background image

10

11

Measuring Current Draw

Heat Anticipators

Heat  anticipators  are  small  resistance  heaters  (wired 

in  SERIES  with  the  "W"  circuit)  and  built  into  most 

electromechanical thermostats. Their purpose is to prevent 

wide swings in room temperature during system operation 

in  the  HEATING  mode.  Since  they  are  wired  in  series, 

the "W" circuit will open if one burns out preventing heat 

operation. 

The heat anticipator provides a small amount of heat to 

the thermostat causing it to cycle (turn off) the heat source 

just prior to reaching the set point of the thermostat. This 

prevents exceeding the set point.

In  order  to  accomplish  this,  the  heat  output  from  the 

anticipator  must  be  the  same  regardless  of  the  current 

flowing through it. Consequently, some thermostats have 

an adjustment to compensate for varying current draw in 

the thermostat circuits.

The proper setting of heat anticipators then is important to 

insure proper temperature control and customer satisfaction.  

A heat anticipator that is set too low will cause the heat 

source to cycle prematurely possibly never reaching set 

point.  A heat anticipator that is set too high will cause the 

heat source to cycle too late over shooting the set point.

The  best  method  to  obtain  the  required  setting  for  the 

heat anticipator, is to measure the actual current draw in 

the  control  circuit  ("W")  using  a  low  range  (0-2.0 Amps) 

ammeter.  After measuring the current draw, simply set the 

heat anticipator to match that value.

Electronic  thermostats  do  not  use  a  resistance  type 

anticipator.  These  thermostats  use  a  microprocessor 

(computer) that determines a cycle rate based on a program 

loaded into it at the factory.

Calculating The  Approximate CFM

The  approximate  CFM  actually  being  delivered  can  be 

calculated by using the following formula:

KILOWATTS x 3413

Temp. Rise x 1.08

DO NOT simply use the Kilowatt Rating of the heater (i.e. 

2.5, 3.4, 5.0) as this will result in a less-than-correct airflow 

calculation.  Kilowatts may be calculated by multiplying the 

measured voltage to the unit (heater) times the measured 

current draw of all heaters (ONLY) in operation to obtain 

watts. Kilowatts are then obtained by dividing by 1000.

EXAMPLE: Measured voltage to unit (heaters) is 230 volts.  

Measured Current Draw of strip heaters is 11.0 amps.

                   

230 x 11.0 = 2530

2530/1000 = 2.53 Kilowatts

2.53  x  3413 = 8635

                   Supply Air   

95°F

                   Return Air   

75°F

                   Temperature Rise  20°

                    

20 x 1.08 = 21.6

                    

 8635 

                    

  21.6

 = CFM

 = 400 CFM

If a low range ammeter is not available, a "Clamp-on" type 

ammeter may be used as follows:

1.    Wrap EXACTLY ten (10) turns of wire around the jaws 

of a clamp-on type ammeter.

2.    Connect one end of the wire to the "W" terminal of 

the  thermostat  sub-base,  and  the  other  to  the  "R" 

terminal.

3.    Turn power on, and wait approximately 1 minute, then 

read meter.

4.    Divide meter reading by 10 to obtain correct anticipator 

setting.

Содержание WallMaster PE07K

Страница 1: ...P2K23 DM 4 03 Standard Unit Seacoast Protected Unit Remote Thermostat Unit Service Manual WallMaster P SERIES Packaged Terminal Air Conditioners Packaged Terminal Heat Pumps...

Страница 2: ...4 Overcharged Refrigerant Systems 15 Restricted Refrigerant Systems 18 Capillary Tube Systems 17 Reversing Valve Operation 17 Electrical Circuit And Coil 18 Checking Reversing Valve 18 Touch Test In H...

Страница 3: ...all Sleeve Condenser Coil Condenser Shroud Compressor Basepan Control Panel Front Cover Control Door Filters Gasket Gasket The information contained in this manual is intended for use by a qualified s...

Страница 4: ...C Seacoast Protection X Seacoast Remote Nominal Heater Size 230V or 265V 0 No Heater 2 2 5 KW 3 3 4 KW 5 5 0 KW Voltage K 230 208V 1Ph 60 Hz R 265V 1Ph 60 Hz UNIT IDENTIFICATION PTAC Serial Number Id...

Страница 5: ...3300 13500 INDOOR CFM 250 250 300 300 325 325 350 350 SENSIBLE HEAT RATIO 0 79 0 79 0 76 0 76 0 76 0 76 0 75 0 75 VENT CFM 60 60 60 60 70 70 70 70 GENERAL INFORMATION PE SERIES Model PE07K PE07R PE09K...

Страница 6: ...essure liquid It next will pass through the refrigerant drier if so equipped It is the function of the drier to trap any moisture present in the system contaminants and large particulate matter The li...

Страница 7: ...only Electrical Rating Tables All 230 208 volt units are equipped with power cords Electric shock hazard Turn off electric power before service or installation All electrical connections and wiring MU...

Страница 8: ...s to the desired location 5 Replace the knob when the desired range has been set 6 Replace the control panel EXAMPLE To set a maximum temperature range of approximately 64 to 86 F move the screws to t...

Страница 9: ...ed Terminal G should be energized whenever a call for heating or cooling is made Typically a heat cool thermostat designed for use with electric heat systems will meet this requirement Honeywell Therm...

Страница 10: ...ype In all cases no matter how simple or complex they are simply a switch or series of switches designed to turn equipment or components ON or OFF at the desired conditions An improperly operating or...

Страница 11: ...n the control circuit W using a low range 0 2 0 Amps ammeter After measuring the current draw simply set the heat anticipator to match that value Electronic thermostats do not use a resistance type an...

Страница 12: ...ging continues Not enough refrigerant undercharge on the other hand will cause the temperature of the suction gas to increase to the point where it does not provide sufficient cooling for the compress...

Страница 13: ...ong enough to establish working pressures in the system 15 to 20 minutes During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator an intermittent hissin...

Страница 14: ...ow over the evaporator coil may indicate some of the same symptoms as an overcharged system An over charge can cause the compressor to fail since it would be slugged with liquid refrigerant The charge...

Страница 15: ...ith a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to...

Страница 16: ...mall capillary tubes connect each end of the main valve cylinder to the A and B ports of the pilot valve A third capillary is a common return line from these ports to the suction tube on the main valv...

Страница 17: ...test the heat relay and the reversing valve relay 3 STANDARDHEATPUMPUNITS Checkforlinevoltage at system switch terminal 7 and thermostat terminal 2 If voltage is not present test the system switch Tes...

Страница 18: ...d within a few seconds since the pressures in the system will not have had time to equalize Voltage should be at or above minimum voltage of 197 VAC as specified on the rating plate If less than minim...

Страница 19: ...o determine why the compressor failed Many compressor failures are caused by the following conditions 1 Improper air flow over the evaporator 2 Overcharged refrigerant system causing liquid to be retu...

Страница 20: ...resistor across terminals When checking a dual capacitor with a capacitor analyzer or ohmmeter both sides must be tested Capacitor Check With Capacitor Analyzer The capacitor analyzer will show wheth...

Страница 21: ...hould the thermostat fail any part of this check it should be replaced Some thermostats may have the terminals identified by the letters C H and L Cooling Only Models Cooling Heating Models CONTACTS M...

Страница 22: ...e table below Should the fan cycle switch fail any part of this check it should be replaced Fan Speed Switch Continuity Check Remote Models Only Remove and label all wires from the fan speed switch Co...

Страница 23: ...e unit to cycle between compressor and electric heat operation Electric Heat Switch Check Out The switch may be checked out with an ohmmeter Remove and label the three wires from the switch Terminal 2...

Страница 24: ...ms Allow all items to dry thoroughly before reinstalling them 3 Periodically at least yearly or bi yearly inspect all control components both electrical and mechanical as well as the power supply Use...

Страница 25: ...Conditions High Load Conditions Low Air Flow Across High Air Flow Across Refrigerant System Low Air Flow Across Indoor Coil Indoor Coil Restriction Outdoor Coil Refrigerant System Reversing Valve not...

Страница 26: ...em Restriction Reversing Valve not Fully Seated Low Airflow Across Indoor Coil Low Airflow Across Outdoor Coil Outdoor Ambient Too High for Operation in Heating Refrigerant System Restriction Outdoor...

Страница 27: ...Reversing Valve Stuck Replace the Reversing Valve Replace the Solenoid Coil NO Is the Solenoid Coil Good Is Line Voltage Present at the Solenoid Valve Is the Selector Switch Set for Heat NO SYSTEM CO...

Страница 28: ...28 Wiring Diagram PTAC Models PE 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 SA 1...

Страница 29: ...29 Wiring Diagram PTAC Models PH 07 09 12 15 KOOSA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 SA 1...

Страница 30: ...30 Wiring Diagram PTAC Models PH 07 09 12 15 K 2 3 5 RA 1 Wiring Diagram PTAC Models PE 07 09 12 15 K 2 3 5 RA 1...

Страница 31: ...31 Wiring Diagram PTAC Models PE 07 09 12 15 KOORA 1 Wiring Diagram PTAC Models PE 07 09 12 15 R00SA 1...

Страница 32: ...32 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 SA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 SA 1...

Страница 33: ...33 Wiring Diagram PTAC Models PE 07 09 12 15 R 2 3 5 RA 1 Wiring Diagram PTAC Models PH 07 09 12 15 R 2 3 5 RA 1...

Страница 34: ...OOTH WIRE POWER F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER SOLENOID CAPACITOR HOT START SENSOR BROWN RED BROWN YELLOW TO INNERWALL...

Страница 35: ...LD SUPPLIED 24 WIRING HARNESS POWER TERMINAL L1 TERMINAL L2 TO UNIT SWITCH SUPPLIED BLACK WIRE SUPPLIED WHITE WIRE TO UNIT SWITCH 24V 240V 208V COM H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOAR...

Страница 36: ...E WIRE FIELD SUPPLIED 24 VOLT WIRES WIRING HARNESS Existing Black Line White Line Supplied Transformer 277V To Unit COM To Fuse Terminal H E R M YELLOW RED FAN 2 1 BLACK RED MOTOR TERM BOARD PURPLE YE...

Страница 37: ...OLT WIRES FIELD SUPPLIED 24 WIRING HARNESS RIBBED WIRE SMOOTH WIRE POWER CORD To Unit Transformer 230V COM F A N H E R M c S C R H 1 L 3 C 2 4 L 3 COM H L1 L2 1 2 COMP 1 3 2 RED BLACK FAN CAPACITOR BR...

Страница 38: ...WIRES FIELD SUPPLIED 24 WIRING HARNESS To Fuse Terminal White Line Supplied Black Line F A N 5 H E R M c 3 4 1 C 2 L 3 H 1 S C R H 1 L 3 C 2 9 5 L 6 COM H L1 L2 3 1 8 2 7 4 1 3 2 RED BLACK FAN HEATER...

Страница 39: ...sformer WHITE WIRE BLACK WIRE SUPPLIED Existing 277V COM 3 2 1 3 R Y W B G 3 1 2 4 1 4 3 1 1 3 6 2 2 4 4 2 F A N H E R M 3 5 4 1 L 3 H 1 C 2 S R C COM 24V COM 277V C GREEN YELLOW YELLOW RED BROWN YELL...

Страница 40: ...4 03 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in t...

Отзывы: