INVERTER SIO Driver
GP-Pro EX Device/PLC Connection Manual
24
External Device Settings
To configure communication settings, use the FUNC/DATA, Up, Down, or PRG/RESET key on the touch panel
located on the front of the External Device. Refer to your External Device manual for details.
1
Turn ON the power of the External Device.
2
Press the PRG/RESET key to move to the program mode.
3
Press the Up or Down key to display the function code group [1.Y_ _ ].
4
Press the FUNC/DATA key.
5
Press the Up or Down key to display the function code you want to set.
6
Press the FUNC/DATA key.
7
Press the Up or Down key to display the setting value.
8
Press the FUNC/DATA key.
9
Press the PRG/RESET key to move to the operation mode.
10
Reboot the External Device.
This completes the External Device settings.
Function Code
Setting
Setup Description
Y11
1
Station address
Y14
2
Speed
Y15
0
Data length selection
Y16
0
Parity bit selection
Y17
0
Stop bit selection
Y20
2
Protocol selection