Boiler data for planning the flue gas system
Description
PE1 Pellet
7
10
15
20
Flue gas temperature at nominal load
°C
140
150
140
150
Flue gas temperature at partial load
100
100
100
100
Flue gas mass flow at nominal load
kg/h
17
25
36
52
kg/s
0.005
0.007
0.010
0.014
Flue gas mass flow at partial load
kg/h
7
7
16
20
kg/s
0.002
0.002
0.004
0.006
Required feed pressure at nominal load
Pa
5
mbar
0.05
Required feed pressure at partial load
Pa
2
mbar
0.02
Maximum permissible feed pressure
Pa
30
mbar
0.3
Flue pipe diameter
mm
99
1)
129
Supply air connection for room air-
independent operation
80
Combustion air volume at nominal load
m³/h
14
20
29
39
1.optional flue gas diameter of 129 mm without additional connecting adapter possible
Description
PE1 Pellet
25
30
32
35
Flue gas temperature at nominal load
°C
140
150
160
160
Flue gas temperature at partial load
100
100
100
100
Flue gas mass flow at nominal load
kg/h
65
72
78
90
kg/s
0.018
0.020
0.022
0.025
Flue gas mass flow at partial load
kg/h
25
30
32
40
kg/s
0.007
0.008
0.009
0.011
Required feed pressure at nominal load
Pa
5
mbar
0.05
Required feed pressure at partial load
Pa
2
mbar
0.02
Maximum permissible feed pressure
Pa
30
mbar
0.3
Flue pipe diameter
mm
149
Supply air connection for room air-
independent operation
100
Combustion air volume at nominal load
m³/h
49
58
62
68
PE1 Pellet 7-20
PE1 Pellet 25-35
Safety
2
Design Information
Installation Instructions PE1 Pellet 7-35 | M1441017_en