Information on
‘Field-adjustable
trip points’ and
‘Advanced Grid
Features’
The inverter is equipped with ‘Field adjustable trip points’ and ‘Advanced Grid Features’.
For further information, please contact ‘Fronius Technical Support’ at the following email
address:
.
FCC / RSS Com-
pliance
FCC
This device corresponds to the limit values for a digital device of class B in accordance with
Part 15 of the FCC regulations. The limit values should provide adequate protection
against harmful interference in homes. This device creates and uses high frequency ener-
gy and can interfere with radio communications when not used in accordance with the in-
structions. However, there is no guarantee against interference occurring in a particular
installation.
If this device interferes with radio or television reception when turning the device on and
off, it is recommended that the user solve this with one or more of the following measures:
-
adjust or reposition the receiving antenna
-
increase the distance between the device and the receiver
-
connect the device to another circuit, which does not include the receiver
-
for further support, please contact the retailer or an experienced radio/TV technician.
Industry Canada RSS
The device corresponds to the license-free Industry Canada RSS standards. Operation is
subject to the following conditions:
(1) The device may not cause harmful interference
(2) The device must accept any interference received, including interference that may
cause undesired operation.
Ground Fault De-
tector / Interrupt-
er, Insulation
Monitoring
The inverter is fitted with the following safety functions as required by UL 1741 and the Na-
tional Electrical Code:
Ground fault detector / interrupter (GFDI)
In photovoltaic systems with negatively grounded solar modules, the negative cable from
the solar module is connected to the grounding system in the inverter. If a ground fault oc-
curs in the DC wiring, the inverter disconnects from the grid.
Insulation monitoring
In photovoltaic systems with ungrounded solar modules, the inverter checks the resis-
tance between the photovoltaic system's positive or negative pole and the ground poten-
tial. In the case of a short circuit between the DC+ or DC- cable and the ground (e.g., due
to poorly insulated DC cables or faulty solar modules) the inverter disconnects from the
grid.
Arc detection/in-
terruption
The inverter is equipped with integrated arc detection/interruption, which detects and ex-
tinguishes serial arcs.
For example, a serial arc can occur after the following errors or situations:
-
Poorly-connected plug connections on the solar module
-
Poor or defective cable connections on the solar module side, which enable a connec-
tion against the earth potential
-
Defective solar modules due to problems in the junction box or production errors, such
as high resistance solder connections in individual solar cells
-
Cables incorrectly connected to an inverter’s input terminals
Содержание Primo 208-240
Страница 2: ...2...
Страница 5: ...Allgemeine Informationen...
Страница 6: ......
Страница 14: ...14...
Страница 15: ...Fehler Suchhilfe...
Страница 16: ......
Страница 34: ...34...
Страница 35: ...Komponenten austauschen...
Страница 36: ......
Страница 55: ...55 DE DC Trenner auf ON stellen 6...
Страница 66: ...66...
Страница 67: ...Sicherheitstechnische berpr fung...
Страница 68: ......
Страница 80: ...80...
Страница 83: ...General Information...
Страница 84: ......
Страница 92: ...92...
Страница 93: ...Troubleshooting guide...
Страница 94: ......
Страница 112: ...112...
Страница 113: ...Replacing components...
Страница 114: ......
Страница 133: ...133 EN US Set the DC disconnector to ON 6...
Страница 144: ...144...
Страница 145: ...Safety inspection...
Страница 146: ......
Страница 158: ...158...
Страница 159: ...Appendix...
Страница 162: ...162...
Страница 163: ...163...