37
*
Depending on the device version
**
Nominal capacity no longer possible
FRONIUS IS 30 /
IS 30 - 48 V
IS 30
IS 30 - 48 V
DC input:
Nominal voltage
24 V
48 V
Voltage range in operation
19 - 32 V
38 - 60 V
Nominal current
100 A
50 A
Max. current
120 A
60 A
AC output (based on DC nominal voltage):
Nominal voltage (+/- 10%)
230 V
230 V
Nominal capacity
2200 VA
2200 VA
Nominal current
10 A
10 A
Max. current
20 A
20 A
Output frequency
50 / 60 Hz *
50 / 60 Hz *
Load detect after
3 W
3 W
Permitted load cos phi
0.3 - 1
0.3 - 1
Harmonic distortion
3.0 %
3.0 %
Relay contact connections:
AC
250 V / 12 A
250 V / 12 A
DC
30 V / 8 A
30 V / 8 A
60 V / 1.5 A
60 V / 1.5 A
General data:
Max. efficiency
93 %
93 %
Power consumption continuous operation
16 W
16 W
Power consumption load detect operation
6 W
6 W
Power consumption standby operation
4 W
4 W
Power consumption OFF operation
0 W
0 W
Temperature range
- 20°C to 50°C**
-20°C to 50°C**
- 4°F to 122°F**
- 4°F to 122°F**
Dimensions l x w x h
384 x 267 x 181 mm 384 x 267 x 181 mm
15.1 x 10.5 x 7.1 in. 15.1 x 10.5 x 7.1 in.
Weight
8 kg
8 kg
17.64 lb.
17.64 lb.
Protection class
IP 20
IP 20
Marks of conformity
CE
CE