11.15.5 How the DMC50 control unit displays and processes a service warning
The service warning
is an irregular event that must be flagged to operators/maintenance technicians. It does not
jeopardise the safety of the machine/operators and it does not stop the dryer, with the exception of the HdS parameter
(STOP dryer due to high dew point), which can be set to stop the dryer.
In the presence of a service warning, the status bar shows a description of the event and turns flashing orange. In this
condition it is not possible to reset the service warning as the cause is still present.
When a service warning is no longer active but has not been reset, the status bar shows a description of the event and
is permanently lit (orange). In this condition the service warning can be reset as the cause has been removed.
With dryer operating (ON)
: the presence of one or more service warnings is
flagged on the display with the status bar changing from green to orange.
With the dryer stopped (STANDBY)
: the presence of one or more service
warnings is not flagged at all on the display.
It is only when the operator wants to start the dryer with the
button that
the DMC50 control unit still enables the dryer to be started in the presence of
a service warning, and displays the warning status by changing the colour of
the status bar (orange).
Resetting a service warning
:
1-
Touch the screen on the status bar where the service warning is shown.
2-
Confirm the service warning is to be reset with OK, or exit without resetting
with Cancel.
NOTE
! After resetting service warnings, the operator/maintenance technician must verify/solve the problem that
caused the service warning.
Service warnings never reset automatically, with the exception of service warning no. 19 (malfunction of electronic
condensation drainer), which is factory-set to enable automatic resetting (Ard parameter
→
Yes setting).
Service
ID
Description
Set
Delay
Reset
15
- Low Dew Point -
Dew point temperature T1 too low
T1 < -1°C
(30.2°F)
5
minutes
T1 > 0°C
(32°F)
16
- High Dew Point -
Dew point temperature T1 too high
T1 > HdA
parameter
Parameter
Hdd
Parameter
HdA-1°K
17
- Probe Fault T2 -
T2 temperature probe fault
-
Flag
immediately
Restore
probe
18
- Probe Fault T3 -
T3 temperature probe fault
-
Flag
immediately
Restore
probe
19
- Drainer -
Malfunction of ELD electronic condensate
drain
Contact
open
20
minutes
Restore
contact
20
- Programmed service -
Scheduled service time expired
Parameter
SrV
Flag
immediately
-
21
- High Discharge Temperature -
Temp. T4 compressor discharge over normal
limits but within safe limits
T4>100°C
(212°F)
60
seconds
T4<95°C
(203°F)
22
- High Evaporating Pressure -
R134.a 4.0 barg
(58,0 psig)
R407C 6.8 barg
(98,6 psig)
60 seconds
R134.a 4.0 barg
(58,0 psig)
R407C 6.8 barg
(98,6 psig)
23
- Low Condensing Pressure -
Variable
180 seconds
Variable
24
- High Condensing Pressure -
Variable
180 seconds
Variable
169201
169318
Specific compressor variable speed drive service warnings
Consult the variable speed drive manual
NOTE
! Service warning no. 19 (drainer) could appear if the dryer operates without compressed air pressure.