Technical data
ACT VS 3000 - 6000
EN - 35
ID
Description
Limits
Scale
Factory
setting
DrC
- Dryer Remote Control -
Enables/disables dryer remote control
Local /
Remote
-
Local
HdA
- High Dewpoint Alarm -
Sets the service warning intervention threshold
high dew point
0…25.0°C
or
32…77°F
0.5°C
or
1°F
20.0°C
or
68°F
Hdd
- High Dewpoint Delay -
Sets the service warning delay time
high dew point
1…20
minutes
1
minute
15
minutes
HdS
- High Dewpoint Alarm Stop -
Select if high dew point service warning
- Stops the dryer (Yes)
- Does not stop the dryer (No)
Yes / No
-
No
SrV
- Service Setting -
Sets the hours remaining till the next service
NOTA :
00.0 = counter disabled
12.0
(x1000)
hours
0.5
(x1000)
hours
8.0
(x1000)
hours
SCL
- Scale -
Sets the temperature/pressure units of measurement
°C = Temperature in °C and pressure in bar
°F = Temperature in °F and pressure in psi
°C / °F
-
°C
AS
- Auto Restart -
Enables/disables automatic dryer restart after restoring the
electricity supply.
Yes = the dryer restarts automatically after restoring the electricity
supply (if it had been started)
No = The dryer must be restarted using the
button.
Yes / No
-
No
Ard
- Auto Reset Service Warning Drain -
Enables/disables the electronic condensation drain fault to be
reset automatically.
Yes = reset automatically
No = reset manually
Yes / No
-
Yes
ACM
- Alarm Contact Management -
Selects the switching logic for the alarm contact on the DMC50
power module:
1 = any alarm and high dew point
2 = any alarm and any service warning
3 = any alarm
1…3
1
1
IPA
- IP Address -
Selects the IP address to use in the serial connection line
1…255
1
1