Your  ZoneAire

®

  Portable  Air  Conditioner  is  designed  to 

evaporate the condensation removed from the interior space 

through  the  exhaust  hose.  Under  certain  conditions  it  is 

possible that the unit will not evaporate 100% of the removed 

moisture.

The unit is designed with a built-in reservoir to accumulate 

excess condensate and help dispose of it.

Internal Water Level

1.  Under any mode if the water level is in the “low” area the 

unit will function normally.

2.  If  the  water  level  is  in  the  “normal”  area  the  unit  will 

continue to function normally while internally evaporating 

the condensate.

3.  If the unit cannot evaporate all of the condensate internally, 

the tank may become full. If the tank becomes full, the unit 

will turn off, and the Water Full light will illuminate.

Draining Water

The water can be drained from the unit by removing the base 

stopper and letting the water drain by gravity.

1.   When  the  WATER  FULL  lamp  is  on  unplug  the  unit 

and move the unit to a suitable location for draining the 

condensation.

2.  Using  the  gravity  drain  method,  ensure  that  the  base 

stopper is located above a suitable area for draining the 

condensate and remove the stopper. Re-install the stopper 

once all water has drained. 

3.  Return the unit to the original location and restore power 

and duct connections.

4.  The WATER FULL indicator should be off and the unit will 

return to normal operating mode.

Permanent Drainage

For permanent and continuous drainage, a 1/2" hose may be 

attached to the unit and led down a drain.

8

Maintenance

Draining excess water

Condensed  water  may  accumulate  in  the  unit.  If  the

internal  tank  becomes  full,  the  Warning  Light  will  shine
and  the  unit  will  not  operate  until  the  unit  has  been
drained.

First, uplug electrical cord from wall outlet. Then, drain
excess water from the tank by placing a pan under the
drain valve, removing the drain plug, and letting the
water drain into the pan. 

When the water stops draining out, replace the drain
plug, and remove the pan of water. Operate the air
conditioner in fan mode to dry the interior of the unit.

Always drain the unit before putting it into storage.

Cleaning and Maintenance

• The unit has an air filter that must be cleaned with

water every two weeks and put back in the unit after it
is completely dry.

• The air discharge grille can be cleaned with a rag or

sponge, warm water and mild detergent.

• Never use hot water, bleach, gasoline, acids, cleaning

fluid or a brush to clean the unit. This will damage the
cabinet and the air discharge area.

• Do not wash the unit with a hose.

Cleaning the filter.

1. Turn Power OFF.

2. Remove  the  air  filter  by  grasping  the  bottom    and

pulling it up and out of the unit.

3. Wash in hot soapy water, rinse and shake dry.
4. 

Replace the filter with the front of the filter toward you. 

5. To dry the filter thoroughly, run your unit in fan mode

for a few minutes. Remember, only a clean filter works
properly and delivers top efficiency at every setting.

Air Conditioner Remote Control 

AAA

IEC R03

1.5V

+

-

AAA

IEC R03

1.5V

The functions work the same as your air conditioner’s
touch controls.

Batteries:  Remove the cover on the back of the remote
controller and insert the batteries with the (+) and (-)
poles pointing in the proper direction.

Drain Valve

Warning: Make sure unit is unplugged before
performing any maintenance procedure.

Proper use and care of
your air conditioner will
help ensure longer life of
the unit. It is
recommended to have a
professional annually
inspect and clean the coils
and condensate water
passages. Expense of
annual inspection is the
consumer’s responsibility.

CAUTION:

• Use only AAA or IEC R03 1.5V batteries.
• Do not attempt to recharge the supplied batteries
• All batteries should be replaced at the same time.
• Do not dispose of the batteries in a fire as they may

explode.

• Do not mix old and new batteries.
• Do not install the batteries with the polarity (+/–)

reversed.

•  Do not mix alkaline, standard (carbon - zinc), or

r

echargeable (nickel-cadmium) batteries.

• Keep batteries and other things that could be

swallowed away from young children. Contact a
doctor immediately if an object is swallowed.

10

CAUTION

Failure to keep air filter clean will result
in poor air circulation. DO NOT operate
without filter. This can render the unit
inoperative.

Removing the filter

CONDENSATION HANDLING

13

Содержание ZoneAir P012A

Страница 1: ...Service Manual Portable Air Conditioner PORT ServMan 04 09 Model P09A P09B P012A P012B ...

Страница 2: ...TIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT CONTACT INFORMATION ...

Страница 3: ...rial Number Identification 6 Technical Specifications 7 Precautions for use 8 Control Panel Operation 9 Remote Control Operation 10 Window Adapter Kit Installation 11 12 Condensation Handling 13 Maintenance and Service 14 Troubleshooting 15 Refrigeration System Diagram 16 Wiring Diagrams 17 Warranty 18 1 ...

Страница 4: ...ssistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and test capacitors according to safe established standards and approved procedures Extreme care proper judgment and safety procedures must be exercised if it becomes necessary to test or troubleshoot equip...

