background image

Recommended procedure for compressor  
replacement

 

1.    Be  certain  to  perform  all  necessary  electrical  and 

refrigeration  tests  to  be  sure  the  compressor  is 
actually defective before replacing. 

2.    Recover  all  refrigerant  from  the  system  though 

the  process  tubes. 

PROPER  HANDLING  OF 

RECOVERED  REFRIGERANT  ACCORDING  TO 
EPA  REGULATIONS  IS  REQUIRED. 

  Do  not  use 

gauge  manifold  for  this  purpose  if  there  has  been 
a  burnout.  You  will  contaminate  your  manifold  and 
hoses.  Use  a  Schrader  valve  adapter  and  copper 
tubing for burnout failures.

3.      After  all  refrigerant  has  been  recovered,  disconnect  

suction and discharge lines from the compressor and  
remove  compressor.  Be  certain  to  have  both  suction  
and discharge process tubes open to atmosphere. 

4.     Carefully pour a small amount of oil from the suction  

stub  of  the  defective  compressor  into  a  clean 
container.  

9.      Evacuate the system with a good vacuum pump capable   

of 

a  fi nal  vacuum  of  200  microns  or  less.  The  system

should be evacuated through both liquid line and suction 
line gauge ports. While the unit is being evacuated, seal 
all openings on the defective compressor. Compressor 
manufacturers will void warranties on units received not 
properly sealed. Do not distort the manufacturers tube 
connections.   

10.    Recharge  the  system  with  the  correct  amount  of

  refrigerant.  The  proper  refrigerant  charge  will  be
   found on the unit rating plate. The use of an accurate

         measuring device, such as a charging cylinder,
         electronic scales or similar device is necessary.
 

COMPRESSOR REPLACEMENT

5.     Using an acid test kit (one shot or conventional kit), test  

the  oil  for  acid  content  according  to  the  instructions  
with the kit. 

6.      If  any  evidence  of  a  burnout  is  found,  no  matter  how  

slight, the system will need to be cleaned up following  
proper procedures. 

7.    Install the replacement compressor. 

8.    Pressurize  with  a  combination  of  R-410A  and  nitrogen 
      and  leak  test  all  connections  with  an  electronic  or 
      Halide  leak  detector.  Recover  refrigerant  and  repair
      any leaks found. 

Repeat Step 8 to insure no more leaks are present.

Unplug and/or disconnect all electrical power 
to the unit before performing inspections, 
maintenances or service. 

Failure to do so could result in electric shock, 
serious injury or death.

WARNING

RISK OF ELECTRIC SHOCK

Sealed Refrigeration System contains refrigerant 
and oil under high pressure.

Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.

Failure  to  follow  these  procedures  could 
result in serious injury or death. 

WARNING

HIGH PRESSURE HAZARD

Extreme care, proper judgment and all safety 
procedures  must  be  followed  when  testing, 
troubleshooting, handling or working around 
unit while in operation with high temperature 
components.  Wear  protective  safety  aids 
such as: gloves, clothing etc. 

Failure to do so could result in serious burn 
injury.

WARNING

HIGH TEMPERATURES

The  use  of  a  torch  requires  extreme  care  and  proper 
judgment.  Follow  all  safety  recommended  precautions 
and  protect  surrounding  areas  with  fi re  proof  materials. 
Have a fi re extinguisher readily available. Failure to follow 
this  notice  could  result  in  moderate  to  serious  property 
damage.

NOTICE

FIRE HAZARD

The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 

Failure to follow proper safety procedures 
result in serious injury or death. 

WARNING

EXPLOSION HAZARD

Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with liquid refrigerant.

Failure to follow these procedures could 
result in minor to moderate injury.

CAUTION

FREEZE HAZARD

27

Содержание WallMaster WE10C33

Страница 1: ...at Back Up WallMaster Money Fan Timer Operation Set Hr Stop Start Temperature Fan Cool Power Cooler Warmer Only Speed Saver Heat Air Conditioners and Heat Pumps Thru the wall Last character may vary 1...

Страница 2: ...ration Repairs Charging 17 20 Hermetic Components Check 21 Reversing Valve Description Operation 22 Testing the Coil and Reversing Valve 23 24 Compressor Checks 25 26 Compressor Replacement 27 28 Rout...

Страница 3: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 4: ...t contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious...

Страница 5: ...an or the underside of the unit Failure to follow these instructions can result in result in damage to the unit and or minor to serious property damage 4 INTRODUCTION This service manual is designed t...

Страница 6: ...ts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models 3 3 KW Heat Strip Nominal 8th DIGIT Marketing Suffix Indicates Modification Subject to change 9th DIGIT Engineering Suffix Indicates Modif...

Страница 7: ...the compressor stops and the electric heat starts then operates with the fan to maintain indoor comfort The unit remains in electric heat mode DEFROST DRAIN Drain automatically opens at approximately...

Страница 8: ...ogram can be certain that the AHAM Certification Seal accurately states the unit s cooling and heating capacity rating the amperes and the energy efficiency ratio ELECTRICAL DATA ELECTRIC SHOCK HAZARD...

Страница 9: ...ur Power PM Cool Fan Only Heat Clock Start Time Stop Time Smart Fan Fan Speed Mode Timer On Off Money Saver Set Hour 2 3 4 1 6 5 7 9 8 10 11 12 14 13 Figure2 WY WEModelheat coolcontrolpanel Figure 1 W...

Страница 10: ...ns constantly If Indoor temp is 1 5 F above set point compressor turns ON If 1 5 F below set point compressor turns OFF Cool Mode with Money Saver ON Fan cycles with the compressor ON OFF operation If...

Страница 11: ...tton once to see the current clock setting Continue pressing the button until you arrive at the current time Hour only Minutes are not shown on the display Make sure that the A M P M setting is correc...

Страница 12: ...ive presses will scroll through all error codes stored Press the Temp Hour button to see the reverse order of the error codes When the end of the stored error codes is reached the temperature Set Poin...

Страница 13: ...OPEN OR SHORT Normal operation is allowed Replace probe see note below E5 CONDENSER TEMPERATURE PROBE OPEN OR SHORT Normal operation is allowed Replace probe E7 MOTOR OPERATION E9 HEAT PUMP ERROR Dur...

Страница 14: ...illustrations below If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of 180 240 seconds the control will 1 Turn off the backup electric heat 2 W...

Страница 15: ...tor Connections The starting winding of a motor can be damaged by a shorted and grounded running capacitor This damage usually can be avoided by proper connection of the running capacitor terminals Fr...

Страница 16: ...sed changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant dri...

Страница 17: ...410A equipment To prevent moisture absorption and lubricant contamination do not leave the refrigeration system open to the atmosphere longer than 1 hour Weigh in the refrigerant charge into the high...

Страница 18: ...igerant and oil under high pressure Proper safety procedures must be followed and proper protective clothing must be worn when working with refrigerants Failure to follow these procedures could result...

Страница 19: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious in...

Страница 20: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 21: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 22: ...posite port liquid line to the indoor coil Refer to refrigerant flow chart This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil In the heating mode of op...

Страница 23: ...side of the system The other two are connected to the indoor and outdoor coils Small capillary tubes connect each end of the main valve cylinder to the A and B portsofthepilotvalve Athirdcapillaryisac...

Страница 24: ...the mid position part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure Should the valve fail to shift from coooling to heat...

Страница 25: ...excess braze from all tubing so that they will slip into fittings on new valve 5 Remove solenoid coil from new valve The use of a torch requires extreme care and proper judgment Follow all safety rec...

Страница 26: ...ated within the compressor shell usually due to recycling of the motor is slow to dissipate It may take anywhere from a few minutes to several hours for the overload to reset Checking the External Ove...

Страница 27: ...is obtained the compressor is grounded and must be replaced Check the complete electrical system to the compressor and compressor internal electrical system check to be certain that compressor is not...

Страница 28: ...em will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 410A and nitrogen and leak test all connections with an electronic o...

Страница 29: ...ll refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approv...

Страница 30: ...o dry thoroughly before reinstalling them ELECTRONIC ELECTRICAL MECHANICAL Periodically at least yearly or bi yearly inspect all control components electronic electrical and mechanical as well as the...

Страница 31: ...outside to ensure that the unit s clearances have not been compromised or altered ROUTINE MAINTENANCE Continued Do not drill holes in the bottom of the drain pan or the underside of the unit Not foll...

Страница 32: ...OR AMBIENT TEMPERATURE F RELATIVE HUMIDITY RH INDOOR COOL HEAT DISCHARGE AIR TEMPERATURE INDOOR F F RETURN AIR TEMPERATURE INDOOR F F DIFFERENTIAL F F OUTDOOR TEMPERATURE OUTDOOR AMBIENT TEMPERATURE F...

Страница 33: ...Trips Reset Button Pops Out The LCDI power cord can trip Reset button pops out due to disturbances on your power supply line Press and release RESET listen for click Reset button latches and remains...

Страница 34: ...re sized to meet the cooling load and heater size is then selected to meet the heating load In extreme northern climates room air conditioners may not be able to be used as a primary source of heat Un...

Страница 35: ...P m e l b o r P Fan motor does not run Inoperative system button Broken loose or incorrect wiring Refer to applicable wiring diagram Repair Open capacitor Test capacitor replace if inoperative Fan sp...

Страница 36: ...to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual...

Страница 37: ...M n i e t a r e p O t i n u d e z i s r e v O Inadequate vapor barrier in building structure particularly floors Advise customer e s u a C e l b i s s o P m e l b o r P Unit short cycles Defective th...

Страница 38: ...it undersized Check heat rise across coil If unit operates efficiently check if insulation can be added to attic or walls If insulation is adequate recommend additional unit or larger one Outdoor t st...

Страница 39: ...lve Defective electronic control board Replace electronic control board e s u a C e l b i s s o P m e l b o r P Heating insufficient Heating capillary tube partially restricted Check for partially sta...

Страница 40: ...UCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE PROBLEM PROBLEM PROBLEM PROBLEM PROBLEM PROBL...

Страница 41: ...AT PUMP ELECTRIC SHOCK HAZARD WARNING Turn off electric power before service or installation Extreme care must be used if it becomes necessary to work on equipment with power applied Failure to do so...

Страница 42: ...Hot Warm Warm Hot TVB Hot Not enough pressure differential at start of stroke or not enough fl ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pr...

Страница 43: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL ONLY MODELS 115 Volt WS08C10 WS10C10 WS12C10 230 Volt WS10C30 WS13C30 WS15C30 42 Last character may vary...

Страница 44: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL COOL WITH ELECTRIC HEAT MODELS 230 Volt WE10C33 WE13C33 WE15C33 43 Last character may vary...

Страница 45: ...WALLMASTER WIRING DIAGRAM ELECTRONIC CONTROL HEAT PUMP WITH ELECTRIC HEAT MODELS 230 Volt WY09C33 WY12C33 44 Last character may vary...

Страница 46: ...l i ngi nas l eeve deepert han 16 3 4 deep s uch as Fedder sBs l eeve 193 4 deep IDK Internal Drain Kit New cons t r uct i onappl i cat i onswher e acondensat edr ai n syst em hasbeen bui l ti nt ot h...

Страница 47: ...ry walls to support the material above the WSD SLEEVE The following considerations should also be given A Adjustable SUB BASE SB 89 or other unit support must be provided for panel wall type construct...

Страница 48: ...e WSD SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE MENTS section Attach the SLEEVE to the INSIDE WALL by driving two 12A x 2 screws in each side of the SLEEV...

Страница 49: ...RD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD 48 INSTALLATION INSTRUCTIONS FOR BAFFLE...

Страница 50: ...the orange backing from the gasket and apply it to the base of the sleeve see fig B Once the gasket has been properly applied the sleeve is ready for the air conditioner to be installed per the instal...

Страница 51: ...S THE DRAIN PLATE DOWN TO FORM A WATERTIGHT SEAL AGAINST THE SLEEVE BASE 4 DRILL A 625 DIAMETER HOLE IN THE BOTTOM OF THE BASE PAN AS SHOWN IN THE ILLUSTRATION THIS HOLE ALLOWS CONDENSATE TO ENTER THE...

Страница 52: ...loves etc Failure to do so could result in serious injury CUT SEVER HAZARD EXCESSIVE WEIGHT HAZARD WARNING Use two people to lift or carry the unit and wear proper protective clothing Failure to do so...

Страница 53: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS SUBBASE...

Страница 54: ...L HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD INSTALLATION INSTRUCTIONS ARCHITEC...

Страница 55: ...54 54 MECHANICAL HAZARD WARNING Be careful with the sharp edges and corners Wear protective clothing and gloves etc Failure to do so could result in serious injury CUT SEVER HAZARD...

Страница 56: ...ts from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units in...

Страница 57: ...T CONTACT INFORMATION 56 FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 210 546 0500 877 599 5665 x 261 FAX 210 546 0731 Email tac friedrich com www friedrich com Print...

Страница 58: ...NOTES...

Страница 59: ...NOTES...

Страница 60: ...FRIEDRICH AIR CONDITIONING CO 10001 Reunion Place Ste 500 San Antonio TX 78216 P 210 546 0500 F 210 546 0731 www friedrich com Printed in the U S A WM ServMan 01 11...

Отзывы: