Contact Current
-
Measurement should only be carried out once measurement of ground conductor cur-
rent has been carried out successfully
-
The device must remain in operation.
Measurements are taken between a grounded point and the touchable, conductive part
which is not connected with the ground conductor.
The contact current must not exceed 0.5 mA *).
1 Measuring instrument
2 Inverter
6.2 Touchable, conductive part not connected to the
ground conductor
8 Insulated assembly of the object being tested
9 Measurement lead
Ri 1–2 k
Touchable, conductive parts not connected to the
ground conductor
*) These requirements relate to DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. In addi-
tion, individual national requirements and standards must also be observed.
PE
mA
L1
1
2
9
N
PE
L1
N
9
8
6.2
Ri
1-2k
Ω
Содержание Primo 208-240
Страница 2: ...2...
Страница 5: ...Allgemeine Informationen...
Страница 6: ......
Страница 14: ...14...
Страница 15: ...Fehler Suchhilfe...
Страница 16: ......
Страница 34: ...34...
Страница 35: ...Komponenten austauschen...
Страница 36: ......
Страница 55: ...55 DE DC Trenner auf ON stellen 6...
Страница 66: ...66...
Страница 67: ...Sicherheitstechnische berpr fung...
Страница 68: ......
Страница 80: ...80...
Страница 83: ...General Information...
Страница 84: ......
Страница 92: ...92...
Страница 93: ...Troubleshooting guide...
Страница 94: ......
Страница 112: ...112...
Страница 113: ...Replacing components...
Страница 114: ......
Страница 133: ...133 EN US Set the DC disconnector to ON 6...
Страница 144: ...144...
Страница 145: ...Safety inspection...
Страница 146: ......
Страница 158: ...158...
Страница 159: ...Appendix...
Страница 162: ...162...
Страница 163: ...163...