Страница 5: ...t contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious burns Make sure to protect personal and surrounding property with fire proof materials Have a fire extinguisher at hand while using a torch Provide adequate ventilation to vent off toxic fumes and wor...

Страница 6: ... and or minor to serious property damage 4 INTRODUCTION This service manual is designed to be used in conjunction with the installation manuals provided with each unit This service manual was written to assist the professional HVAC service technician to quickly and accurately diagnose and repair any malfunctions of this product This manual therefore will deal with all subjects in a general nature ...

Страница 7: ...unit INTRODUCTION 5 1 Control panel 2 Air outlet 3 Signal receptor 4 Handle 5 Caster 6 Air outlet hose 7 Air filter 8 Air intake hose 9 1 2 water outlet drain 10 Power supply cord ...

Страница 8: ...Manufactured L 0 C 3 F 6 J 9 A 1 D 4 G 7 B 2 E 5 H 8 Year Manufactured A 1 D 4 G 7 K 0 B 2 E 5 H 8 C 3 F 6 J 9 Month Manufactured A Jan D Apr G Jul K Oct B Feb E May H Aug L Nov C Mar F Jun J Sept M Dec L H G K 00001 Production Run Number Product Line R RAC RAC SERIAL NUMBER IDENTIFICATION GUIDE MODEL NUMBER CODE Unit MODEL AND SERIAL Number Unit Identification P 09 A ...

Страница 9: ...2 212 18 40 5 80 125V 15A 5 15P P12A 11500 115 60 10 5 1280 19 5 x 33 6 x 15 5 4 2 235 24 7 40 5 86 125V 15A 5 15P Model Cooling Capacity BTU h Voltage Hz Amps Watts Dimensions W x H x D Dehumidification Pints Hour Indoor Air Circulation CFM Refrigerant Charge 410 A Locked Rotor Amps Net Weight lbs Circuit Rating Plug Face NEMA P09B 10000 115 60 10 8 1200 19 25 x 33 62 x 15 55 4 2 224 21 2 50 77 2...

Страница 10: ...nterference Ensure that the discharge air outlet is free from obstructions and not impeded by walls or other structures Operate the unity ONLY in the upright position When unplugging the unit hold the power plug securely and pull it out carefully Do not use damaged or improper AC socket Do not use the unit near gas appliances or in the vicinity of flammable liquids Failure to follow this warning c...

Страница 11: ...ER USE EXTENSION CORDS TO OPERATE AN AIR CONDITIONER TEST RESET Test Button Reset Button Mode control The mode control has three settings Cool Dehumidify and Fan The settings are adjusted with the Mode Control button A light will indicate which setting is currently being used Cooling operation 1 Press MODE button to choose the cooling mode LCD window will show cool During the cooling operation alw...

Страница 12: ...tion can be accessed from the remote control Battery replacement Remove the cover on the back of the remote control and insert the batteries with the and poles pointing in the proper direction CAUTION Use only AAA or IEC R03 1 5V batteries Remove the batteries if the remote control is not used for a month or longer Do not attempt to recharge the supplied batteries All batteries should be replaced ...

Страница 13: ...hese parts and ensure that all parts are present Window panel Attaches to window opening to allow air exchange for system air transfer Window panel extensions Extends window panel to fit windows of various dimensions Tube adapters Connect air exchange tubes to window panel Screws 12 screws are included for assembling the window adapter kit Some screws may be partially assembled onto window panel A...

Страница 14: ...ontally This installation may also be used for crank style windows 3 Tighten the four screws on the window panel to secure the window panel extensions 4 Close window 5 The window adapter kit should now fit securely within the window frame and you can now attach the air exchange tubes Ifyouarehavingtroubleattachingtheairexchange tubes you may attach the tubes prior to installing the window adapter ...

Страница 15: ...drained from the unit by removing the base stopper and letting the water drain by gravity 1 When the WATER FULL lamp is on unplug the unit and move the unit to a suitable location for draining the condensation 2 Using the gravity drain method ensure that the base stopper is located above a suitable area for draining the condensate and remove the stopper Re install the stopper once all water has dr...

Страница 16: ...he air filter 1 Pull the filter out as shown in the drawing 2 Take out the air filter from the filter cover 3 Wash the air filter by immersing it gently into warm about 40 C or 104 F water with a neutral detergent or vacuum the filter clean 4 Rinse the filter and dry it thoroughly in a shaded place 5 Install the air filter back to its original place Cleaning the air conditioner Clean the surface o...

Страница 17: ...TROUBLESHOOTING 15 ...

Страница 18: ...16 TROUBLESHOOTING The compressor bolts are loose or copper tubes are contacting other metal parts Tighten bolts Adjust copper tubes Unblock below72 F ...

Страница 19: ...17 REFRIGERATOR SYSTEM DIAGRAM SCHEMATIC WIRING DIAGRAM ...

Страница 20: ...uses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed in a corrosive atmosphere default or delay in performance caused by w...

Страница 21: ......

Страница 22: ...20 ...

Страница 23: ...TIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT CONTACT INFORMATION ...

Страница 24: ...AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A PORT ServMan 04 09 ...

Отзывы: