Example 2:
Input
Battery
Fronius
Ohmpilot
Quantity
Primary
meter
Quantity
Secondary
meter
Modbus 0 (M0)
1
3
Modbus 1 (M1)
0
4
0
2
0
1
Multi-meter sys-
tem - Fronius
GEN24 inverter
If several Fronius Smart Meters are installed, a separate address must be set for each
one (see
Setting the address of the Fronius Smart Meter
on page
). The primary
meter is always assigned address 1. All the other meters are numbered consecutively
with the address range from 2 to 14. Different Fronius Smart Meter power categories can
be used in combination.
IMPORTANT!
Use max. 7 secondary meters in the system. To avoid interference, it is recommended to
install the terminating resistors according to chapter
on page
Location of the primary meter in the consumption branch. *Terminating resistor R 120 Ohm
16