33
Error number 333
Over current
Cause:
Short circuit at AC output
Remedy:
Disconnect load, correct short circuit
Error number 334
Internal err
Cause:
Device error
Remedy:
Inform service
Error numbers 335 - 337
Internal err
Cause:
Device error
Remedy:
Inform service
Error number 391
Display lost
Cause:
Communication with display is not possible
Remedy:
Inform service
Error number 392
Display fault
Cause:
Display error
Remedy:
Turn device off/on
Error number 393
Old software
Cause:
AC processor software is incompatible with new firmware display
processor
Remedy:
Update software (service)
Error number 401
Slave fault
Cause:
The master device has detected an error in a slave device in multi-
phase operation
Remedy:
Correct error at slave device
Error number 402
Sync lost
Cause:
Synchronization signal from master device has not been received
multiple times
Remedy:
Check communication connection
Error number 403
Sync lost
Cause:
A reset was triggered at the parallel bus
Remedy:
Device will correct error automatically
Error number 404
No slave
Cause:
Error in communication setup in multi-device operation
Remedy:
Check setup settings and communication connections and correct if
necessary
Error number 405
Old firmware
Cause:
Configuration error after service
Remedy:
Carry out firmware update
Error number 406
Ph cfg err
Cause:
Incorrect phase system setting
Remedy:
Check device settings and communication connections
Displayed Ser-
vice Codes
(continued)