background image

RAR3500

13

GB  

General Instructions

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The guarantee is only valid if the units 
are used in the manner intended by the 
manufacturer and in accordance with the 
Frico mounting and operating instructions.

Application area

The RAR3500 air curtain unit is supplied 
without heat, with electrical heating or hot 
water coil and is intended for installation 
above entrances and smaller doors up to 3.5 
metres in height.

RAR3500 is recessed in false ceilings above 

entrances.

Protection class: IP20

Operation

Air is drawn in from underneath and blown 
out downwards towards the entrance so that 
it shields the door opening and minimises 
heat loss. To get the best curtain effect the 
unit must extend the full width of the door 
opening. 

The grille for directing exhaust air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
cold air. 

The air speed is adjusted to the desired 

airflow. 

The efficiency of the air curtain(s) depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure.  

NOTE! Negative pressure in the building 
considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced!

Installation

The air curtain unit is installed horizontally 
with the supply air grille facing downwards as 
close to the door as possible, concealed in the 
false ceiling. The only visible part of the unit 
is the underside that is level with the ceiling.

For the protection of wider doorways, 

several units can be mounted next to each 
other. 

Ensure that the service hatch is accessible 

and can be fully opened.

1. The mounting brackets are fixed to the unit 

during transport. Slacken these off, turn 
them around and screw into place on the 
unit according to figure 1.

2. Hang up on threaded bars (M8) according to 

figure 2a (not included).

3. Adjust the height using the lower nut so 

that the frame is on the level of the ceiling. 
Lock using the upper nut.

Mounting on threaded bars inside unit.

1. The mounting brackets are fixed to the 

unit during transport. Loosen them and 
screw them into place inside the unit in the 
intended holes.

2. Hang up on threaded bars (M8) according 

to figure 2b (not included). Note that 
the brackets are at different heights and 
threaded rods shall be of different lengths.

3. Adjust the height using the lower nut so 

that the frame is on the level of the ceiling. 
Lock using the upper nut.

Electrical installation

The installation, which should be preceded by 
an omnipolar switch with a contact separation 
of at least 3 mm, should only be wired by a 
competent electrician and in accordance with 
the latest edition of IEE wiring regulations.

The control system is pre-installed in the 

aircurtain with an integrated control board, 
(see fig 5). 

PLS is supplied pre-programmed with quick-

release connections. 

Modular cables are connected to the control 

board, by opening the service hatch, as shown 
in fig. 3 and 5. See manual for PLS.

1. The service hatch is opened by loosening 

the snap fixings located on the down side 
(turn 90°). See fig. 3.

2. RAR3500A: The unit is fitted with cable and 

plug.

  RAR3500W: The unit is fitted with cable 

and plug.

Assembly and operating instructions

Содержание RAR3500 Series

Страница 1: ...Original instructions RAR3500 GB ...

Страница 2: ...A 302 B 595 325 532 D 638 RAR3500 2 Mounting Fig 1 The mounting brackets on delivery Type A mm B mm C mm RAR3510 1057 1016 1067 RAR3515 1567 1526 1577 RAR3520 2073 2031 2083 ...

Страница 3: ...RAR3500 3 Fig 2a Mounting on threaded bars Mounting Fig 2b Mounting on threaded bars inside unit ...

Страница 4: ...hatch Fig 5 PLS inside unit SIRe RAR3500 4 Water connections Fig 4 The water coil is connected inside the unit through holes which are made during installation on the upper side or through the side of the unit possible places are marked with punch marks ...

Страница 5: ...3 m CC605 5 m CC610 10 m CC615 15 m CC403 30 m CC405 50 m CC410 10 m CC415 15 PLS C PLSB PLSAC PLSRTX PLSUR CC CJ4 CJ6 VOT Type Ø VKF15LF DN15 VKF15NF DN15 VKF20 DN20 VKF25 DN25 VKF32 DN32 SD230 BPV10 VOT15 DN15 VOT20 DN20 VOT25 DN25 VKF SD230 BPV10 VLSP RAR3500 5 ...

Страница 6: ...Transformer 230V 200V 170V 145V 120V 100V N Blue Black AR3520A W AR3515A W SIReB1 AR3510A W Wiring diagrams RAR3500 Internal wiring diagram RAR3500A W RAR3500 6 ...

Страница 7: ... Black Grey Blue Transformer 230V 200V 170V 145V 120V 100V N Blue Black AR3520E18 AR3515E14 SIReB1 AR3510E09 400V3 230V AR3510E09 3515E14 AR3520E18 Wiring diagrams RAR3500 Internal wiring diagram RAR3500E RAR3500 7 ...

Страница 8: ... L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional L 2m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC PLSB2 PLSRTX optional CC6XX CC6XX max 10 m PLSUB1 PLSB2 PLSB2 CC6XX RAR3500 8 ...

Страница 9: ... Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional SD230 SD230 SD230 L 1 5m L 2m PLSB2 PLSRTX optional CC6XX CC6XX max 10 m PLSUB1 PLSB2 PLSB2 CC6XX PLS Basic RAR3500W RAR3500 9 ...

Страница 10: ...11 8 28 7 35 5 0 35 16 4 min 2200 12 7 38 0 10 1 7 17 40 7 0 21 6 5 Supply water temperature 60 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 60 40 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPa Output 2 kW Outlet air temp C Water flow l s Pressure drop kPa RAR3510W max 2300 9 4 29 9 0 11 5 2 min 1100 ...

Страница 11: ...0 08 0 6 9 3 35 5 0 11 1 RAR3520WLL max 4800 22 9 29 0 27 2 5 23 7 32 5 0 29 2 8 min 2200 10 7 27 0 11 0 6 13 1 35 4 0 16 1 Supply water temperature 45 C Room temperature 18 C Outlet air temperature 32 C 1 Water temperature 45 35 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPa Output 2 kW Outlet air temp C Water flow l s Pressur...

Страница 12: ... Weight kg RAR3510E09 4 5 9 1100 2300 25 12 42 62 230V 2 45 A 400 V3 13 A 1057 42 RAR3515E14 7 13 5 1550 3400 27 13 43 63 230V 3 5 A 400 V3 19 5 A 1567 58 RAR3520E18 9 18 2200 4800 25 11 45 64 230V 5 2 A 400 V3 26 A 2073 78 RAR3500 W with water heat coil for low water temperature 480 C Type Output 4 kW Airflow 1 m3 h t 3 4 C Water volume l Sound level 2 dB A Voltage V Amperage A Length mm Weight k...

Страница 13: ... ceiling For the protection of wider doorways several units can be mounted next to each other Ensure that the service hatch is accessible and can be fully opened 1 The mounting brackets are fixed to the unit during transport Slacken these off turn them around and screw into place on the unit according to figure 1 2 Hang up on threaded bars M8 according to figure 2a not included 3 Adjust the height...

Страница 14: ...of the unit possible places are marked with punch marks The connections to the heating coil must be equipped with shut off valves to allow problem free removal Adjustment of the air curtain and air flow The direction and speed of the air flow should be adjusted considering the load on the opening Pressure forces affect the air stream and make it bend inwards into the premises when the premises are...

Страница 15: ...ctric heater coil RAR3500E 1 Mark and disconnect the cables to the electric heater coil 2 Remove the mounting screws securing the electric heater coil in the unit and lift the electric heater coil out 3 Install the new electric heater coil in reverse order to the above Replacing the water coil RAR3500W 1 Shut off the water supply to the unit 2 Disconnect the connections to the water coil 3 Remove ...

Страница 16: ...y be run for a short time when it is not being used for extended periods of time Safety For all installations of electrically heated products should a residual current circuit breaker 300 mA for fire protection be used Keep the areas around the air intake and exhaust grilles free from possible obstructions During operation the surfaces of the unit can be hot The unit must not be fully or partially...

Страница 17: ...Art no 112794 20160218 LE CH Technical Support tel 46 313368600 ...

Отзывы: