background image

 

1-5. Maintenance, service and faults 

 

The UPS system operates with hazardous voltages. Repairs may be carried out only 
by qualified maintenance personnel.   

 

Caution - 

risk of electric shock. Even after the unit is disconnected from the mains 

(building wiring outlet), components inside the UPS system are still connected to the 
battery and electrically live and dangerous.   

 

Before carrying out any kind of service and/or maintenance, disconnect the batteries 
and verify that no current is present and no hazardous voltage exists in the terminals 
of high capability capacitor such as BUS-capacitors.   

 

Only persons are adequately familiar with batteries and with the required 
precautionary measures may replace batteries and supervise operations. 
Unauthorized persons must be kept well away from the batteries.   

 

Caution -

 risk of electric shock. The battery circuit is not isolated from the input 

voltage. Hazardous voltages may occur between the battery terminals and the 
ground. Before touching, please verify that no voltage is present!   

 

Batteries may cause electric shock and have a high short-circuit current. Please take 
the precautionary measures specified below and any other measures necessary when 
working with batteries:   

remove wristwatches, rings and other metal objects   

use only tools with insulated grips and handles.   

 

When changing batteries, install the same number and same type of batteries.   

 

Do not attempt to dispose of batteries by burning them. This could cause battery 
explosion.   

 

Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin 
and eyes. It may be toxic.   

 

Please replace the fuse only with the same type and amperage in order to avoid fire 
hazards.   

 

Do not dismantle the UPS system. 

 
 

 
 

 

 
 

 
 

 
 

 

 
 

 
 
 

Содержание 1.5K

Страница 1: ...1K 1 5K 2K 3K Online UPS Uninterruptible Power Supply System User Manual ...

Страница 2: ...s 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 6 3 Operations 8 3 1 Button operation 8 3 2 LCD Panel 8 3 3 Audible Alarm 10 3 4 LCD display wordings index 10 3 5 UPS Setting 10 3 6 Operating Mode Description 13 3 7 Faults Reference Code 13 3 8 Warning indicator 14 4 Troubleshooting 15 5 Storage and Maintenance 17 6 Specifications 18 ...

Страница 3: ...ver them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the buil...

Страница 4: ...s must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any...

Страница 5: ... are two different types of online UPS standard and long run models Please refer to the following model table Model Type Model Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K L 1 5K L TOWER IEC Type Schuko Type India Type Africa Type NEMA Type 2K L TOWER IEC Type Schuko Type India Type Africa Type NEMA Type 3K L TOWER IEC Type Schuko Type India Type Africa Type NEMA T...

Страница 6: ...ica Type Africa Type NEMA Type NEMA Type NEMA Type UK Type UK Type UK Type 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port ...

Страница 7: ...eral outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon comple...

Страница 8: ...ng this initial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower...

Страница 9: ...de UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to def...

Страница 10: ...tery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is work...

Страница 11: ...ding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives There are 9 programs to set up Refer to below table Paramete...

Страница 12: ...uency setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Interface Setting Pa...

Страница 13: ...0 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac For 110 115 120 127 VAC models 85 115 setting the low voltage poi...

Страница 14: ...ery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but still...

Страница 15: ...econd Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over temperature Sounding every second Charger failure Sounding every second Out of bypass voltage range Sounding every second ...

Страница 16: ...nd the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icon and is flashing on LCD display and alarm is sounding twice every second U...

Страница 17: ... directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD...

Страница 18: ...dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months 1 2 hours Be sure to deliver the spent battery to a recycling facility or ship it to your dealer i...

Страница 19: ... Load 6 THD Non linear Load 4 THD Linear Load 7 THD Non linear Load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 85 88 Battery Mode 83 BATTERY Standard Model Battery Type 12 V 7 AH 12 V 9 AH 12 V 7 AH 12 V 9 AH Numbers 3 3 6 6 Recharge Time 4 hours recover to 90 capacity Typical Charging Current 1 0 A max Charging Volta...

Отзывы: