Friedrich VEA24K25 Series Скачать руководство пользователя страница 8

8

920-159-03

All Vert-I-Pak 

chassis are shipped 

with a 20" x 14" 

filter installed.  If 

an accessory filter 

holder is to be 

used, you MUST 

remove the factory 

shipped filter from 

the chassis.  Do NOT 

use two filters

Indoor Return Air Grille Installation

There are two Indoor Return Air Grille options as shown in Figure 9.  

Choose the option that best suits your needs.  Use the installation 

instructions provided with accessories for installation details.

Return Air Grille Options

Figure 9

Option 2 

Field Supplied

Return Air Grille

Must have a minumum of 250 

square inches of free area.

Notes:

A.  These are the Friedrich recommended return air grille/

filter/access panel arrangements. Consult the factory on 

other arrangements. Improper return air arrangements 

will cause performance problems.

B.  Return air arrangements are shown from the front, but 

can also be installed from the right or left side of the unit.

Drain Pan Installation

Figure 7

Drain Connection 

and Location

CAUTION:

 

THE ACCESSORY DRAIN PAN (VPDP1) MUST BE 

INSTALLED BEFORE INSTALLING THE UNIT.

1.  The accessory drain pan has two (2) provisions (left & right) 

for connecting an external condensate drain.

2.  A field supplied condensate drain system must be connected 

to one of the two 3/4" FPT connections.

3.  The remaining connection must be plugged using the 3/4" 

pipe plug (provided) and field suppled teflon tape or pipe 

joint compound.

4.  Failure to follow these procedures may result in serious 

property damage.

5.  This is the primary drain pan. A field supplied secondary 

condensate pan may be applied. Check with local codes.

Condensate Disposal System

The VPDP1 drain pan features two ¾ female PVC fittings to at

-

tach a drain connection to on the left or right side of the drain pan.  

Condensate piping can be routed to the left, right or beneath the 

unit platform.

 

See drain pan installation manual for more information.

Part 1:

    The system’s first stage increases energy efficiency 

utilizing a factory installed fan that slings the cold 

condensate onto the hot outdoor coil.

Part 2:

    When high outdoor humidity prevents the slinger 

from disposing of all the condensate, the excess 

condensate overflows into the condensate drain pan 

and out of the ¾" internal drain connections.

Part 3:

    If Parts 1 & 2 fail for any reason, excess condensate 

overflows from a spillway directly into the wall plenum 

to the outside of the building. 

 IF THIS OCCURS, 

THIS IS A WARNING THAT THE CHASSIS OR 

DRAIN NEEDS SERVICING.

Option 1 

VPRG4 Return Air Grille 

with Access Panel

A field-supplied (25" x 20") 

filter is mounted inside the 

hinged access door. 

Содержание VEA24K25 Series

Страница 1: ...920 159 03 11 07 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Страница 2: ...ectrical and Thermostat Wiring Diagrams 11 Chassis Operation Fresh Air Door 12 Low Ambient Protection 12 Room Freeze Protection 12 Emergency Heat Override 12 Emergency Heat Operation 12 Service Servic...

Страница 3: ...louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should be kept 12 24 60 VPAK VPAK VPAK POL...

Страница 4: ...I Pak Chassis Specifications Voltage V 230 208 Refrigerant R 22 Chassis Width 23 125 Chassis Depth 23 125 Chassis Height 47 25 Supply Duct Collar 10 Drain Connection 3 4 FPT Min Circuit Amps See Namep...

Страница 5: ...grounded Wire Sizing Use recommended wire size given in tables and install a single branch circuit All wiring must comply with local and national codes NOTE Use copper conductors only CAUTION Electric...

Страница 6: ...ions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation Figure 3 Typical Utility Closet Chassis Shown in Closet...

Страница 7: ...ide wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Страница 8: ...tedrainsystemmustbeconnected to one of the two 3 4 FPT connections 3 The remaining connection must be plugged using the 3 4 pipe plug provided and field suppled teflon tape or pipe joint compound 4 Fa...

Страница 9: ...the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the wall...

Страница 10: ...n the wires through the side hole in the box and under the control components in the box to reach the connection terminal for the wiring 4 Make the wire connections appropriately matching the wires as...

Страница 11: ...03 NOTE THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC CONNECTION TERMINAL Electrical Thermostat Wiring Diagram...

Страница 12: ...h Air Door is an intake system The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil Move the slide left to open and right to close the fresh air door...

Страница 13: ...heefficiencyofyourVert I Pakandallows lint and dirt to accumulate on the indoor air coil Lint and dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replac...

Страница 14: ...coil Fan motor failure Restricted air flow Non condensables in refrigeration system 07 I D coil temperature 30 Deg F for 2 consecutive minutes Alternately flash set point and error code Continue fan o...

Страница 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Страница 16: ...n contact the Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must...

Отзывы: