2

Safety EN

WARNING! 

Incorrect operation or shoddy workmanship can cause serious injury or damage. Commissioning of the 

inverter may only be carried out by trained personnel in accordance with the technical regulations. You should read 
the safety rules before commissioning the equipment or carrying out maintenance work.

WARNING! 

An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules that are 

exposed to light.
-

Make sure that both the AC side and the DC side of the inverter are de-energised before carrying out any con-
nection work. 

-

Only an authorised electrical engineer is permitted to connect this equipment to the public grid.

WARNING! 

An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules.

-

The DC main switch is only to be used to de-energise the power stage set. The connection area is still live when 
the DC main switch is switched off. 

-

Ensure that the power stage set and connection area are disconnected from one another before carrying out 
any maintenance or service tasks.

-

The power stage set, which is enclosed in a separate housing, must only be disconnected from the connection 
area when in a de-energized state.

-

Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained 
service technicians.

WARNING! 

An electric shock can be fatal. Danger from residual voltage in capacitors.

Wait for the capacitors to discharge. The discharge time is 5 minutes.

WARNING! 

An inadequate ground conductor connection can cause serious injury or damage. The housing screws 

provide a suitable ground conductor connection for grounding the housing and must NOT be replaced by any other 
screws that do not provide a reliable ground conductor connection.

WARNING! 

Work that is carried out incorrectly can cause serious injury and damage. Overvoltage protection must 

only ever be installed and connected by a qualified electrical installation engineer! Follow the safety rules!
Make sure that both the AC side and the DC side of the inverter are de-energised before carrying out any installation 
or connection work.

CAUTION! 

Risk of damage to the inverter from dirt or water on the terminals and contacts of the connection area.

-

When drilling, ensure that terminals and contacts in the connection area do not become dirty or wet.

-

The wall bracket without a power stage set does not conform to the protection class of the inverter as a whole, 
and therefore must not be installed without the power stage set.
The wall bracket should be protected from dirt and moisture during installation.

CAUTION! 

Risk of damage to the inverter as the result of incorrectly tightened terminals. Incorrectly tightened ter-

minals can cause heat damage to the inverter that may result in a fire. When connecting AC and DC cables, ensure 
that all the terminals are tightened to the specified torque.

CAUTION! 

Risk of damage to inverter from overload.

-

The maximum amperage when connecting to a single DC terminal is 33 A.

-

Connect the DC+ and DC- cables to the DC+ and DC- terminals on the inverter, taking care to ensure that the 
polarity is correct.

-

The maximum DC input voltage must not exceed 1000 V DC.

NOTE! 

Degree of protection IP 66 is only applicable if the inverter is permanently attached to the wall bracket with 

screws.
Degree of protection IP 20 applies to the wall bracket with no inverter.

NOTE! 

The solar modules connected to the inverter must comply with the IEC 61730 Class A standard.

NOTE! 

When photovoltaic modules are exposed to light they supply current to the inverter.

IMPORTANT! 

Please refer to the leaflet "Installation and commissioning information sheet" (42,0410,1962).

Содержание Symo

Страница 1: ...Fronius Symo Installation Perfect Charging Perfect Welding Solar Energy www youtube com FroniusSolar LEARN MORE WITH OUR HOW TO VIDEOS 42 0410 2024 001 10032014...

Страница 2: ...0...

Страница 3: ...zuverl ssige Schutzleiter Verbindung ersetzt werden WARNUNG Fehlerhaft durchgef hrte Arbeiten k nnen schwerwiegende Sach und Personensch den verursa chen Einbau und Anschluss eines berspannungs Schutz...

Страница 4: ...iable ground conductor connection WARNING Work that is carried out incorrectly can cause serious injury and damage Overvoltage protection must only ever be installed and connected by a qualified elect...

Страница 5: ...remplacer ces vis par d autres vis qui n offriraient pas ce type de connexion de conducteur de terre autoris e AVERTISSEMENT Les erreurs en cours d op ration peuvent entra ner des dommages corporels e...

Страница 6: ...er sustituidos por otros tornillos que no garanticen una conducci n fiable del conductor protector ADVERTENCIA Los trabajos realizados de forma defectuosa pueden causar graves da os materiales y perso...

Страница 7: ...messa a terra del corpo esterno e non devono in alcun caso essere sostituite da altre viti senza collegamento affidabile AVVISO L esecuzione errata dei lavori pu causare gravi lesioni personali e dann...

Страница 8: ...huis en mogen in geen geval door andere schroeven zonder betrouwbare aardedraad worden vervan gen WAARSCHUWING Verkeerd uitgevoerde werkzaamheden kunnen ernstig lichamelijk letsel en zware materi le...

Страница 9: ...r uden sikker jord forbindelse ADVARSEL Forkert udf rt arbejde kan for rsage alvorlige personskader og materielle skader Installation og tils lutning af oversp ndingsbeskyttelsen m kun foretages af au...

Страница 10: ...8 EL DC AC DC DC DC DC Fronius 5 AC DC AC DC 33 A DC DC DC DC DC DC 1000 V DC IP 66 IP 20 IEC 61730 A...

Страница 11: ...9 42 0410 1962...

