Function
Display on LED
Monitor
Description
Verify
data
ueri
and
Function code
data block number,
displayed
alternately
Verifies (collates) the data stored in the memory of the copy adapter with the function code data held in the inverter.
When a discrepancy is detected, the verify operation will be aborted, with the function code in disagreement
displayed blinking. Pressing the
key again will cause the verification to continue from the next function code.
If you press the
key during a verify operation (
ueri
is blinking), the verify operation that is under way will be
aborted and
err
will appear blinking(*).
err
will appear blinking(*) also when the copy adapter does not contain any valid data.
Data
protection
proT
and
Function code
data block number,
displayed
alternately
Protects the memory contents in the copy adapter.
When this function is enabled, no data can be read out from the inverter. The data writing and verifying are possible.
If you press the
key,
err
will appear blinking(*).
(*)To get out of the error state indicated by a blinking
err
or
cper
, press the
key.
Some function code data cannot be copied (stored) into another inverter.
For safety considerations, some function code data cannot be copied to another inverter if the specifications of the destination inverter are
different from those of the source inverter. Which function code data can or cannot be copied is summarized in the FRENIC-Mini Instruction
Manual (INR-SI47-1205-E), Chapter 5, the "Data copy" column of Section 5.1 "Function Code Tables," using the following designations:
Y :
Can be copied unconditionally.
Y
1 :
Cannot be copied if the rated capacity differs from the source inverter.
Y
2 :
Cannot be copied if the rated input voltage differs from the source inverter.
N :
Cannot be copied in any situation.
(
The function codes marked with N cannot be verified, either.
)
Set up manually function code data that cannot be copied individually as necessary, using Menu #1 "Data setting" in Programming mode.
Frequency settings cannot be copied for safety.
Transition flow
Figure 3.2 shows the status transition flow of the inverter during data copying operation. Figure 3.3 shows the status transition flow to apply when you
select a function code data block number.
The copy adapter can store ten blocks of function code data in the internal memory.
* The selected copy function name and function code data block number appear alternately.
Figure 3.2 Status Transition during Data Copying