background image

34

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS 

 

 

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

Compressor
does not run 

Low voltage 

Check voltage at compressor. 115V & 230V 
units will operate at 10% voltage variance 

Temperature not set cold enough or  
room air thermistor inoperative

Set temperature to lower than ambient
temperature. Test thermistor and replace
if inoperative.

Compressor hums but cuts off on  
overload 

Hard start compressor. Direct test compressor.  
If compressor starts, add starting components 

Open or shorted compressor
windings

Check for continuity & resistance 

Open overload 

 Test overload protector & replace if inoperative 

Open capacitor 

 Test capacitor & replace if inoperative 

Inoperative system button 

Test for continuity in all positions. Replace if  
inoperative

Broken, loose or incorrect wiring 

Refer to appropriate wiring diagrams to check 
wiring. Correct as needed.

 

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

Fan motor

does not run 

Inoperative system button

Broken, loose or incorrect wiring 

 Refer to applicable wiring diagram. Repair. 

Open capacitor 

 Test capacitor & replace if inoperative 

Fan speed button defective. 

Inoperative fan motor 

Test fan motor & replace if inoperative (be sure 
internal overload has had time to reset) 

 

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

Does not cool or  

only cools slightly 

Undersized unit 

 Refer to industry standard sizing chart 

Indoor ambient thermistor open
or shorted.

See alarms. Replace thermistor if necessary.

Dirty

fi

 

l

a

u

n

a

M

 

s

r

e

n

w

O

 

n

i

 

d

e

d

n

e

m

m

o

c

e

r

 

s

a

 

n

a

e

l

C

 

 

r

e

t

l

 

Dirty or restricted condenser or
evaporator coil 

Use pressure wash or biodegradable cleaning 
agent to clean 

Poor air circulation 

 Adjust discharge louvers. Use high fan speed 

Low capacity - undercharge 

 Check for leak & make repair 

Compressor not pumping properly 

Check amperage draw against nameplate. If
not conclusive, make pressure test 

Replace user interface if inoperative

Test button & replace user interface if inoperative 

Possible Solution

Possible Solution

Possible Solution

Содержание WallMaster WE10C33

Страница 1: ...at Back Up WallMaster Money Fan Timer Operation Set Hr Stop Start Temperature Fan Cool Power Cooler Warmer Only Speed Saver Heat Air Conditioners and Heat Pumps Thru the wall Last character may vary 1...

Страница 2: ...ration Repairs Charging 17 20 Hermetic Components Check 21 Reversing Valve Description Operation 22 Testing the Coil and Reversing Valve 23 24 Compressor Checks 25 26 Compressor Replacement 27 28 Rout...

Страница 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 4: ...t contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious...

Страница 5: ...an or the underside of the unit Failure to follow these instructions can result in result in damage to the unit and or minor to serious property damage 4 INTRODUCTION This service manual is designed t...

Страница 6: ...ts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models 3 3 KW Heat Strip Nominal 8th DIGIT Marketing Suffix Indicates Modification Subject to change 9th DIGIT Engineering Suffix Indicates Modif...

Страница 7: ...the compressor stops and the electric heat starts then operates with the fan to maintain indoor comfort The unit remains in electric heat mode DEFROST DRAIN Drain automatically opens at approximately...

Страница 8: ...ogram can be certain that the AHAM Certification Seal accurately states the unit s cooling and heating capacity rating the amperes and the energy efficiency ratio ELECTRICAL DATA ELECTRIC SHOCK HAZARD...

Страница 9: ...ur Power PM Cool Fan Only Heat Clock Start Time Stop Time Smart Fan Fan Speed Mode Timer On Off Money Saver Set Hour 2 3 4 1 6 5 7 9 8 10 11 12 14 13 Figure2 WY WEModelheat coolcontrolpanel Figure 1 W...

Страница 10: ...ns constantly If Indoor temp is 1 5 F above set point compressor turns ON If 1 5 F below set point compressor turns OFF Cool Mode with Money Saver ON Fan cycles with the compressor ON OFF operation If...

Страница 11: ...tton once to see the current clock setting Continue pressing the button until you arrive at the current time Hour only Minutes are not shown on the display Make sure that the A M P M setting is correc...

Страница 12: ...ive presses will scroll through all error codes stored Press the Temp Hour button to see the reverse order of the error codes When the end of the stored error codes is reached the temperature Set Poin...

Страница 13: ...OPEN OR SHORT Normal operation is allowed Replace probe see note below E5 CONDENSER TEMPERATURE PROBE OPEN OR SHORT Normal operation is allowed Replace probe E7 MOTOR OPERATION E9 HEAT PUMP ERROR Dur...

Страница 14: ...illustrations below If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of 180 240 seconds the control will 1 Turn off the backup electric heat 2 W...

Страница 15: ...tor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor This damage usually can be avoided by proper connection of the running capacitor terminals Fr...

Страница 16: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Страница 17: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Страница 18: ...igerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants Failure to follow these procedures could result...

Страница 19: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Страница 20: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 21: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 22: ...posite port liquid line to the indoor coil Refer to refrigerant flow chart This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil In the heating mode of op...

Страница 23: ...side of the system The other two are connected to the indoor and outdoor coils Small capillary tubes connect each end of the main valve cylinder to the A and B portsofthepilotvalve Athirdcapillaryisac...

Страница 24: ...the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure Should the valve fail to shift from coooling to heat...

Страница 25: ...excess braze from all tubing so that they will slip into fittings on new valve 5 Remove solenoid coil from new valve The use of a torch requires extreme care and proper judgment Follow all safety rec...

Страница 26: ...ated within the compressor shell usually due to recycling of the motor is slow to dissipate It may take anywhere from a few minutes to several hours for the overload to reset Checking the External Ove...

Страница 27: ...is obtained the compressor is grounded and must be replaced Check the complete electrical system to the compressor and compressor internal electrical system check to be certain that compressor is not...

Страница 28: ...em will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 410A and nitrogen and leak test all connections with an electronic o...

Страница 29: ...ll refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approv...

Страница 30: ...o dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mechanical as well as the...

Страница 31: ...outside to ensure that the unit s clearances have not been compromised or altered ROUTINE MAINTENANCE Continued Do not drill holes in the bottom of the drain pan or the underside of the unit Not foll...

Страница 32: ...OR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F DIFFERENTIAL F F OUTDOOR TEMPERATURE OUTDOOR AMBIENT TEMPERATURE F...

Страница 33: ...Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches and remains...

Страница 34: ...re sized to meet the cooling load and heater size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Un...

Страница 35: ...P m e l b o r P Fan motor does not run Inoperative system button Broken loose or incorrect wiring Refer to applicable wiring diagram Repair Open capacitor Test capacitor replace if inoperative Fan sp...

Страница 36: ...to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual...

Страница 37: ...M n i e t a r e p O t i n u d e z i s r e v O Inadequate vapor barrier in building structure particularly floors Advise customer e s u a C e l b i s s o P m e l b o r P Unit short cycles Defective th...

Страница 38: ...it undersized Check heat rise across coil If unit operates efficiently check if insulation can be added to attic or walls If insulation is adequate recommend additional unit or larger one Outdoor t st...

Страница 39: ...lve Defective electronic control board Replace electronic control board e s u a C e l b i s s o P m e l b o r P Heating insufficient Heating capillary tube partially restricted Check for partially sta...

Страница 40: ...UCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE PROBLEM PROBLEM PROBLEM PROBLEM PROBLEM PROBL...

Страница 41: ...AT PUMP ELECTRIC SHOCK HAZARD WARNING Turn off electric power before service or installation Extreme care must be used if it becomes necessary to work on equipment with power applied Failure to do so...

Страница 42: ...Hot Warm Warm Hot TVB Hot Not enough pressure differential at start of stroke or not enough fl ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pr...

Страница 43: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL ONLY MODELS 115 Volt WS08C10 WS10C10 WS12C10 230 Volt WS10C30 WS13C30 WS15C30 42 Last character may vary...

Страница 44: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL WITH ELECTRIC HEAT MODELS 230 Volt WE10C33 WE13C33 WE15C33 43 Last character may vary...

Страница 45: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL HEAT PUMP WITH ELECTRIC HEAT MODELS 230 Volt WY09C33 WY12C33 44 Last character may vary...

Страница 46: ...l i ngi nas l eeve deepert han 16 3 4 deep s uch as Fedder sBs l eeve 193 4 deep IDK Internal Drain Kit New cons t r uct i onappl i cat i onswher e acondensat edr ai n syst em hasbeen bui l ti nt ot h...

Страница 47: ...ry walls to support the material above the WSD SLEEVE The following considerations should also be given A Adjustable SUB BASE SB 89 or other unit support must be provided for panel wall type construct...

Страница 48: ...e WSD SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE MENTS section Attach the SLEEVE to the INSIDE WALL by driving two 12A x 2 screws in each side of the SLEEV...

Страница 49: ...RD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD 48 INSTALLATION INSTRUCTIONS FOR BAFFLE...

Страница 50: ...the orange backing from the gasket and apply it to the base of the sleeve see fig B Once the gasket has been properly applied the sleeve is ready for the air conditioner to be installed per the instal...

Страница 51: ...S THE DRAIN PLATE DOWN TO FORM A WATERTIGHT SEAL AGAINST THE SLEEVE BASE 4 DRILL A 625 DIAMETER HOLE IN THE BOTTOM OF THE BASE PAN AS SHOWN IN THE ILLUSTRATION THIS HOLE ALLOWS CONDENSATE TO ENTER THE...

Страница 52: ...loves etc Failure to do so could result in serious injury CUT SEVER HAZARD EXCESSIVE WEIGHT HAZARD WARNING Use two people to lift or carry the unit and wear proper protective clothing Failure to do so...

Страница 53: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS SUBBASE...

Страница 54: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS ARCHITEC...

Страница 55: ...54 54 MECHANICAL HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD...

Страница 56: ...ts from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units in...

Страница 57: ...T CONTACT INFORMATION 56 FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 210 546 0500 877 599 5665 x 261 FAX 210 546 0731 Email tac friedrich com www friedrich com Print...

Страница 58: ...NOTES...

Страница 59: ...NOTES...

Страница 60: ...FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 P 210 546 0500 F 210 546 0731 www friedrich com Printed in the U S A WM ServMan 01 11...

Отзывы: