background image

12

13

Hot Start Sensor

(Heat Pump Models Only)

Under cold room conditions, the Hot Start Sensor brings 

on the heater strips with a call for heat.  This is to dis-

tribute warm air at the beginning of the heat cycle.  Once 

the return air has warmed sufficiently, the heat pump 
mode will begin.

Refrigerant Charging

NOTE:  Because The Ptac System Is A Sealed System, 

Service  Process  Tubes  Will  Have  To  Be  Installed.  

First Install A Line Tap And Remove Refrigerant From 

System.  Make Necessary Sealed System Repairs And 

Vacuum System.  Crimp Process Tube Line And Solder 

End Shut.  Do Not Leave A Service Valve In The Sealed 

System.

Proper  refrigerant  charge  is  essential  to  proper  unit 

operation.  Operating  a  unit  with  an  improper  refrigerant 

charge will result in reduced performance (capacity) and/or 

efficiency. Accordingly, the use of proper charging methods 

during servicing will insure that the unit is functioning as 

designed and that its compressor will not be damaged.

Too much refrigerant (overcharge) in the system is just as 

bad (if not worse) than not enough refrigerant (undercharge). 

They both can be the source of certain compressor failures if 

they remain uncorrected for any period of time. Quite often, 

other problems (such as low air flow across evaporator, 

etc.) are misdiagnosed as refrigerant charge problems. The 

refrigerant circuit diagnosis chart will assist you in properly 

diagnosing these systems.

An overcharged unit will at times return liquid refrigerant 

(slugging)  back  to  the  suction  side  of  the  compressor 

eventually  causing  a  mechanical  failure  within  the 

compressor. This  mechanical  failure  can  manifest  itself 

as valve failure, bearing failure, and/or other mechanical 

failure. The specific type of failure will be influenced by the 

amount of liquid being returned, and the length of time the 

slugging continues.

Not enough refrigerant (undercharge) on the other hand, 

will cause the temperature of the suction gas to increase to 

the point where it does not provide sufficient cooling for the 

compressor motor. When this occurs, the motor winding 

temperature  will  increase  causing  the  motor  to  overheat 

and possibly cycle open the compressor overload protector. 

Continued overheating of the motor windings and/or cycling 

of the overload will eventually lead to compressor motor 

or

overload failure.

Method Of Charging

The acceptable method for charging the PTAC system is 

the Weighed in Charge Method.  The weighed in charge 

method is applicable to all units. It is the preferred method 

to use, as it is the most accurate.

The weighed in method should always be used whenever 

a charge is removed from a unit such as for a leak repair, 

compressor replacement, or when there is no refrigerant 

charge left in the unit. To charge by this method, requires 

the following steps:

1.   Install a piercing valve to remove refrigerant from the 

sealed system.  (Piercing valve must be removed from 

the system before recharging.)

2.   Recover  Refrigerant  in  accordance  with  EPA 

regulations.

3.   Install a process tube to sealed system.

4.   Make necessary repairs to system.

5.   Evacuate system to 300 microns or less.

6.   Weigh in refrigerant with the property quantity of R-22 

refrigerant.

7.   Start unit, and verify performance.

8.   Crimp the process tube and solder the end shut.

Fan Cycle Switch

The fan cycle switch is located behind the decorative front 
cover below the control box. It is designed to operate the fan 
either continuously or intermittently with the compressor or 
heating elements.  When the switch is in the 

CONTINUOUS

 

position, the fan will run continuously when the unit is turned 
on.  With the fan cycle switch in the 

CYCLE

 position, the 

fan will run only when the compressor or heating elements 
cycle on.

NOTE: It is recommended that this switch be set in the continuous position for maximum comfort and 

temperature control. 

Содержание WallMaster PE07K

Страница 1: ...P2K23 DM 4 03 Standard Unit Seacoast Protected Unit Remote Thermostat Unit Service Manual WallMaster P SERIES Packaged Terminal Air Conditioners Packaged Terminal Heat Pumps...

Страница 2: ...4 Overcharged Refrigerant Systems 15 Restricted Refrigerant Systems 18 Capillary Tube Systems 17 Reversing Valve Operation 17 Electrical Circuit And Coil 18 Checking Reversing Valve 18 Touch Test In H...

Страница 3: ...all Sleeve Condenser Coil Condenser Shroud Compressor Basepan Control Panel Front Cover Control Door Filters Gasket Gasket The information contained in this manual is intended for use by a qualified s...

Страница 4: ...C Seacoast Protection X Seacoast Remote Nominal Heater Size 230V or 265V 0 No Heater 2 2 5 KW 3 3 4 KW 5 5 0 KW Voltage K 230 208V 1Ph 60 Hz R 265V 1Ph 60 Hz UNIT IDENTIFICATION PTAC Serial Number Id...

Страница 5: ...3300 13500 INDOOR CFM 250 250 300 300 325 325 350 350 SENSIBLE HEAT RATIO 0 79 0 79 0 76 0 76 0 76 0 76 0 75 0 75 VENT CFM 60 60 60 60 70 70 70 70 GENERAL INFORMATION PE SERIES Model PE07K PE07R PE09K...

Страница 6: ...essure liquid It next will pass through the refrigerant drier if so equipped It is the function of the drier to trap any moisture present in the system contaminants and large particulate matter The li...

Страница 7: ...only Electrical Rating Tables All 230 208 volt units are equipped with power cords Electric shock hazard Turn off electric power before service or installation All electrical connections and wiring MU...

Страница 8: ...s to the desired location 5 Replace the knob when the desired range has been set 6 Replace the control panel EXAMPLE To set a maximum temperature range of approximately 64 to 86 F move the screws to t...

Страница 9: ...ed Terminal G should be energized whenever a call for heating or cooling is made Typically a heat cool thermostat designed for use with electric heat systems will meet this requirement Honeywell Therm...

Страница 10: ...ype In all cases no matter how simple or complex they are simply a switch or series of switches designed to turn equipment or components ON or OFF at the desired conditions An improperly operating or...

Страница 11: ...n the control circuit W using a low range 0 2 0 Amps ammeter After measuring the current draw simply set the heat anticipator to match that value Electronic thermostats do not use a resistance type an...

Страница 12: ...ging continues Not enough refrigerant undercharge on the other hand will cause the temperature of the suction gas to increase to the point where it does not provide sufficient cooling for the compress...

Страница 13: ...ong enough to establish working pressures in the system 15 to 20 minutes During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator an intermittent hissin...

Страница 14: ...ow over the evaporator coil may indicate some of the same symptoms as an overcharged system An over charge can cause the compressor to fail since it would be slugged with liquid refrigerant The charge...

Страница 15: ...ith a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to...

Страница 16: ...mall capillary tubes connect each end of the main valve cylinder to the A and B ports of the pilot valve A third capillary is a common return line from these ports to the suction tube on the main valv...

Страница 17: ...test the heat relay and the reversing valve relay 3 STANDARDHEATPUMPUNITS Checkforlinevoltage at system switch terminal 7 and thermostat terminal 2 If voltage is not present test the system switch Tes...

Страница 18: ...d within a few seconds since the pressures in the system will not have had time to equalize Voltage should be at or above minimum voltage of 197 VAC as specified on the rating plate If less than minim...

Страница 19: ...o determine why the compressor failed Many compressor failures are caused by the following conditions 1 Improper air flow over the evaporator 2 Overcharged refrigerant system causing liquid to be retu...

Страница 20: ...resistor across terminals When checking a dual capacitor with a capacitor analyzer or ohmmeter both sides must be tested Capacitor Check With Capacitor Analyzer The capacitor analyzer will show wheth...

Страница 21: ...hould the thermostat fail any part of this check it should be replaced Some thermostats may have the terminals identified by the letters C H and L Cooling Only Models Cooling Heating Models CONTACTS M...

Страница 22: ...e table below Should the fan cycle switch fail any part of this check it should be replaced Fan Speed Switch Continuity Check Remote Models Only Remove and label all wires from the fan speed switch Co...

Страница 23: ...e unit to cycle between compressor and electric heat operation Electric Heat Switch Check Out The switch may be checked out with an ohmmeter Remove and label the three wires from the switch Terminal 2...

Страница 24: ...ms Allow all items to dry thoroughly before reinstalling them 3 Periodically at least yearly or bi yearly inspect all control components both electrical and mechanical as well as the power supply Use...

Страница 25: ...Conditions High Load Conditions Low Air Flow Across High Air Flow Across Refrigerant System Low Air Flow Across Indoor Coil Indoor Coil Restriction Outdoor Coil Refrigerant System Reversing Valve not...

Страница 26: ...em Restriction Reversing Valve not Fully Seated Low Airflow Across Indoor Coil Low Airflow Across Outdoor Coil Outdoor Ambient Too High for Operation in Heating Refrigerant System Restriction Outdoor...

Страница 27: ...Reversing Valve Stuck Replace the Reversing Valve Replace the Solenoid Coil NO Is the Solenoid Coil Good Is Line Voltage Present at the Solenoid Valve Is the Selector Switch Set for Heat NO SYSTEM CO...

Страница 28: ...28 Wiring Diagram PTAC Models PE 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 SA 1...

Страница 29: ...29 Wiring Diagram PTAC Models PH 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 SA 1...

Страница 30: ...30 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 RA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 RA 1...

Страница 31: ...31 Wiring Diagram PTAC Models PE 07 09 12 15 KOORA 1 Wiring Diagram PTAC Models PE 07 09 12 15 R00SA 1...

Страница 32: ...32 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 SA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 SA 1...

Страница 33: ...33 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 RA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 RA 1...

Страница 34: ...OOTH WIRE POWER F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER SOLENOID CAPACITOR HOT START SENSOR BROWN RED BROWN YELLOW TO INNERWALL...

Страница 35: ...LD SUPPLIED 24 WIRING HARNESS POWER TERMINAL L1 TERMINAL L2 TO UNIT SWITCH SUPPLIED BLACK WIRE SUPPLIED WHITE WIRE TO UNIT SWITCH 24V 240V 208V COM H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOAR...

Страница 36: ...E WIRE FIELD SUPPLIED 24 VOLT WIRES WIRING HARNESS Existing Black Line White Line Supplied Transformer 277V To Unit COM To Fuse Terminal H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOARD PURPLE YE...

Страница 37: ...OLT WIRES FIELD SUPPLIED 24 WIRING HARNESS RIBBED WIRE SMOOTH WIRE POWER CORD To Unit Transformer 230V COM F A N H E R M c S C R H 1 L 3 C 2 4 L 3 COM H L1 L2 1 2 COMP 1 3 2 RED BLACK FAN CAPACITOR BR...

Страница 38: ...WIRES FIELD SUPPLIED 24 WIRING HARNESS To Fuse Terminal White Line Supplied Black Line F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER...

Страница 39: ...sformer WHITE WIRE BLACK WIRE SUPPLIED Existing 277V COM 3 2 1 3 R Y W B G 3 1 2 4 1 4 3 1 1 3 6 2 2 4 4 2 F A N H E R M 3 5 4 1 L 3 H 1 C 2 S R C COM 24V COM 277V C GREEN YELLOW YELLOW RED BROWN YELL...

Страница 40: ...4 03 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in t...

Отзывы: