14
2017 Fueltec Model CF50E Fuel Polishing System
1.
Close inlet & outlet valves on left or right filter
housing.
2.
Open top air bleed valve.
3.
Loosen swing bolt eye nuts and remove housing
cover.
4.
Remove bag filter hold down.
5.
Remove and dispose soiled filter bag after each
use.
6.
Insert new filter bag into housing and seat bag
flange on housing baffle plate.
7.
Insert filter hold down.
8.
Install filter housing cover and swing bolts into
slots in cover.
9.
Tighten swing bolt eye nuts hand tight then 1/4
turn more.
(do not over tighten)
13. Close air bleed valve and open inlet & outlet valves
14. Resume operation.
PRIMARY FILTER REPLACEMENT
The Model CF50E Mobile has two independent primary bag filters within stainless steel
housings. Each filter can be changed without stopping the system by closing the respec-
tive supply and return valves.
Note:
Change primary filter bags when vacuum gauge
reads
15”