Страница 12: ...ezet csatlakoz s n lk li m s csavarra cser lni FIGYELMEZTET S A hib san elv gzett munka s lyos szem lyi s r l seket s anyagi k rokat okozhat T lfes z lts g v delem be p t s t s csatlakoztat s t csak e...

Страница 13: ...uyucu iletken ba lant s olmayan di er vidalarla de i tirilmemelidir NOT Hatal olarak ger ekle tirilen i ler ciddi can ve mal kay plar na yol a abilir Bir a r gerilim korumas n n kuru lumu ve ba lant s...

Страница 14: ...no ich zast powa innymi rubami bez niezawodnego pod czenia przewodu ochron nego OSTRZE ENIE Nieprawid owo przeprowadzone prace mog doprowadzi do powstania powa nych obra e cia a oraz szk d materialnyc...

Страница 15: ...ctv m ochrann ho vodi e a proto nesm j b t v dn m p pad nahrazeny jin mi rouby bez spolehliv ho propojen s ochrann m vodi em VAROV N Chybn proveden pr ce m e zap init z va n zran n a materi ln kody Ve...

Страница 16: ...spojenia ochrann ho vodi a VAROVANIE Chybne vykonan pr ce m u zapr ini z va n kody na majetku a osobn ujmu Mont a pripojenie prep ovej ochrany sm vykon va iba licencovan elektroin talat ri Dodr iavaj...

Страница 17: ...confi vel ALERTA Servi os prestados de forma incorreta podem causar danos materiais e les es pessoais graves A in stala o e conex o de uma prote o contra sobretens o somente pode ser realizada por in...

Страница 18: ...dsledarf rbindelse VARNING Felaktigt utf rda arbeten kan f rorsaka sv ra sak och personskador Endast licensierade elinstallat rer f r montera och ansluta ett versp nningsskydd Beakta s kerhetsf reskri...

Страница 19: ...17 Fronius Symo Installation Help Deutsch English Deutsch www fronius com QR link 4204260175DE English www fronius com QR link 4204260175EN...

Страница 20: ...stallation L1 L3 N IP 66 L1 L3 N L1 L3 N L1 L3 N 2000 m 2001 m 2500 m UDCmax 1000 V UDCmax 950 V L1 L3 N 3000 m 2501 m 3001 m 3400 m UDCmax 900 V UDCmax 850 V 3400 m L1 L3 N NH3 L1 L3 N L1 L3 N L1 L3...

Страница 21: ...19 200 mm 100 mm 200 mm 25 C 60 C 0 100 1 2 3 4...

Страница 22: ...20 1 1 2 3 min 3x 2 3...

Страница 23: ...21 1...

Страница 24: ...Cu max Class 4 1 OFF 1 2 Fronius Symo 10 0 3 M max C 63 A Fronius Symo 12 5 3 M max C 63 A Fronius Symo 15 0 3 M max C 63 A Fronius Symo 17 5 3 M max C 63 A Fronius Symo 20 0 3 M max C 63 A AC RCD Na...

Страница 25: ...25 mm DC1 DC2 DC DC 3x TX20 1 2 5 10 mm 10 25 mm 2 1 2 1 DC DC 2 3 D1 D2 D3 D1 D1 D1 15 mm 70 mm D 6 mm 4 1 DC 1 DC 1 PV 1 PV 1 PV 2 DC 1 DC 2 DC 2 DC 2 DC 2 1 2 3 3 4 5 6 1 2 3 max 33 A to a single D...

Страница 26: ...3 3 4 5 6 1 2 3 max 33 A to a single DC terminal MPPT1 max 27 A to a single DC terminal MPPT2 5 2 DC DC 2 1 1 DC 6 0 2000 m UDCmax 1000 V 2001 2500 m UDCmax 950 V 2501 3000 m UDCmax 900 V 3001 3400 m...

Страница 27: ...25 TX 20 10 3x TX20 1 5 1 7 Nm 11 11 2 DC DC 2 1 1 DC 12 DC DC Fronius Symo Installation Help DE berspannungsschutz EN Surge protection...

Страница 28: ...26 DATCOM...

Страница 29: ...27 3 Nm TX25 3 1 6 7 2 4 5...

Страница 30: ...28...

Страница 31: ...29 Operation 1 2 AC ON 2 3 1 3 2 1 4 2 i n s t E X V 0 0 0 3 0 x 0 0 0 1 n e w D E 1 V 0 0 0 8 0 x 0 0 0 1 1 C O N F I G C o u n t r y 5...

Страница 32: ...IL Israel BR2 Brasil 6 kVA IT2 Italia Dimensioni impianto 6 kVA BR3 Brasil 6 kVA IT3 Italia Dimensioni impianto 6 kVA CH Schweiz Suisse Svizzera Svizra ITMT Italia Media tensione CY Cyprus MG50 Microg...

Страница 33: ...31 Firmware Update USB 3 5 4 4 1 2 2...

Страница 34: ...nd all addresses of our sales branches and partner firms Fronius International GmbH 4600 Wels Froniusplatz 1 Austria E Mail pv sales fronius com http www fronius com Fronius USA LLC Solar Electronics...

Отзывы: