PB
TROUBLESHOOTING
Protection Circuit Fault Isolation
Protection diagnosis of the complete machine (all types of protection during operation, i.e. under-voltage, over-voltage and
overcurrent protection)
Note:List all types of protection that may occur to the complete machine and describe the conditions and signs of the start, course
and end of such protection.
Voltage protection
Protection against AC input over-voltage/under-voltage
1.Conditions for protection against AC input over‑voltage/under‑voltage:
If the input AC voltage is greater than “protective over‑voltage value” or less than “protective under‑voltage value” for five seconds,
over‑voltage/under‑voltage protection starts. (E6)
2.Protection actions against AC input over‑voltage/under‑voltage
The system stops operation.
3. Conditions for ending AC input over‑voltage/under‑voltage:
If the input AC voltage is lower than “the protective over‑voltage value” ‑10V, or higher than “the protective under‑voltage value”
+10V, the over‑voltage/under‑voltage protection will be released.
Current protection:
1.Protection against over‑current
Conditions for over‑current protection: if the current is equal to or greater than “current value for starting the refrigeration current
protection (E2 value)” for six seconds, over‑current protection starts.
Protection actions against over‑current: indoor display screen and outdoor indicator give indications, the compressor and outdoor
fan stop, but indoor fan runs normally.
Condition for ending over‑current protection: when the current drops below “current value for releasing the refrigeration current
protection (E2 value)”, over‑current protection will be released.
2.Frequency decreasing for over‑current
Conditions for over‑current frequency decreasing: if the current is equal to or greater than “current value for starting the
refrigeration current protective frequency decreasing (E2 value)”, over‑current frequency decreasing starts.
Over‑current frequency decreasing actions: the compressor will decrease frequency at rate of (E2 value)Hz/S. The indoor and
outdoor fans run.
Conditions for ending over‑current frequency decreasing: when the current drops below “current value for starting the refrigeration
current protective prohibition of frequency rising (E2 value)”, over‑current under‑clocking will be released.
*Is the limit auto‑reset*
3.Prohibition of frequency increasing of compressor exhausting
Conditions for prohibition of frequency rising of compressor discharge
Condition 1: in the case of frequency decreasing of compressor discharge, the discharge temperature of the compressor drops below
39.2F
Condition 2: in normal operation, the discharge temperature of compressor reaches 41F.
Either of the above two conditions is met, prohibition of frequency rising of compressor discharge begins.
Actions relates to prohibition of frequency rising of compressor discharge: the frequency of compressor maintains at the current
level, which may decrease as the case requires while cannot rise. The indoor and outdoor fans run.
Condition for ending prohibition of frequency rising of compressor discharge: if the temperature of compressor discharge rises
above 42.8F, prohibition of frequency rising of compressor discharge will be released.
4. Prohibition of frequency for anti-overload of outdoor coiled pipe (cooling condenser temperature high) – To prevent compressor
overload from tripping.
Condition for anti‑overload prohibition of frequency of outdoor coil pipe: in the case of anti‑overload frequency decreasing of outdoor
coiled pipe, anti‑overload prohibition of frequency of the unit begins when the temperature of outdoor coiled pipe drops below “the
anti‑overload frequency decreasing temperature of outdoor coiled pipe”.
Actions relates to anti‑overload prohibition of frequency of outdoor coiled pipe: the frequency of compressor maintains at the current
level, which may decrease as the case requires while cannot rise. The indoor and outdoor fans run.
Condition for ending anti‑overload prohibition of frequency of outdoor coiled pipe: if the temperature of outdoor coiled pipe drops
below “temperature to release the anti‑overload state of outdoor coiled pipe”, anti‑overload prohibition of frequency of outdoor
coiled pipe will be released.
Содержание FPCG0912
Страница 9: ...9 INTRODUCTION Product Appearance Cassette type Model Btu h Indoor Unit Out door Unit 24K 36K...
Страница 119: ...119 OPERATION Figure 301 Remote Control Operation and Function...
Страница 132: ...132 INSTALLATION Outdoor Units Fig 432 Fig 433...
Страница 140: ...140 MAINTENANCE...
Страница 163: ...163 COMPONENTS TESTING Fan Motor Fig 605...
Страница 200: ...200 WIRINGDIAGRAMS 7k Wall Units...
Страница 203: ...203 WIRING DIAGRAMS 24k Outdoor Units Electric wiring diagram 1993419 E...
Страница 204: ...204 WIRING DIAGRAMS 36k Outdoor Units...
Страница 205: ...205 PARTSCATALOG 18K Outdoor Condensor...
Страница 206: ...206 PARTSCATALOG 18K Outdoor Condensor...
Страница 207: ...207 PARTSCATALOG 18K Outdoor Condensor...
Страница 210: ...210 PARTSCATALOG 24K Outdoor Condensor Figure 901A 4 C 4x12...
Страница 211: ...211 PARTS CATALOG 24K Outdoor Condensor Figure 901B 1 1 1 I I i I I _ ____ I L i...
Страница 212: ...212 PARTS CATALOG 24K Outdoor Condensor Figure 901C II c tx12 II...
Страница 215: ...215 PARTS CATALOG 36K Outdoor Condensor Figure 902A 11 I i i r I h 1 1 I I _ I 11 12 11 I I I Ii I 1 I Ii L l_ ii I _...
Страница 216: ...216 PARTS CATALOG 36K Outdoor Condensor Figure 902B i...
Страница 217: ...217 PARTS CATALOG 36K Outdoor Condensor Figure 902C u...
Страница 222: ...222 PARTS CATALOG 9K 12K Indoor Cassette Figure 904 B M4x08...
Страница 226: ...226 PARTS CATALOG 24K INDOOR CASSETTE FIgure 906 0 1 A 4X8 13 19 NOTE I I r 1 I I iA 4X12 t I 9 5X53 11 4 _ _ A 4X10...
Страница 228: ...228 PARTS CATALOG 9K 12K DUCTED INDOOR Figure 907a...
Страница 229: ...229 Figure 907b PARTS CATALOG 9K 12K DUCTED INDOOR...
Страница 230: ...230 Figure 907c PARTS CATALOG 9K 12K DUCTED INDOOR...
Страница 232: ...232 PARTS CATALOG 18K Ducted Indoor Figure 908a...
Страница 233: ...233 PARTS CATALOG 18K Ducted Indoor Figure 908b...
Страница 234: ...234 PARTS CATALOG 18K Ducted Indoor Figure 908c...
Страница 236: ...236 PARTS CATALOG 24k Ducted Indoor Figure 909a _ _ _ 1...
Страница 237: ...237 PARTS CATALOG 24k Ducted Indoor Figure 909b _ _ __lllfllllllllllalll l rla _ fllll _ 2...
Страница 238: ...238 PARTS CATALOG 24k Ducted Indoor Figure 909c A __ _ _ C llillllp_ ___ 111 11111111111A11 _ lffllllllal 3...