Location of the primary meter at the feed-in point. *Terminating resistor R 120 Ohm
The following must be observed in a multi-meter system:
-
Connect the primary meter and the battery to different channels (recommended).
-
The remaining Modbus participants must be distributed equally.
-
Only assign each Modbus address once.
-
Terminating resistors must be positioned individually for each channel.
Menu structure
A graphic view of the menu structure can be found in the User Information that is sup-
plied as standard.
Setting the
address of the
Fronius Smart
Meter
Symbol
Name
Event
Function
Prog
1 x
Increases the set value
Page
1 x
Moves the cursor
+
Enter
1 x
Confirms the entry
1
Press "Prog" and "Page" at the same
time to call up code entry.
2
Enter the password "2633". Increase
the value with "Prog" and change to
the next digit with "Page".
3
Press "Prog" and "Page" at the same
time again to switch to the menu item
"Addr" (address).
4
Set the relevant address.
-
Permissible values: 1 - 14
17