0 00 to 10 00 s 0 10 s o80 UPS Operation level Edc 120 to 220 for 200 V class series 120 V Edc 240 to 440 for 400 V class series 240 V o81 Torque Boost Gain for UPS Operation 0 00 to 3 00 1 50 9 TROUBLESHOOTING Alarm code Alarm name Alarm description OC1 Overcurrent protection dur...

Страница 32: ...has detected a communications error with the option card Er5 Option error detection The option card has detected an error Er6 Start check function The inverter prohibits any run operations and displays Er6 on the 7 segment LED monitor if any run command is present when Powering up An alarm is released the key is turned ON or an alarm reset RST is input Enable communications link LE has been activa...

Страница 33: ...th Friedrich Ebert Str 19 35325 Mücke Tel 49 0 6400 9518 14 Fax 49 0 6400 9518 22 mrost fujielectric de Switzerland Fuji Electric Europe GmbH ParkAltenrhein 9423 Altenrhein Tel 41 71 85829 49 Fax 41 71 85829 40 info fujielectric ch www fujielectric ch Spain Fuji Electric Europe GmbH Sucursal en España Ronda Can Fatjó 5 Edifici D Local B Parc Tecnològic del Vallès 08290 Cerdanyola Barcelona Tel 34 ...

Отзывы: