5

Window installation

Maintain a clear distance (from walls, furniture, etc.)
of at least 10 inches around the unit to allow proper
air circulation and prevent damage to the unit.

Important: Do not over-stretch the exhaust tube or
make any unnecessary bends in it.

Installing the window adapter kit

Note: The window adapter kit must be installed and

connected for the air conditioner to work properly in

Cool mode. The window adapter kit is not required

when using the unit in Heat, Dehumidify, or Fan

modes.

Your window adapter kit has been designed to fit
most standard vertical and horizontal window
applications. However, it may be necessary for you to
improvise/modify some aspects of the installation
procedures for certain types of windows.

1. Open window. (fig.A)

2. Place window panel with extensions into window

frame and adjust to width of window. (fig.B)

Window adapter kit may be installed vertically as
well as horizontally. This installaton may also be
used for crank style windows. (fig.E)

3. Tighten the four screws on the window panel to

secure the window panel extensions. 

4. Close window. (fig.C)

5. The window adapter kit should now fit securely

within the window frame and you can now attach
the air exchange tubes. If you are having trouble
attaching the air exchange tubes, you may attach
the tubes prior to installing the window adapter kit.

Attaching the air exchange tubes to the air

conditioner

1.  Attach the tubes to the window adapter kit.

2.  Attach the other end to the air conditioner. 

To attach air exchange tubes: push tube onto tube
adapter and twist until the tab is in place in the hole
on the tube.

To remove air exchange tubes: twist the end until the
tab is clear of the hole in the tube and pull off.

Do not attach the tubes if using the unit in
dehumidify or heat mode.

A

D

E

C

B

Vertical installation

7

8

9

Installing the window adapter kit

Note:  The  window  adapter  kit  must  be  installed  and 

connected for the air conditioner to work properly in Cool 

mode. The window adapter kit is not required when using 

the unit in Dehumidify or Fan modes.
Your  window  adapter  kit  has  been  designed  to  fit  most 

standard  vertical  and  horizontal  window  applications. 

However,  it  may  be  necessary  for  you  to  modify  some 

aspects of the installation procedures for certain types of 

windows.
1.  Open window.
2.  Place window panel with extensions into window frame 

and adjust to width of window. 

  Window adapter kit may be installed vertically as well as 

horizontally. This installation may also be used for crank 

style windows.

3.  Tighten the four screws on the window panel to secure 

the window panel extensions. 

4.  Close window.
5.  The window adapter kit should now fit securely within the 

window frame and you can now attach the air exchange 

tubes. If you are having trouble attaching the air exchange 

tubes,  you  may  attach  the  tubes  prior  to  installing  the 

window adapter kit.

Attaching  the  air  exchange  tubes  to  the  air 

conditioner

1.  Attach the tubes to the window adapter kit.

2.  Attach the other end to the air conditioner. 

To attach air exchange tubes: push tube onto tube adapter 

and twist until the tab is in place in the hole on the tube.

To remove air exchange tubes: twist the end until the tab is 

clear of the hole in the tube and pull off.

Do not attach the tubes if using the unit in dehumidify 

mode.

Maintain a clear distance (from walls, furniture, etc.) 

of at least 10 inches around the unit to allow proper 

air circulation and prevent damage to the unit.

Important:  Do  not  over-stretch  the  exhaust  tube  or 

make any unnecessary bends in it.

12

Содержание ZoneAir P012A

Страница 1: ...Service Manual Portable Air Conditioner PORT ServMan 04 09 Model P09A P09B P012A P012B ...

Страница 2: ...TIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT CONTACT INFORMATION ...

Страница 3: ...rial Number Identification 6 Technical Specifications 7 Precautions for use 8 Control Panel Operation 9 Remote Control Operation 10 Window Adapter Kit Installation 11 12 Condensation Handling 13 Maintenance and Service 14 Troubleshooting 15 Refrigeration System Diagram 16 Wiring Diagrams 17 Warranty 18 1 ...

Страница 4: ...ssistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and test capacitors according to safe established standards and approved procedures Extreme care proper judgment and safety procedures must be exercised if it becomes necessary to test or troubleshoot equip...

Страница 5: ...t contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious burns Make sure to protect personal and surrounding property with fire proof materials Have a fire extinguisher at hand while using a torch Provide adequate ventilation to vent off toxic fumes and wor...

Страница 6: ... and or minor to serious property damage 4 INTRODUCTION This service manual is designed to be used in conjunction with the installation manuals provided with each unit This service manual was written to assist the professional HVAC service technician to quickly and accurately diagnose and repair any malfunctions of this product This manual therefore will deal with all subjects in a general nature ...

Страница 7: ...unit INTRODUCTION 5 1 Control panel 2 Air outlet 3 Signal receptor 4 Handle 5 Caster 6 Air outlet hose 7 Air filter 8 Air intake hose 9 1 2 water outlet drain 10 Power supply cord ...

Страница 8: ...Manufactured L 0 C 3 F 6 J 9 A 1 D 4 G 7 B 2 E 5 H 8 Year Manufactured A 1 D 4 G 7 K 0 B 2 E 5 H 8 C 3 F 6 J 9 Month Manufactured A Jan D Apr G Jul K Oct B Feb E May H Aug L Nov C Mar F Jun J Sept M Dec L H G K 00001 Production Run Number Product Line R RAC RAC SERIAL NUMBER IDENTIFICATION GUIDE MODEL NUMBER CODE Unit MODEL AND SERIAL Number Unit Identification P 09 A ...

Страница 9: ...2 212 18 40 5 80 125V 15A 5 15P P12A 11500 115 60 10 5 1280 19 5 x 33 6 x 15 5 4 2 235 24 7 40 5 86 125V 15A 5 15P Model Cooling Capacity BTU h Voltage Hz Amps Watts Dimensions W x H x D Dehumidification Pints Hour Indoor Air Circulation CFM Refrigerant Charge 410 A Locked Rotor Amps Net Weight lbs Circuit Rating Plug Face NEMA P09B 10000 115 60 10 8 1200 19 25 x 33 62 x 15 55 4 2 224 21 2 50 77 2...

Страница 10: ...nterference Ensure that the discharge air outlet is free from obstructions and not impeded by walls or other structures Operate the unity ONLY in the upright position When unplugging the unit hold the power plug securely and pull it out carefully Do not use damaged or improper AC socket Do not use the unit near gas appliances or in the vicinity of flammable liquids Failure to follow this warning c...

Страница 11: ...ER USE EXTENSION CORDS TO OPERATE AN AIR CONDITIONER TEST RESET Test Button Reset Button Mode control The mode control has three settings Cool Dehumidify and Fan The settings are adjusted with the Mode Control button A light will indicate which setting is currently being used Cooling operation 1 Press MODE button to choose the cooling mode LCD window will show cool During the cooling operation alw...

Страница 12: ...tion can be accessed from the remote control Battery replacement Remove the cover on the back of the remote control and insert the batteries with the and poles pointing in the proper direction CAUTION Use only AAA or IEC R03 1 5V batteries Remove the batteries if the remote control is not used for a month or longer Do not attempt to recharge the supplied batteries All batteries should be replaced ...

Страница 13: ...hese parts and ensure that all parts are present Window panel Attaches to window opening to allow air exchange for system air transfer Window panel extensions Extends window panel to fit windows of various dimensions Tube adapters Connect air exchange tubes to window panel Screws 12 screws are included for assembling the window adapter kit Some screws may be partially assembled onto window panel A...

Страница 14: ...ontally This installation may also be used for crank style windows 3 Tighten the four screws on the window panel to secure the window panel extensions 4 Close window 5 The window adapter kit should now fit securely within the window frame and you can now attach the air exchange tubes Ifyouarehavingtroubleattachingtheairexchange tubes you may attach the tubes prior to installing the window adapter ...

Страница 15: ...drained from the unit by removing the base stopper and letting the water drain by gravity 1 When the WATER FULL lamp is on unplug the unit and move the unit to a suitable location for draining the condensation 2 Using the gravity drain method ensure that the base stopper is located above a suitable area for draining the condensate and remove the stopper Re install the stopper once all water has dr...

Страница 16: ...he air filter 1 Pull the filter out as shown in the drawing 2 Take out the air filter from the filter cover 3 Wash the air filter by immersing it gently into warm about 40 C or 104 F water with a neutral detergent or vacuum the filter clean 4 Rinse the filter and dry it thoroughly in a shaded place 5 Install the air filter back to its original place Cleaning the air conditioner Clean the surface o...

Страница 17: ...TROUBLESHOOTING 15 ...

Страница 18: ...16 TROUBLESHOOTING The compressor bolts are loose or copper tubes are contacting other metal parts Tighten bolts Adjust copper tubes Unblock below72 F ...

Страница 19: ...17 REFRIGERATOR SYSTEM DIAGRAM SCHEMATIC WIRING DIAGRAM ...

Страница 20: ...uses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed in a corrosive atmosphere default or delay in performance caused by w...

Страница 21: ......

Страница 22: ...20 ...

Страница 23: ...TIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT CONTACT INFORMATION ...

Страница 24: ...AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A PORT ServMan 04 09 ...

Отзывы: