Technical data
Selectiva 2 kW
Mains voltage
1)
~ 230 V, ± 15%
Grid frequency
50/60 Hz
Mains fuse protection
2)
max. 16 A
Minimum mains lead cross section
1.5 mm² (0.002325 in.²)
Protection class
I (with ground conductor)
Max. permitted mains impedance Z
max
on
PCC
3)
None
Standby usage
4.9 W
EMC device class
B
Dimensions L x W x H
341 x 110 x 198 mm
(13.43 x 4.33 x 7.8 in.)
Degree of contamination
3
Degree of protection
4)
IP21
Overvoltage category
II
Operating temperature
5)
-20°C to +40°C
(-4°F to 104°F)
Storage temperature
-25°C to +80°C
(-13°F to 176°F)
Relative humidity
maximum 85%
Maximum altitude above sea level
2000 m (6561 ft.)
Mark of conformity
according to rating plate
Product standard
EN62477-1
1)
The device is approved for operation on neutral-earthed networks.
2)
The thermal stress of the circuit breaker must not exceed 30,000 A
2
s.
3)
Interface to a 230/400 V and 50 Hz public grid.
4)
For indoor use only, do not expose to rain or snow.
5)
A high ambient temperature may result in power degradation (derating).
Device-specific
data
Max. AC
current
Max. AC
power
Nominal
voltage
Max.
charging
current
Weight
6)
2040 2 kW
7.9 A
1540 W
24 V
40 A
5.8 kg
(12.79 lb)
2050 2 kW
9.9 A
1930 W
24 V
50 A
6.1 kg
(13.45 lb)
2060 2 kW
12.0 A
2330 W
24 V
60 A
6.1 kg
(13.45 lb)
2070 2 kW
12.1 A
2350 W
24 V
70 A
6.1 kg
(13.45 lb)
58