OUTDOOR UNIT

1. Check if the piping connections are secure.

2. Check that the stems of 2-way valve and 3-way valve are closed

fully.

3. Connect the gauge manifold charge hose to the charging port

of the 3-way valve (side with the projection for pushing in the
valve core).

4. Open the low pressure side valve of the gauge manifold fully.

5. Operate the vacuum pump and start pump down.

6. Slowly loosen the flare nut of the 3-way valve and check if air

enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in
the outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and
do not operate it during the following work.

Set the unit on a strong stand, such as one made of concrete blocks to
minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trouble.

Connector cover removal

Remove the tapping screws.

Installing the connector cover

(1) After inserting the two front hooks, then insert the rear hook.
(2) Tighten the tapping screws.

7. Pump down the system for at least 15 minutes, then check if the

compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8. At the end of pump down, close the low pressure side gauge of

the gauge manifold fully and stop the vacuum pump.

9. Slowly loosen the valve stem of the 3-way valve. When the

compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose from
the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

 10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.14 ft•lbs (30 kgf•cm) until it
stops turning.)

 11.  Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

ELECTRICAL WIRING (OUTDOOR UNIT)

1. Remove the screws, then remove the control box cover.
2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut.
3. Connect inter-unit wire harness and power supply to the terminal.

 Refer to the wiring diagram

4. Use the screws to install the control box cover.

Tightening torque

Blank cap (2-way valve) 14.75 to 18.44 ft•lbs (200 to 250 kgf•cm)

Blank cap (3-way valve) 22.12 to 25.81 ft•lbs (300 to 350 kgf•cm)

Charging port cap

7.37 to 8.85 ft•lbs (100 to 120 kgf•cm)

LO

HI

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg
-1 bar)

High
pressure
side valve
(closed)

Low pressure
side valve

Blank cap

Charge
hose

Vacuum pump

2-way valve

Valve stem

Charge hose

Charging port cap

Charging port

Gauge manifold

Compound pressure gauge

Pressure gauge

 

CAUTION

(1) Refrigerant must not be discharged into atmos-

phere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

Tapping screw

Rear hooks

Connector cover

Front hooks

 

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may

exposed to strong wind, fasten it securely.

WARNING

Be sure to comply with local codes while run-
ning the wire from the indoor unit to the outdoor
unit (size of wire and wiring method, etc. ).

Every wire must be connected firmly.

No wire should be allowed to touch refrigerant
tubing, the compressor or any moving part.

Loose wiring may cause the terminal to over-
heat or result in unit malfunction. A fire hazard
may also exist. Therefore, be sure all wiring is
tightly connected.

Connect wires to the matching numbers of ter-
minals.

NOTE:

Connector trade size for this unit is 1/2” (12.7 mm). The connector
can be bought at a hardware store. Refer to 

How to connect wir-

ing to the terminals

 for instructions on connecting depending on

the wire type you are using.

The fuse located in the outdoor unit provides power supply pro-
tection and may blow when power is applied if the system has
been incorrectly wired.

Lock nut

Cord Clamp

Conduit
connector

Power supply

Inter-unit
wire harness

Indoor unit

Terminal

Grounding line

Control line

(Inter Unit)
Power line

DISCONNECT
SWITCH
(FIELD SUPPLY)

Outdoor unit

Terminal

POWER SUPPL

Y

1 phase, 208/230V

G

G

1

1

G

G

3

3

2

2

1

1

2

2

3

3

208/230V

208/230V

208/230V

208/230V

208/230V

208/230V

5

5

(L)(L

)

(N)(N

)

4

4

Earth screw

Indoor unit
terminal block

Outdoor unit
terminal block

Disconnect switch

Earth screw

Power supply line

1

2

3

4

1

2

3

4

5

G

G

Содержание MW24C3F

Страница 1: ...unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drippin...

Страница 2: ...trol box cover 2 Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut 3 Connect inter unit wire harness and power supply to the terminal Refer to the wiring dia...

Страница 3: ...usty 3 Do not install the unit where people pass 4 Take your neighbors into consideration so that they are not dis turbed by air blowing into their windows or by noise 5 Providethespaceshowninthefigur...

Страница 4: ...ormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage REMOTE CONTROL UNIT INSTALLATION 1 REMOTE CONTROL UNIT HOLDER...

Страница 5: ...cer CONNECTING THE PIPING CONNECTION 1 Install the outdoor unit wall cap supplied with the optional installation set or procured at the site to the wall pipe 2 Connect the outdoor unit and indoor unit...

Страница 6: ...3 way valve when the reading on the compound pressure gage becomes 0 05 0 MPa 0 5 0 kg cm2 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation Press the...

Страница 7: ...4 Shape the loop wire properly place it on the terminal board and tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cut the wire end with a wire cutter or wire cuttin...

Страница 8: ......

Отзывы: