4.3.8 Fitting adjustable feet in boiler room (optional)
If the closed duct in the boiler room exceeds 2m, an additional support is recommended:
Ø 15 mm
r
Remove the brackets from the supporting post
r
Remove the screws of the trough flange at the relevant position
- 4x hexagonal screw M12 x 35
r
Secure the brackets to the trough flange with the previously removed screws
r
Position the supporting post at the bracket and screw together
- 4x hexagonal screw M12 x 35
Screwing the adjustable feet to the floor:
r
Mark two holes each for the adjustable feet on the left and right on the floor
r
Drill the holes marked
- Drill diameter 15 mm
- Min. drill depth 105 mm
r
Insert the heavy load anchors into the bore holes and tighten with a spanner (AF 17
mm)
4.3.9 Closing the wall penetration
r
Pack the space in the wall penetration with a non-flammable insulating material
Ä
Insulate the partition as per EN 1366-3 / EN 13501-2
r
Close the wall penetration on the store side and the boiler room side with a non-
flammable covering
NOTICE
Do not connect the transfer channel to the brickwork (with concrete), as this will transfer
sound through all the brickwork.