Parameters overview | 5
B0640421_en | Operating instructions Control Panel RBG 3200
17
5.1.2 Heating - Temperatures
Basic display
Heating
Heating circuit 1
Temperatures
Desired room temperature during heating mode
Prerequisite:
Heating circuit used in conjunction with remote control
Room temperature which is regulated during the set heating times.
Desired room temperature during setback mode
Prerequisite:
Heating circuit used in conjunction with remote control
Room temperature which is regulated outside of the set heating times.
Flow temperature SP at outside air temperature of +10°C
First setting point for definition of heating curve.
Flow temperature SP at outside air temperature of -10°C
Second setting point for definition of heating curve.
Outside air temperature
Flow temperature
Example for
underfloor heating
Example for
radiators
Reduction of flow temperature in setback mode
The flow temperature is reduced by this value during setback mode.
External temperature, at which heating circuit pump switches off in heating mode
If the outside air temperature exceeds this value during heating, the heating circuit pumps and
mixing valve are deactivated.
External temperature, at which heating circuit pump switches off in setback mode
If the outside air temperature falls below this value in setback mode, the heating circuit pumps
and mixing valve are activated.
Frost protection temperature
If the room temperature or the flow temperature is lower than the set value, the heating circuit
pump will be switched on and the heating circuit mixer keeps to the maximum heating circuit
flow temperature that is set.