background image

19

20

4. Flaring work
A) Firmly hold copper pipe in a die in 

the dimension shown in the table 
below.

1,3

1,6

1,8

2,2

Máx.

0,7

1,0

1,0

2,0

A (mm)

Mín.

OUTER

DIAMETER (mm)

6,35

9,52

12,70

16

Connection Adjustment

1.  Align the pipes to be connected.
2.  Unscrew the flare nut with your 

fingers and then with a wrench and 
screw wrench, as shown in the 
following figure.

OUTER

DIAMETER (mm)

6,35

9,52

12,70

16

TIGHTENING

TORQUE(cm)

1500 (153 kgf/cm)

2500 (255 kgf/cm)

3500 (357 kgf/cm)

4500 (459 kgf/cm)

ADDITIONAL TIGHTENING

TORQUE(cm)

1600 (163 kgf/cm)

2600 (265 kgf/cm)

3600 (367 kgf/cm)

4700 (479 kgf/cm)

Caution: 

Excessive torque can 

break nut depending on installation 
conditions.

Electrical work

1. If there is serious safety problem 

about the power supply, the 
technicians should refuse to install 
the air conditioner and explain to 
the client until the problem is 
solved.

2. Power voltage should be in the 

range of 90%~110%of rated 
voltage.

3. The creepage protector and main 

power switch with a 1.5 times 
capacity of Max. Current of the unit 
should be installed in power circuit.

4. Ensure the air conditioner is 

grounded well.

5. According to the attached Electrical 

Connection Diagram located on the 
panel of the outdoor unit to connect 
the wire.

6. All wiring must comply with local 

and national electrical codes and be 
installed by qualified and skilled 
electricians.

7. An individual branch circuit and 

single receptacle used only for this 
air conditioner must be available. 
See the following table for 
suggested wire sizes and fuse 
specifications:

Electric safety regulations for the initial Installation

Bar

Copper
pipe

Handle

Clamp
handle

Yoke

Red arrow mark

Flare

nut

Pipings

Indoor unit
tubing

Содержание FASC09F2MBHLW

Страница 1: ... TYPE ROOM AIR CONDITIONER MODELS S5 04 07 FM_English_R410A_130320A ATTENTION Please read this manual completely before operating your room air conditioner FAS C E 09F2MBHLW FAS C E 12F2MBHLW FAS C E 18F2MBHLW FAS C E 24F2MBHLW ...

Страница 2: ...ation required to guarantee your safety and the appropriate use of your air conditioner Please read all of the instructions before using the air conditioner and keep this manual for future reference We know you will enjoy your new air conditioner and thank you for choosing our product We hope you will consider us for future purchase The packaging material used is recyclable we recommend that you s...

Страница 3: ... electric shock 5 Keep firearms away It may cause fire 6 Do not operate or stop the unit by switching on or off the power It may cause electric shock or fire due to heat generation 7 Do not operate with wet hands or in damp environment It may cause electric shock 8 Do not allow water to run into electric parts It may cause failure of machine or electric shock 9 Do not drink water drained from air ...

Страница 4: ...unit and degrade the insulation It may cause an electric shock 20 Ventilate the room well when used together with a stove etc An oxygen shortage may occur 21 When the unit is to be cleaned switch off and turn off the circuit breaker Do not clean unit when power is on as it may cause fire and electric shock it may cause an injury 22 Do not put a children pet or house plant where it will be exposed ...

Страница 5: ...d 1 Site with machine oil 2 Sites with a high concentration of salinity such as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such as wireless equipment welding machines and medical installations 5 Sites with flammable gases or volatile material 6 Sites with special environmental conditions 7 Laundry rooms Indoor Unit 1 The unit must be ins...

Страница 6: ...ping extension of no less than 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access the installation site More than 60cm More than 30cm More than 200cm More than 30cm More than 60cm Parts list NUMBERING PART NAME Installation plate Clip anchor Self tapping scr...

Страница 7: ... insulated independently 7 5 4 2 3 1 Indoor unit Outdoor unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More than 60cm More than 15cm A B C Indoor unit installation Installation plate description 2 3m or more 45 41 45 41 45 Attention ...

Страница 8: ...Outdoorunit 5 7mm Do not put the end of drain hose into water Do not block water flow by a rise Connective pipe and drainage installation Drainage 1 Run the drain hose sloping downward Do not install the drain hose as illustrated below 2 When connecting extension drain hose insulate the connecting part of extension drain hose with a shield pipe do not let the drain hose slack Connective pipe insta...

Страница 9: ...side make sure the fan operating properly by putting the unit lengthwise along the wall or using a dust or shield plates 3 Specially in windy area install the unit to prevent the admission of wind If need suspending installation the installation bracket should accord with technique requirement in the installation bracket diagram 4 The installation wall should be solid brick concrete or the same in...

Страница 10: ...tle longer than the measured distance D Cut the cable 1 5m longer than the pipe length 2 Burr removal A Completely remove all burrs from the cut cross section of pipe tube B Put the end of the copper tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing 3 Putting nut on A Remove flare nuts attached to indoor and outdoor unit then put them on pipe tu...

Страница 11: ...echnicians should refuse to install the air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times capacity of Max Current of the unit should be installed in power circuit 4 Ensure the air conditioner is grounded well 5 According to the attached Electrical Co...

Страница 12: ...he system 1 The inside and outside connecting cable can be connected without removing the front grille 2 The indoor power cord type is H05VV F or H05V2V2 F the outdoor power cord and interconnected cord type is H07RN F 3 Lift the indoor unit panel up remove the electrical box cover by loosening the screw 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor r...

Страница 13: ...e cable as illustrated in the installation diagram of indoor and outdoor units 5 Insulate unused cords conductors with PVC tape Process them so they do not touch any electrical or metal parts Connect the cable to the outdoor unit Screw Cover Terminal block of outdoor unit For 8k 12k and 18k Btu models For 24k Btu models Terminal block of outdoor unit To indoor unit To indoor unit To power supply T...

Страница 14: ...w 1 Pressure in the system rises 2 Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of parts in the refrigeration system 6 Therefore the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the...

Страница 15: ...sure charge hose Vacuum pump Charge hose Manifold valve 76cm Hg Charge hose Handle Lo Handle Hi Outdoor unit Indoor unit 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve Electrical safety Perform the electric safe check after completing installation Gas leak check Soap water method Apply a soap water or a liquid neutral detergent on the indoor unit connect...

Страница 16: ...ime it is recommended that the air filter be cleaned before use During continuous use clean the air filter every two weeks 5 This air conditioner was designed for use under the following conditions Optimum performance will be achieved within these operating temperatures If air conditioner is used outside of the above conditions certain safety protection features might come into operation and cause...

Страница 17: ...ir conditioner starts defrosting automatically or when the warm air control feature is activated in heating operation Temperature indicator Displays the temperature settings when the air conditioner is operational Displays the malfunction code Signal receiver 13 16 14 15 Front panel frame Front panel Air filter inside front panel Horizontal airflow grille Vertical airflow grille Temperature sensor...

Страница 18: ... no receiving beep from the indoor unit or if the transmission indicator on the remote controller fails to light 2 The remote controller is powed by two dry batteries R03 LR03X2 housed in the rear part and protected by a cover 3 Remove the cover by pressing and sliding off 4 Remove the old batteries and insert the new batteries placing the and ends correctly 5 Reattach the cover by sliding it back...

Страница 19: ...e control description TEMP Push the button to increase setting temperature or to increase Hour during Timer setting Push the button to decrease setting temperature or to decrease Hour during Timer setting FAN SPEED Used to select the Fan Speed in four steps AUTO LOW MED or HIGH Each time the button is pressed the fan speed mode is shifted TIMER ON Press this button to initiate the auto on time seq...

Страница 20: ...of 8 C The display window of indoor unit will display FP Press the buttons of ON OFF SLEEP FP MODE FAN SPEED UP DOWN and SHORTCUT while operating will cancel the FP LED Disable Active indoor screen Display When pushing more than 2 seconds the FOLLOW ME function will be activated pushing more than 2 seconds again to disable LOCK When you press the recessed LOCK button all current settings are locke...

Страница 21: ... or High 4 Press the ON OFF button to start the air conditioner In the FAN mode the setting temperature is not displayed in the remote controller and you are not able to control the room temperature either In this case only step 1 3 and 4 may be performed Adjusting air flow direction Use the SWING and DIRECT button to adjust the desired airflow direction 1 When push the DIRECT button the horizonta...

Страница 22: ...set time Example To start the air conditioner in 6 hours 1 Press the TIMER ON button the last setting of starting operation time and the signal h will show on the display area 2 Press the TIMER ON button to display 6 0h on the TIMER ON display of the remote controller 3 Wait for 3 seconds and the digital display area will show the temperature again The TIMER ON indicator remains on and this functi...

Страница 23: ...on is only available under COOL AUTO COOL FORCED COOL and DRY mode Before selecting the function it is recommended to run the air conditioner under cooling operation for about half an hour Once the Self Clean function is activated all TIMER setting will be cancelled During SELF CLEAN operation when pressing the SELF CLEAN button on the remote controller again the unit will stop the operation and t...

Страница 24: ...on To automatically swing the air flow direction up down Perform this function while the air conditioner is in operation Clean air function optional Improving the quality of indoor air is one of the purposes of an air conditioner This air conditioner is equipped with ionizer or Plasma Dust Collector Depending on specific configuration of the model With the anions generated by Ionizer the air circu...

Страница 25: ... of the air outlet to the desired position To automatically swing the air flow direction up down Perform this function while the air conditioner is in operation Press the SWING button on the remote controller To stop the function press the SWING button again Press AIR DIRECTION button to lock louver in desired position The AIR DIRECTION and SWING buttons Manual operation without remote control Man...

Страница 26: ...he fresh air filter at least once a month and replace every 4 to 5 months Use a vacuum cleaner filtro de aire filtro de aire then dry 6 Clean the support frame using a vacuum cleaner or water After dry for a couple of hours or until dry 7 Insert the fresh air filter in its original place 8 Insert the high part of the air filter fresh air filter Support frame again in the unit keeping in mind that ...

Страница 27: ... from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit A peculiar smell comes out from the indoor unit This is caused by the indoor unit giving off smells permeated from building material from furniture or smoke The air conditioner turns to FAN only mode from COOL or HEAT For cooling and heating models only mode W...

Страница 28: ...h 5 times per second and the flashing is not stop by disconnecting and connecting the unit 2 Frequent change of fuses and malfunctions in the switch circuit 3 Water spills over the equipment 4 Remote control does not work 5 Any other abnormal situation If your air conditioner malfunctions check the following information to find solutions or probable causes of the failure Do not try to repair the u...

Страница 29: ...55 56 Notes Notes ...

Отзывы: