7
920-159-02 (10-04)
3) Electrical Information
Electrical Data
* Single circuit from main box. Based on copper wire, single in su lat ed conductor at 60°C.
NOTE:
Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for over seas applications.
SAMPLE
VHA/VEA24K25 VHA/VEA24K34 VHA/VEA24K50VHA/VEA24K75VHA/VEA24K10
230/208
230/208
230/208
230/208
230/208
230/208
68
68
68
68
68
68
13.7/12.4
13.7/12.4
13.7/12.4
13.7/12.4
13.7/12.4
13.7/12.4
17.2/15.9
22.1/20.3
30.7/28.1
44.3/40.3
57.9/52.7
15.6/15.6
25/25
25/25
35/30
45/45
60/60
20/20
H A R D
W I R E D
14/14
12/12
8/10
6/6
4/6
14/14
Voltage ( V)
LRA - Comp. (A)
Cooling Current (A)
MIN. Ckt. Amps (A)
Max Branch Circuit Fust (Amps)
Power Connection
Recommended Branch
Circuit Wire Sizes*
AWG - American Wire Gauge
MODEL
VHA/VEA24K00
Sample Name plate (see your chassis name plate)