Firmware Update
General
You can update the ‘Fronius Datalogger Web’ firmware from the ‘Firmware update’
selection option.
Procedure:
1.
Download the current firmware from the Fronius homepage
2.
Run the downloaded update file on the PC / laptop
This will start a web server from which ‘Fronius Datalogger Web’ will download the
required files.
3.
Use your Internet browser to open the ‘Fronius Datalogger Web’ website
4.
Open Settings / Firmware update
5.
Enter the IP address of PC / laptop
6.
Click on the ‘Run update’ button
This update process can take several minutes. The power supply to the ‘Fronius
Datalogger Web’ should not be interrupted during this time.
The web interface and the connection to ‘Fronius Solar.access’ or ‘Fronius
Solar.web’ will not be available during the update process.
The update is complete when all LEDs are green or blinking.
If the connection to the server should fail:
-
deactivate the firewall for the duration of the update
-
retry the update
Firmware Update
‘Firmware update’ selection option