background image

—13—

— Replacement of the refrigeration cycle.

1. When replacing the refrigeration cycle, be sure to

discharge the refrigerant system using a Freon

TM

recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon

TM

. Leave the valve in place after 

servicing the system.

2. After discharging the unit completely, remove the

desired component, and unbrace the pinch-off
tubes.

3. Solder service valves into the pinch-off tube ports,

leaving the valves open.

4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.

1) Connect the vacuum pump, as illustrated Fig.

18A.

2) Start the vacuum pump, slowly open manifold 

valves A and B with two full turns
counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold

and entire system.

3) Operate the vacuum pump for 20 to 30 minutes, 

until 600 microns of vacuum is obtained. Close 
valves A and B, and observe vacuum gauge for 
a few minutes. A rise in pressure would 
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop 

the vacuum pump.

4) Remove the hose from the vacuum pump and

place it on the charging cylinder. See Fig. 18B.
Open valve C.
Discharge the line at the manifold connection.

5) The system is now ready for final charging.

6. Recharge as follows :

1) Refrigeration cycle systems are charged from the

High-side. If the total charge cannot be put 
in the High-side, the balance will be put in the 
suction line through the access valve which you 
installed as the system was opened.

2) Connect the charging cylinder as shown in Fig. 18B.

With valve C open, discharge the hose at the
manifold connection.

3) Open valve A and allow the proper charge to 

enter the system. Valve B is still closed.

4) If more charge is required, the high-side will not 

take it. Close valve A.

5) With the unit running, open valve B and add the 

balance of the charge.

a. Do not add the liquid refrigerant to the Low-

side.

b. Watch the Low-side gauge; allow pressure to 

rise to 30 lbs.

c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the 

charge is in the system.

6) When satisfied the unit is operating correctly, 

use the pinch-off tool with the unit still running 
and clamp on to the pinch-off tube. Using a tube 
cutter, cut the pinch-off tube about 2 inches from 
the pinch-off tool. Use sil-fos solder and solder 
pinch-off tube closed. Turn off the unit, allow it to 
set for a while, and then test the leakage of the 
pinch-off connection.

NOTES

If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.

CAUTION

Содержание UE08A13A

Страница 1: ...US08 US10 US12 UE08 UE10 UE12 2 03 Thru the Wall Series Thru the Wall Series Service and Parts Manual 115 Volts UE08A13A US08A10A US10A10A US12A10A 230 Volts US10A30A UE10A33A US12A30A UE12A33A...

Страница 2: ...RCUIT DIAGRAM 29 6 EXPLODED VIEW 31 7 REPLACEMENT PARTS LIST 32 1 PREFACE This SERVICE MANUAL provides various service information including the mechanical and electrical parts etc This room air condi...

Страница 3: ...OOR C 35 DB 23 9 WB EVAPORATOR 2 ROW 12 STACKS 2 ROW 11 STACKS CONDENSER FAN INDOOR TURBO FAN FAN OUTDOOR PROPELLER TYPE FAN WITH SLINGER RING FAN SPEEDS FAN COOLING 2 3 FAN MOTOR 6 POLES OPERATION CO...

Страница 4: ...700 1 030 1 050 1 200 1 230 5 2 4 7 6 2 5 8 9 5 9 5 26 7 DB 19 4 WB 35 DB 23 9 WB 440 15 5 OZ 465 16 4 OZ 2 ROW 12 STACKS 2 ROW 11 STACKS 2 ROW 17 STACKS L BENDED TYPE TURBO FAN PROPELLER TYPE FAN WIT...

Страница 5: ...10 0 9 5 9 5 3 850 9 200 11 200 1 230 2 900 3 500 10 7 14 0 15 3 26 7 DB 19 4 WB 35 DB 23 9 WB 21 1 DB 15 6 WB 8 3 DB 6 1 WB 425 15 0 OZ 440 15 5 OZ 465 16 4 OZ 2 ROW 12 STACKS 2 ROW 11 STACKS 2 ROW 1...

Страница 6: ...the FAN ONLY position Side air intake side cooled air discharge Built in adjustable THERMOSTAT Washable one touch filter Compact size 6 PULL OPEN PUSH CLOSE Off Turns air conditioner off Med Fan Only...

Страница 7: ...at Heating with the high speed fan operation Turn the Temperature Knob to the desired setting The central position is a normal setting for average conditions You can change this setting if necessary i...

Страница 8: ...OL BOX 1 Remove the front grille Refer to section 2 1 1 2 Remove the screw which fasten the control box See Fig 3 3 Pull the control box from the barrier See Fig 3 4 Discharge the capacitor by placing...

Страница 9: ...5 7 Remove the orifice See Fig 5 8 Remove the clamp which secures the turbo fan with plier See Fig 6 9 Remove the turbo fan with plier or your hand without touching blades See Fig 7 10 Re install the...

Страница 10: ...y system install one such as a WATCO A 1 before venting the FreonTM Leave the valve in place after servicing the system 3 Disconnect the 3 leads from the compressor 4 After purging the unit completely...

Страница 11: ...cification marked on the supply cord fitted to the unit 2 3 5 THERMOSTAT 1 Remove the control box Refer to section 2 1 3 2 Unfold the control box Refer to section 2 3 3 3 Remove the 2 screws which fas...

Страница 12: ...rator at the left side and the right side 4 Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors 5 Remove the evaporator 6 Re install the compo...

Страница 13: ...fold connection 5 The system is now ready for final charging 6 Recharge as follows 1 Refrigeration cycle systems are charged from the High side If the total charge cannot be put in the High side the b...

Страница 14: ...r proof seal Leak detector Tubing cutter Hand Tools to remove components Service valve A COMPOUND GAUGE EVAPORATOR LOW PRESSURE SIDE COMPRESSOR CAPILLARY TUBE CONDENSER HIGH PRESSURE SIDE SEE INSETS B...

Страница 15: ...ons 2 Size options To avoid risk of personal injury property damage or product damage due to the weight of this device and sharp edges that may be exposed Air conditioners covered in this manual pose...

Страница 16: ...Qty Plastic grille 263 4 x 161 2 1 Horizontal Insulation Strips 13 8 x 5 8 x 273 16 1 13 8 x 13 8 x 273 16 1 Around Insulation Strips 13 8 x 3 4 x 611 2 1 13 8 x 13 8 x 611 2 1 Support Block 13 4 x 13...

Страница 17: ...e bottom of the sleeve as shown below Remove the backing from the Around Insulation strip 13 8 x 3 4 x 611 2 and attach that to the inside front of the sleeve as shown below Install the new unit into...

Страница 18: ...l Insulation strip 13 8 x 5 8 x 273 16 and attach that to the inside bottom of the sleeve as shown below Remove the backing from the Around Insulation strip 13 8 x 3 4 x 611 2 and attach that to the i...

Страница 19: ...all Trim 2 ea FIG 31 Air conditioners covered in this manual pose an excessive weight hazard Two or more people are needed to move and install the unit To prevent injury or strain use proper lifting a...

Страница 20: ...king from the Horizontal Insulation strip 13 8 x 13 8 x 273 16 and attach that to the inside bottom of the sleeve as shown below Remove the backing from the Around Insulation strip 13 8 x 13 8 x 611 2...

Страница 21: ...the front of the air conditioner until trim is flush with sleeve as shown below 8 Air conditioners covered in this manual pose an excessive weight hazard Two or more people are needed to move and ins...

Страница 22: ...h to use an extension cord use a CSA certified UL listed 3 wire grounding extension cord rated 15A 125V 3 4 1 ELECTRICAL DATA FOR 115V MODEL 3 4 2 ELECTRICAL DATA FOR 230 208V MODEL 3 4 3 ELECTRICAL S...

Страница 23: ...m Refer to Fig 41 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle MOTOR COMPRESSOR OIL LIQUID REFRIGERANT CAPILLARY TUBE OUTSIDE COOLING AIR FOR REFRIGERANT PASS...

Страница 24: ...gas leakage Repair gas leak Replacement of unit if the unit is beyond repair Satisfactory operation with temperature difference of inlet outlet air 44 6 50 F Check heat load increase Unexpected residu...

Страница 25: ...ation Replacement of fan motor Regular but fails to start Replacement of compressor locking of rotor metal Improper thermostat setting Loose terminal connection Improper wiring Irregular motor resista...

Страница 26: ...earings if motor shaft will not rotate replace the motor Check voltage See limits on this page If not within limits call an electrician Test capacitor Check bearings Does the fan blade rotate freely I...

Страница 27: ...Check the position of knob If not at the coldest setting advance the knob to this setting and restart unit Check continuity of the thermostat Replace thermostat if circuit is open Check the capacitor...

Страница 28: ...e causing the compressor to cycle Straighten the fins or replace the coil Test capacitor Check the terminals If loose repair or replace Check the system for a restriction If restricted clean of replac...

Страница 29: ...MARKS DESCRIPTION POWER CORD ROTARY SWITCH FAN MOTOR CAPACITOR THERMOSTAT COMPRESSOR OVERLOAD PROTECTOR US08A10A US10A10A US12A10A US10A30A US12A30A 2H00677R 2H00677S 2H00677G 2H00598E 4681A20044G 468...

Страница 30: ...OTOR CAPACITOR ROTARY SWITCH POWER INPUT 7 1 8 6 4 2 F C C H RD BL BK BL BK L H OR BR OR BR THERMOSTAT WH BK YL BL RD RD YL C L H R S C BR YL O L P BK RD RD RD FUSE LINK BI METAL THERMOSTAT HEATER BL...

Страница 31: ...A33A 354210 753010 753011 349480 554031 W48602 559010 346811 349600 567502 349001 130410 352113 35211A 352115 W48602 249950 137215 149410 W0CZZ 264110 130900 435301 135312 147581 147582 2 147582 1 352...

Страница 32: ...SY 5239A10002E R 349001 DAMPER VENTILATION 4900A20001A R E 135312 GRILLE ASSY FRONT 3531A20121A R 135313 GRILLE INLET 3530A20053A R 147581 LOUVER HORIZONTAL 4758A20008B R 147582 1 LOUVER VERTICAL 4758...

Страница 33: ...MPER VENTILATION 4900A20001A R E 135312 GRILLE ASSY FRONT 3531A20121A R 135313 GRILLE INLET 3530A20053A R 147581 LOUVER HORIZONTAL 4758A20008B R 147582 1 LOUVER VERTICAL 4758A20009A R 147582 2 LOUVER...

Страница 34: ...01A R E 135312 GRILLE ASSY FRONT 3531A20121C 3531A20121B R 135313 GRILLE INLET 3530A20053A R 147581 LOUVER HORIZONTAL 4758A20008B R 147582 1 LOUVER VERTICAL 4758A20009A R 147582 2 LOUVER VERTICAL 4758...

Страница 35: ...UE12 2 03 Printed in the U S A Post Office Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4480 FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedri...

Отзывы: