background image

7

Avoid Service Checklist

Before calling for service,  review  this  list. It  may  save  you time and expense. This 
list  includes  common occurrences that are  not  the result of defective workmanship 

  OCCURRENCE                        SOLUTION

   Air conditioner will not operate.  

Wall plug disconnected. Push plug firmly into wall outlet.

House  fuse  blown  or circuit  breaker  tripped.  Replace fuse with time  delay type or 
reset  circuit breaker.

Selector Control in OFF position. Turn  selector  to  ON (some models) or the desired 
FAN or COOL setting.
Unit  turned  off  by  moving  thermostat  to  a  higher  number  and  then immediately 
turning  back to a colder number. Wait approximately 3 minutes. Listen for compress
or to start.

   Air from unit does not feel cold
   enough.

Turn selector to a higher COOL position

Thermostat set too warm. Set thermostat to colder temperature.

Air conditioner cooling, but
room is too warm- ice forming
on cooling coil behind 
decorative front.

Outdoor  temperature  below  60°F (15°C).  To  defrost  the  coil,  set  selector to FAN 
position. Then, set thermostat to warmer position.

Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set  
selector to FAN .

Thermostat  set  too  cold  for  night-time cooling. To defrost the coil, set selector to a 
FAN position. Then, set thermostat to a warmer position.

Air conditioner cooling, but 
room is too warm-NO ice
forming on cooling coil
behind decorative front.

Dirty air filter-air restricted. Clean air filter. Refer to Care and Cleaning section.

Thermostat set too warm. Turn thermostat clockwise to a colder setting.

Plug current device tripped. Preset RESET  button.

Room temperature below 60°F (15°C). Cooling may not occur until room temperature 
rises above 60°F (15°C).

Temperature  sensing  tube  touching  cold  coil, located  behind  air filter. Straighten 
tube away from coil.

Air   directional  louvers   positioned   improperly.   Position   louvers   for   better   air 
distribution.

Front  of  unit  is  blocked  by  drapes,  blinds,  furniture, etc.-restricts air distribution.
Clear  blockage in front of unit. 

Doors,   windows,  registers,  etc,  open- cold  air  escapes.  Close  doors,  windows,
registers, etc.

Unit  recently  turned  on  in  hot  room,  allow additional time to remove 

“ 

stored heat

from walls, ceiling, floor and furniture.

Air conditioner turns on and 
off rapidly.

Dirty air filter-air restricted. Clean air filter. 

Outside  temperature  extremely  hot.  Set  to  high cool to bring air past cooling coils 
more frequently.

Noise when unit is cooling

Air movement sound. This is normal. If too loud, set to a slower FAN setting.
Sound of  fan  hitting  water-moisture  removal system. This is normal when humidity 
is high. Close doors windows and registers.

Window vibration- poor  installation.  Refer  to  installation instructions or check with 
installer.

Water dripping INSIDE when
unit is cooling.

Improper   installation.  Tilt  air   conditioner  slightly  to  the  outside  to  allow   water 
drainage. Refer to installation instructions - check with installer.

Water dripping OUTSIDE when
unit is cooling.

Unit  removing  large  quantity  of  moisture  from humid room.  This  is normal during
excessively humid days. 

 
or materials in this appliance

Unit  turned  off  and  then  on  too  quickly.  Turn  unit  off  and  wait  3 minutes before 
restarting.

Thermostat set too low. Adjust thermostat to higher number for cooling.

Содержание 819042151-01

Страница 1: ...USE CARE MANUAL THIS AIR CONDITIONER IS EQUIPPED WITH A NEW INDUSTRY STANDARD POWER SUPPLY CORD WITH A TEST RESET FUNCTION READ AND SAVE THESE INSTRUCTIONS AIR CONDITIONER P N 819042151 01 ...

Страница 2: ...nish after installation This warranty does not cover the following 1 CONSEQUENTIAL OR INCIDENTAL DAMAGES SUCH AS PROPERTY DAMAGE AND INCIDENTAL EXPENSES RESULTING FROM ANY BREACH OF THIS WRITTEN OR ANY IMPLIED WARRANTY Note Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation or exclusion may not apply to you 2 Service calls which do not in...

Страница 3: ...to refrigerant passing through the evaporator during normal operation High Pitched Chatter Today s high efficiency compressors may have a high pitched chatter during the cooling cycle Sound of Rushing Air At the front of the unit you may hear the sound of rushing air being moved by the fan Pinging or Swishing Droplets of water hitting the condenser during normal operation may cause pinging or swis...

Страница 4: ...d To minimize shock and fire hazards proper grounding is important The power cord is equipped with a three prong grounding plug and a current leakage detection device for protection against shock firehazards Your air conditioner must be used in a properly grounded wall receptacle If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breake...

Страница 5: ...n for other settings Using Air Conditioner NOTE If the air conditioner is turned off wait 3 minutes before restarting This allows pressure inside the compressor and equalize Failure to follow these instructions may be harmful to your unit 5 The controls featured in this manual are representative of many available models Your model may offer slightly different features Cool Mode The desired cool se...

Страница 6: ...10 ...

Страница 7: ... to a colder setting Plug current device tripped Preset RESET button Room temperature below 60 F 15 C Cooling may not occur until room temperature rises above 60 F 15 C Temperature sensing tube touching cold coil located behind air filter Straighten tube away from coil Air directional louvers positioned improperly Position louvers for better air distribution Front of unit is blocked by drapes blin...

Отзывы: