5

920-159-02 (10-04)

electrical 

entrance

control box

Fig ure  4

Top View

II.  Installation

1)  Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1.  Three inches minimum clearance on 
three sides of the unit must be allowed for return airfl ow, installation access and service access.  See Figures 1 & 2 for clear anc es and 
ref er ence di men sions.

NOTE: Drain pan must be installed in closet prior to chassis 
insertion into plenum. See Figure 7 (page 8) for drain pan 
installation details.

•  Vert-I-Pak Chassis 2-ton dimensions:  

23" wide x 23" deep x 47 1/4" high.

•  VPAWP1-8/1-14  Wall Plenum cut-out 

dimensions 24 5/8" wide x 30 7/8" high.

•  VPRG4 Access Panel cutout dimensions: 

27" wide by 55 3/4" high.

•  See Figure 8 (Page 10) for proper 

chassis installation.

Fig ure  3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Exterior Wall

Flexible Ductwork

Rigid Ductwork

VPAWP1-8/1-14 Wall Plenum

Plenum 

VPDP1 drain pan 
beneath unit is 
required on all 
VEA/VHA24 units. 
Drain pan must be 
installed prior to 
chassis installation 

Chassis is 
shipped with 
vibration 
isolators 
installed

3" Clearance on all 

three sides minimum for 

service and installation

Optional Platform

Field-supplied 
Filter (25" x 20")

58"

29"

Optional field 

installed drain pan 

(refer to local codes)

VPRG4 Access Panel & 
Return Air Filter Grille

Power 
Disconnect

Содержание VEA24K00 Series

Страница 1: ...920 159 02 10 04 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Страница 2: ...tion 9 Thermostat Control 12 10 Low Ambient Protection for Compressor Fan 12 11 Heating Defrost Heat Pump Models only 12 12 Fresh Air Door 13 13 Condensate Disposal System 13 IV Service Maintenance Wa...

Страница 3: ...bery a clearance of 24 from the outdoor louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 sh...

Страница 4: ...tors under unit Factory collar accepts 10 ex duct Section I General Speci cations VERT I PAK MODEL IDENTIFICATION GUIDE MODEL NUMBER V E A 24 K 50 RT A SERIES ELECTRIC HEATER SIZE A Series 00 No elect...

Страница 5: ...x 23 deep x 47 1 4 high VPAWP1 8 1 14 Wall Plenum cut out dimensions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis inst...

Страница 6: ...e outside wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the...

Страница 7: ...2 4 K 7 5 V H A V E A 2 4 K 1 0 230 208 230 208 230 208 230 208 230 208 230 208 68 68 68 68 68 68 13 7 12 4 13 7 12 4 13 7 12 4 13 7 12 4 13 7 12 4 13 7 12 4 17 2 15 9 22 1 20 3 30 7 28 1 44 3 40 3 57...

Страница 8: ...that branch circuit or general purpose outlet is grounded Wire Sizing Use recommended wire size given in tables and installasinglebranchcircuit Allwiringmustcomply with local and national codes NOTE...

Страница 9: ...KW 2 5 KW 3 4 KW HEATER BLACK SEE NOTE 6 PRESSURE WHITE RELAY HEAT RELAY HEAT RELAY HEAT RELAY HEAT BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK BLACK RED RED RED RED RED RED RED RED 2 5KW 3 4KW 5...

Страница 10: ...ccessories for installation details Return Air Grille Options Figure 9 VPRG2 Return Air Grille Unit requires a eld supplied access door or panel and a 16 x 20 lter VPRG4 Return Air Grille with Access...

Страница 11: ...drain to the condensate exit location Be sure to use te on tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing...

Страница 12: ...callyswitchestoelectricheatduring defrost Whentheoutdoorambienttemperaturedropsbelowa45 F factory setting the chassis automatically switches to electric heat As outdoor ambient temperatures rise above...

Страница 13: ...bly Maintenance can be accomplished easily by referring to the following directions However before performing any maintenance consider these important safety precautions WARNING ElectricalShockHazard...

Страница 14: ...pany International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must be presented to establish the date of insta...

Страница 15: ...thermostat with one touch adjustment Mounts to wall for control of unit Same as VPAL2 but can be ordered in a special color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver tha...

Страница 16: ...ctory Certi ed Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 Fax 210 357 4480 www friedrich c...

Отзывы: