Installation

Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1.  Three inches minimum clearance 

on three sides of the unit must be allowed for return airflow, installation access and service access.  See Figures 1 & 2 for clearances 

and reference dimensions.

NOTE: Drain pan must be installed in closet prior to 

chassis insertion into plenum. See Figure 7 for drain pan 

installation details.

•  Vert-I-Pak Chassis 2-ton dimensions:  

 

23" wide x 23" deep x 47 1/4" high.

•  VPAWP1-8/1-14  Wall Plenum cut-out 

dimensions 24 5/8" wide x 30 7/8" high.

•  VPRG4 Access Panel cutout dimensions: 

27" wide by 55 3/4" high.

•  See Figure 8 (Page 10) for proper chassis 

installation.

Figure 3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Exterior Wall

Flexible Ductwork

Rigid Ductwork

VPAWP1-8/1-14 Wall Plenum

Plenum 

VPDP1 drain pan beneath 

unit is required on all 

VEA/VHA24 units. Drain 

pan must be installed prior 

to chassis installation 

Chassis is 

shipped with 

vibration 

isolators 

installed

3" Clearance on all 

three sides minimum for 

service and installation

Optional Platform

Field-supplied 

Filter (25" x 20")

58"

29"

Optional field 

installed drain pan 

(refer to local codes)

VPRG4 Access Panel & 

Return Air Filter Grille

Power 

Disconnect

electrical 

entrance

control box

Figure 4

Top View

Outside Wall

Содержание VEA24K25 Series

Страница 1: ...920 159 03 11 07 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Страница 2: ...ectrical and Thermostat Wiring Diagrams 11 Chassis Operation Fresh Air Door 12 Low Ambient Protection 12 Room Freeze Protection 12 Emergency Heat Override 12 Emergency Heat Operation 12 Service Servic...

Страница 3: ...louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should be kept 12 24 60 VPAK VPAK VPAK POL...

Страница 4: ...I Pak Chassis Specifications Voltage V 230 208 Refrigerant R 22 Chassis Width 23 125 Chassis Depth 23 125 Chassis Height 47 25 Supply Duct Collar 10 Drain Connection 3 4 FPT Min Circuit Amps See Namep...

Страница 5: ...grounded Wire Sizing Use recommended wire size given in tables and install a single branch circuit All wiring must comply with local and national codes NOTE Use copper conductors only CAUTION Electric...

Страница 6: ...ions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation Figure 3 Typical Utility Closet Chassis Shown in Closet...

Страница 7: ...ide wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Страница 8: ...tedrainsystemmustbeconnected to one of the two 3 4 FPT connections 3 The remaining connection must be plugged using the 3 4 pipe plug provided and field suppled teflon tape or pipe joint compound 4 Fa...

Страница 9: ...the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the wall...

Страница 10: ...n the wires through the side hole in the box and under the control components in the box to reach the connection terminal for the wiring 4 Make the wire connections appropriately matching the wires as...

Страница 11: ...03 NOTE THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC CONNECTION TERMINAL Electrical Thermostat Wiring Diagram...

Страница 12: ...h Air Door is an intake system The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil Move the slide left to open and right to close the fresh air door...

Страница 13: ...heefficiencyofyourVert I Pakandallows lint and dirt to accumulate on the indoor air coil Lint and dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replac...

Страница 14: ...coil Fan motor failure Restricted air flow Non condensables in refrigeration system 07 I D coil temperature 30 Deg F for 2 consecutive minutes Alternately flash set point and error code Continue fan o...

Страница 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Страница 16: ...n contact the Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must...

Отзывы: