127
PB
OPERATION
24k and 36k Control Mode
7. Outdoor four-way Valve Control
Four‑way valve of the outdoor machine shuts down when cooling but starts when heating. The operation of heating defrosting refers
to defrosting operation and, when the heating remote shutdown, the four‑way valve disconnects in 50s when the compressor stops
working.
8. Start-up Protection
To prevent compressor from restart frequently in the condition that system pressure has not been completely balanced, it can’t be
restarted within 3 minutes.
9. Pressure Protection
Pressure switch is normally kept open. When the pressure grows too high, the pressure switch will close and will enter pressure
protection control. The frequency will automatically decrease. If the pressure is still unable to return to normal condition after
decreasing frequency, compressor will stop and report the fault code of pressure protection.
Содержание FPCG0912
Страница 9: ...9 INTRODUCTION Product Appearance Cassette type Model Btu h Indoor Unit Out door Unit 24K 36K...
Страница 119: ...119 OPERATION Figure 301 Remote Control Operation and Function...
Страница 132: ...132 INSTALLATION Outdoor Units Fig 432 Fig 433...
Страница 140: ...140 MAINTENANCE...
Страница 163: ...163 COMPONENTS TESTING Fan Motor Fig 605...
Страница 200: ...200 WIRINGDIAGRAMS 7k Wall Units...
Страница 203: ...203 WIRING DIAGRAMS 24k Outdoor Units Electric wiring diagram 1993419 E...
Страница 204: ...204 WIRING DIAGRAMS 36k Outdoor Units...
Страница 205: ...205 PARTSCATALOG 18K Outdoor Condensor...
Страница 206: ...206 PARTSCATALOG 18K Outdoor Condensor...
Страница 207: ...207 PARTSCATALOG 18K Outdoor Condensor...
Страница 210: ...210 PARTSCATALOG 24K Outdoor Condensor Figure 901A 4 C 4x12...
Страница 211: ...211 PARTS CATALOG 24K Outdoor Condensor Figure 901B 1 1 1 I I i I I _ ____ I L i...
Страница 212: ...212 PARTS CATALOG 24K Outdoor Condensor Figure 901C II c tx12 II...
Страница 215: ...215 PARTS CATALOG 36K Outdoor Condensor Figure 902A 11 I i i r I h 1 1 I I _ I 11 12 11 I I I Ii I 1 I Ii L l_ ii I _...
Страница 216: ...216 PARTS CATALOG 36K Outdoor Condensor Figure 902B i...
Страница 217: ...217 PARTS CATALOG 36K Outdoor Condensor Figure 902C u...
Страница 222: ...222 PARTS CATALOG 9K 12K Indoor Cassette Figure 904 B M4x08...
Страница 226: ...226 PARTS CATALOG 24K INDOOR CASSETTE FIgure 906 0 1 A 4X8 13 19 NOTE I I r 1 I I iA 4X12 t I 9 5X53 11 4 _ _ A 4X10...
Страница 228: ...228 PARTS CATALOG 9K 12K DUCTED INDOOR Figure 907a...
Страница 229: ...229 Figure 907b PARTS CATALOG 9K 12K DUCTED INDOOR...
Страница 230: ...230 Figure 907c PARTS CATALOG 9K 12K DUCTED INDOOR...
Страница 232: ...232 PARTS CATALOG 18K Ducted Indoor Figure 908a...
Страница 233: ...233 PARTS CATALOG 18K Ducted Indoor Figure 908b...
Страница 234: ...234 PARTS CATALOG 18K Ducted Indoor Figure 908c...
Страница 236: ...236 PARTS CATALOG 24k Ducted Indoor Figure 909a _ _ _ 1...
Страница 237: ...237 PARTS CATALOG 24k Ducted Indoor Figure 909b _ _ __lllfllllllllllalll l rla _ fllll _ 2...
Страница 238: ...238 PARTS CATALOG 24k Ducted Indoor Figure 909c A __ _ _ C llillllp_ ___ 111 11111111111A11 _ lffllllllal 3...