—1
5
—
CONDITION
5. Noisy operati
on
6. Water drips
7. Compressor cycles on overload
protector. (OLP)
CAUSE
Fan
Loose foreign material inside the housing.
Tube hits frame.
Fan blade hits frame
Internal compressor noise.
Loose set screws
Worn bearings of Motor Assembly
The bucket is not installed properly.
Connection may be loose.
Leak in bucket
Water drips when bucket removed for
emptying.
Bucket overflows.
High or low line voltage. (115V ± 10%)
Poor air circulation.
Heat Exchange
r
clogged with dust or dirt.
Motor
Short circuit or ground in electrical circuit
Unit pressures not equalized
Capacitor
Wiring
Refrigeration system
Stuck compressor
Overload protector (OLP)
REMEDY
If cracked, out of balance, or partially
missing, replace it
Remove it.
Adjust tubing
routine
carefully.
Check Motor Mount. If loose, tighten it.
Replace compressor.
Tighten them.
If knocking sounds continue when running
or loose, replace the motor. If the motor
hums or noise appears to be internal while
running, replace motor assembly.
The bucket should be properly positioned
on the hangers of the drain pan.
Check connection and repair.
Replace bucket.
Before removing bucket, the unit should
be turned off.
Check micro switch and float.
Check line voltage. It must be between
103.5V and 126.5V volts.
If intermittent, provide new supply.
Move dehumidifier for free and
unobstructed air flow.
Clean dust or dirt on the Heat Exchange
r
.
If not running, determine the cause.
Replace if required.
Check electrical circuit. Repair.
Allow 2 or 3 minutes for pressure to
equalize before starting compressor.
Test the capacitor.
Check the terminals. If loose, repair or
replace.
Check the system for a restriction.
Check compressor, replace compressor
Check OLP, if externally mounted.
Replace if open. (If the compressor
temperature is high, remove the OLP,
cool, and retest.)