4.4 Technical data
4.4.1 PT4e 120 - 150
Description
PT4e 120 - 150
120
140
150
Rated heat output
kW
120
140
150
Heat output range
36-120
42-140
45-150
Electrical connection
400V / 50Hz / fused C16A
Power consumption (NL/PL) for boiler without ESP
3)
W
127 / 49
125 / 51
124 / 52
Weight of boiler (including stoker, without water)
kg
1308
1641
Boiler capacity (water)
l
228
320
Available feed height of pump
1)
(with ΔT = 20K)
mbar
460
860
790
Max. permitted operating temperature
°C
90
Permitted operating pressure
bar
4
Boiler class as per EN 303-5: 2012
5
Airborne sound level
dB(A)
<70
Permitted fuel as per EN ISO 17225
2)
Part 2: Wood pellets class A1 / D06
Test book number (boiler without ESP
3)
)
PB 144 00 20
PB 165 00 20
PB 166 00 20
Test book number (boiler with ESP
3)
)
PB 170 00 20
PB 171 00 20
PB 172 00 20
1.Pump output less water resistance in the boiler
2.Detailed information on the fuel can be found in the operating instructions in the section entitled “Permitted fuels”
3.ESP: electrostatic particle separator (optional)
Regulation (EU) 2015/1187
Heating space annual rate of use ηs
%
≥ 77
Regulation (EU) 2015/1189 - Emissions in [mg/m³]
1)
seasonal space heating emissions of particulate (PM)
≤ 40
seasonal space heating emissions of organic gaseous compounds
(OGC)
≤ 20
seasonal space heating emissions of carbon monoxide (CO)
≤ 500
seasonal space heating emissions of nitrogen oxides (NO
x
)
≤ 200
1.Emissions of particulate matter, organic gaseous compounds, carbon monoxide and nitrogen oxides shall be expressed standardised to a dry flue gas basis at 10 % oxygen and
standard conditions at 0°C and 1013 millibar
Technology
4
Technical data
Installation Instructions PT4e 120-180 | M2270020_en
19