background image

CONDITION

1. Dehumidifier does not start. (Both

compressor and fan motor do not

operate.)

2. Motor runs but compressor does not

run.

3. Does not defrost

 control

4. Insufficient dehumidification

CAUSE

No power

Poor plug contact at outlet.
Bucket is full.

Humidity control is in Off position

Wire disconnected or loose

Capacitor.

(Discharge capacitor before testing.)

Voltage (115V ± 10%)

Wiring

Defrost control 

Capacitor

(Discharge capacitor before servicing.)

Compressor

Overload protector (OLP)

Defrost control is defective.
Low relative humidity
Poor air circulation

H/E clogged with dust and dirt
Air filter is dirty.
Motor is not operating.

REMEDY

Check power supply at outlet.

Correct if none.
Install plug properly or replace it.
If Auto Shut Off lights, empty the bucket

and replace properly.
Turn the humidity control switch toward

Max.(35degrees,R.H.)
Connect wire. Refer to wiring diagram for

terminal identification. Repair or replace

loose terminal.
Test capacitor.

Replace if not within ±10% of

manufacturer's rating. Replace if shorted,

open, or damaged.
It must be between 103.5V and 126.5V. If

not within limits, call an electrician
Check the wire connections; If loose,

repair or replace the terminal. If the wires

are disconnected, refer to wiring diagram

for identification, and replace the wires.

Check the wire connections; If not

according to the wiring diagram, correct

the connections.
The Defrost 

c

ontrol senses frost build-up

on the evaporator coil and automatically

shuts off the compressor. The fan

continues to run, drawing air across the

coil, and melting the frost. When the coil is

defrosted, the compressor automatically

restarts, and dehumidifying resumes.
Check the capacitor.

Replace if not within ±10% of

manufacturer's rating. Replace if shorted,

open, or damaged.
Check the compressor for open circuit or

ground. If open or grounded, replace the

compressor.
Check the compressor OLP if externally

mounted. Replace if open. (If the

compressor temperature is high, remove

OLP, cool, and retest.)
Check defrost control, replace it.
Turn dehumidifier off.
Move dehumidifier to obtain free and

unobstructed air circulation.
Clean evaporator and/or condenser assembly
Clean it.
Check Motor, repair or replace it.

—1

4

4. TROUBLESHOOTING GUIDE 

Содержание D30C

Страница 1: ...r S ervice and Parts P Manual DehumSvcParts 06 05 D30C D40C D50C D65C FA N S PE E D TIM E R Hig h Low 4h r On Of f 2h r On Of f HU MI DIT Y CON TR OL BUC K E T FUL L POW E R HU MID ITY S E TT IN G Au...

Страница 2: ...3 1 3 CABINET AND CONTROL BOX 7 3 2 CONTROL PARTS 8 3 2 1 POWER CORD ASSEMBLY 8 3 2 2 SENSOR ASSEMBLY 8 3 2 3 PWB PCB ASSEMBLY MAIN 8 3 2 4 CAPACITOR 8 3 2 5 MICRO SWITCH ASSEMBLY 8 3 2 6 CONTROL PAN...

Страница 3: ...upply before servicing or replacing any component Do not cut off the grounding prong or alter the plug in any manner 1 2 FEATURES AND DIMENSIONS 1 2 1 FEATURES Quiet operation High efficiency Adjustab...

Страница 4: ...o be emptied Power Operation starts when this button is pressed and stops when the button is pressed again Fan Speed This controls the speed of the airflow High Fan speed is set to high Low Fan speed...

Страница 5: ...TS N NOT SERVICE PARTS Q TY PER SET 1 1 1 1 1 1 1 1 1 RE MARKS S S S S S S S S S 1 2 3 4 5 6 7 8 9 DESCRIPTION POWER CORD ASSEMBLY MOTOR ASSEMBLY CAPACITOR COMPRESSOR SET OLP PWB PCB ASSEMBLY DISPLAY...

Страница 6: ...RKS S S S S S S S S S 1 2 3 4 5 6 7 8 9 DESCRIPTION POWER CORD ASSEMBLY MOTOR ASSEMBLY CAPACITOR COMPRESSORT SET OLP PWB PCB ASSEMBLY DISPLAY SENSOR ASSEMBLY SWITCH ASSEMBLY MICRO PWB PCB 0ASSEMBLY MA...

Страница 7: ...l box See Figure 7 3 Remove 8 screws on all sides of the cabinet 4 Lift the cabinet from the base See Figure 7 5 Remove a screw fasten the ground wire on the inside of control box 6 Remove 1 screw tha...

Страница 8: ...ct the switch wires from the micro switch assembly See Figure 10 3 2 3 PWB PCB ASSEMBLY MAIN 1 Disconnect all wires of the motor and the compressor from PWB PCB ASSEMBLY MAIN 2 Remove the screw which...

Страница 9: ...ISPLAY to the display cover 3 2 7 FAN AND MOTOR 1 Turn the nut left and pull out the fan by hands carefully 2 Remove 2 screws that fasten H E 3 Lift the H E and turn the H E around 45 degree clockwise...

Страница 10: ...ischarge and the Suction tube connected to the compressor 3 Remove 2 screws that fasten the heat exchanger 4 Unfasten 2 screws that secure the shroud on the sides then lift shroud from the drain pan S...

Страница 11: ...erconnecting tubes of the evaporator and condenser carefully 6 Remove the H E assembly from the shroud See Figure 19 7 Unbraze the capillary tube at the connections of the condenser and evaporator See...

Страница 12: ...rigeration cycle systems are charged from the High side If the total charge cannot be put in the High side the balance will be put in the suction line through the access valve which you installed as t...

Страница 13: ...eal leak detector tubing cutter hand tools to remove components service valve B A COMPRESSOR COMPOUND GAUGE MANIFOLD GAUGE SEE INSETS BELOW EXTERNAL VACUUM PUMP CHARGING CYLINDER HI LOW A B A B C COND...

Страница 14: ...ace if shorted open or damaged It must be between 103 5V and 126 5V If not within limits call an electrician Check the wire connections If loose repair or replace the terminal If the wires are disconn...

Страница 15: ...t Replace compressor Tighten them If knocking sounds continue when running or loose replace the motor If the motor hums or noise appears to be internal while running replace motor assembly The bucket...

Страница 16: ...MODEL D30C 354210 554030 130900 349600 149980 162615 346811 359012 264110 148390 144410 752140 436500 249950 266011 130411 435300 330870 135312 W0CZZ 268714 35211A 552111 567502 554160 550140 352113...

Страница 17: ...0C W0CZZ 162615 268714 264110 249950 352113 552111 550140 567502 554160 354210 554030 135312 130900 349600 149980 346811 359012 148390 144410 752140 152302 436500 130401 268712 266011 238310 435300 33...

Страница 18: ...0C 35211A 552111 352113 567502 554160 550140 W0CZZ 162615 268714 264110 249950 354210 554030 135312 130900 349600 149980 346811 359012 148390 144410 752140 152302 436500 130401 268712 266011 238310 43...

Страница 19: ...5C 35211A 352113 552111 567502 554160 550140 W0CZZ 162615 268714 264110 249950 354210 554030 135312 130900 349600 149980 346811 359012 148390 144410 752140 152302 436500 130401 268712 266011 238310 43...

Страница 20: ...BLY MAIN 67307604 346811 MOTOR ASSEMBLY 67500128 35211A TUBE ASSEMBLY SUCTION 67400210 352113 TUBE ASSEMBLY DISCHARGE 67400212 552111 TUBE ASSEMBLY CAPILLARY 67302126 354210 EVAPORATOR ASSEMBLY 674001...

Страница 21: ...PWB PCB ASSEMBLY MAIN 67307604 346811 MOTOR ASSEMBLY 67500081 35211A TUBE ASSEMBLY SUCTION 67400211 352113 TUBE ASSEMBLY DISCHARGE 67500091 552111 TUBE ASSEMBLY CAPILLARY 67500094 354210 EVAPORATOR AS...

Страница 22: ...PWB PCB ASSEMBLY MAIN 67307604 346811 MOTOR ASSEMBLY 67500081 35211A TUBE ASSEMBLY SUCTION 67500208 352113 TUBE ASSEMBLY DISCHARGE 67400213 552111 TUBE ASSEMBLY CAPILLARY 67400215 354210 EVAPORATOR AS...

Страница 23: ...PWB PCB ASSEMBLY MAIN 67307604 346811 MOTOR ASSEMBLY 67500129 35211A TUBE ASSEMBLY SUCTION 67400209 352113 TUBE ASSEMBLY DISCHARGE 67400214 552111 TUBE ASSEMBLY CAPILLARY 67302127 354210 EVAPORATOR AS...

Страница 24: ...ed in the U S A Post Office Box 1540 4200 N Pan Am E xpressway S an Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4480 FR IE DR ICH AIR CONDITIONING CO Visit our web site at www friedrich com Us e...

Отзывы: